Heat Pump - Installation and Operation Manual
Page 1
51300102101 RevB Heat Pump For In-Ground Pool & Spa Installations Installation and Operation Manual Contents Safety Instructions 1 Before You Begin 4 Installation 9 Electrical Wiring 14 Operation 15 Maintenance & Service.......21 Troubleshooting 24 Replacement Parts 27 Hayward Industries 1415 Vantage Park Dr., Suite 400 Charlotte, NC 28203 Phone: (908) 355-7995 www.hayward.com USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
51300102101 RevB Heat Pump For In-Ground Pool & Spa Installations Installation and Operation Manual Contents Safety Instructions 1 Before You Begin 4 Installation 9 Electrical Wiring 14 Operation 15 Maintenance & Service.......21 Troubleshooting 24 Replacement Parts 27 Hayward Industries 1415 Vantage Park Dr., Suite 400 Charlotte, NC 28203 Phone: (908) 355-7995 www.hayward.com USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Heat Pump - Installation and Operation Manual
Page 2
...damage and if ignored presents a potential hazard. National Electric Code (NEC) in Canada. SAVE THESE INSTRUCTIONS 1 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS Basic safety precautions should always be followed, including the following signal... are important but not related to follow instructions can cause death, serious injury and/or property damage. When you see this manual, look for manufacturer information. NOTICE - This is the safety-alert symbol. Conformance With Codes: The heater shall be installed ...
...damage and if ignored presents a potential hazard. National Electric Code (NEC) in Canada. SAVE THESE INSTRUCTIONS 1 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS Basic safety precautions should always be followed, including the following signal... are important but not related to follow instructions can cause death, serious injury and/or property damage. When you see this manual, look for manufacturer information. NOTICE - This is the safety-alert symbol. Conformance With Codes: The heater shall be installed ...
Heat Pump - Installation and Operation Manual
Page 3
... suction outlet component is recommended. ! Failure to a gas supply line. 2 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS o Dual suction fittings shall not be properly secured to use or climb on this manual and on the equipment. o In addition two or more than 50 PSI. WARNING - Suction...entrapment as the filtration system, pumps, and heaters must be in filter upper body. All electrical wiring MUST be in open filter manual air relief valve. Read, Understand, and Follow all times. Suction Entrapment Hazard. Hazardous Pressure. Pool and spa water heating and circulation...
... suction outlet component is recommended. ! Failure to a gas supply line. 2 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS o Dual suction fittings shall not be properly secured to use or climb on this manual and on the equipment. o In addition two or more than 50 PSI. WARNING - Suction...entrapment as the filtration system, pumps, and heaters must be in filter upper body. All electrical wiring MUST be in open filter manual air relief valve. Read, Understand, and Follow all times. Suction Entrapment Hazard. Hazardous Pressure. Pool and spa water heating and circulation...
Heat Pump - Installation and Operation Manual
Page 5
... NO Pool Closing Time? Verify that the installation was done according to Expect When Operating Your Pool Heater INSTALLATION - Before You Begin What to owner's manual instructions. NO Open Bypass (Figure A) and Drain the Heater Heating Needed? Verify pH level once a week. - If the heat exchanger is required for more often... on Touch Pad IMPORTANT FOR THE HEALTH OF YOUR FAMILY AND FOR YOUR POOL HEATER - Route all pool water piping, but do -it 4 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS YES Connect Water Piping to let the water circulate in the unit.
... NO Pool Closing Time? Verify that the installation was done according to Expect When Operating Your Pool Heater INSTALLATION - Before You Begin What to owner's manual instructions. NO Open Bypass (Figure A) and Drain the Heater Heating Needed? Verify pH level once a week. - If the heat exchanger is required for more often... on Touch Pad IMPORTANT FOR THE HEALTH OF YOUR FAMILY AND FOR YOUR POOL HEATER - Route all pool water piping, but do -it 4 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS YES Connect Water Piping to let the water circulate in the unit.
Heat Pump - Installation and Operation Manual
Page 12
...Fibermesh 3" Conc. Pad by local codes. Concrete Screw w/ S.S. Do not use the specified hardware shown in Figure 8. 11 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS The minimum flow rate is set, note the position and remove the valve handle to ensure sufficient heat removal from the ...require unnecessarily high pumping energy. GALV. Failure to be accomplished by temporarily installing a flow meter on the water flow. Once the manual bypass valve is to install an External Bypass Assembly with the exception of; To complete the installation use with a minimum length ...
...Fibermesh 3" Conc. Pad by local codes. Concrete Screw w/ S.S. Do not use the specified hardware shown in Figure 8. 11 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS The minimum flow rate is set, note the position and remove the valve handle to ensure sufficient heat removal from the ...require unnecessarily high pumping energy. GALV. Failure to be accomplished by temporarily installing a flow meter on the water flow. Once the manual bypass valve is to install an External Bypass Assembly with the exception of; To complete the installation use with a minimum length ...
Heat Pump - Installation and Operation Manual
Page 13
...pump and the pool) of Unit Gasket Union Connector Union Nut Gasket Union Connector Union Nut 12 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS CAUTION: Improperly adjusted manual bypass valves will not allow the raw chlorine to drain back to the heater if the flow rates are... not responsible for pressure switch adjustment in property damage. ! FIGURE 8: General Pad Plumbing Layout Filter Pool Heater Pool Pump Manual Isolation Valves Check Valve Manual Bypass Valve Chemical Loop Chemical Feeder From Pool or Spa To Pool or Spa ! However, if there is equipped with ...
...pump and the pool) of Unit Gasket Union Connector Union Nut Gasket Union Connector Union Nut 12 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS CAUTION: Improperly adjusted manual bypass valves will not allow the raw chlorine to drain back to the heater if the flow rates are... not responsible for pressure switch adjustment in property damage. ! FIGURE 8: General Pad Plumbing Layout Filter Pool Heater Pool Pump Manual Isolation Valves Check Valve Manual Bypass Valve Chemical Loop Chemical Feeder From Pool or Spa To Pool or Spa ! However, if there is equipped with ...
Heat Pump - Installation and Operation Manual
Page 14
.... F H 1. V S Notes: 1. H 3. Isolate the heat pump from the heat pump CONSUMER KIT adjacent to the unit to facilitate easy service procedures Pool (Parallel) H C R 13 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS Install bypass loop for each unit. Failure to operate the pressure safety switch when the pump is running. Install union style fittings... the pool/spa water, install a loop as gasfired or solar-powered devices must be generated by gas and solar units, isolating it with and without a manual bypass valve.
.... F H 1. V S Notes: 1. H 3. Isolate the heat pump from the heat pump CONSUMER KIT adjacent to the unit to facilitate easy service procedures Pool (Parallel) H C R 13 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS Install bypass loop for each unit. Failure to operate the pressure safety switch when the pump is running. Install union style fittings... the pool/spa water, install a loop as gasfired or solar-powered devices must be generated by gas and solar units, isolating it with and without a manual bypass valve.
Heat Pump - Installation and Operation Manual
Page 15
... WARNING: All electrical wiring MUST be made as shown in conformance with the latest edition of Electric Shock Review all wiring secured for this manual prior to , grounding, bonding and other general wiring procedures. ! NOTICE: Manufacturer does not recommend the use of swimming pool or spa...personal injury and/or may also cause property damage. ! FIGURE 13: Power Connections T2 T1 Contactor (Contacteur) L2 L1 14 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS There is a ground lug inside the heater cabinet, and a copy is created. The heater must be made in ...
... WARNING: All electrical wiring MUST be made as shown in conformance with the latest edition of Electric Shock Review all wiring secured for this manual prior to , grounding, bonding and other general wiring procedures. ! NOTICE: Manufacturer does not recommend the use of swimming pool or spa...personal injury and/or may also cause property damage. ! FIGURE 13: Power Connections T2 T1 Contactor (Contacteur) L2 L1 14 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS There is a ground lug inside the heater cabinet, and a copy is created. The heater must be made in ...
Heat Pump - Installation and Operation Manual
Page 19
...can switch to °F or °C. Once the heating mode has been programmed, it will be displayed for service 18 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS Fahrenheit Versus Celsius: The control will vary from 15 minutes to several hours depending on ambient air conditions. This time ...set point and the high limit temperature. Check TROUBLE SHOOTING SECTION in the mode that temperature was last selected (i.e. The fan will operate in this manual. 11. The heater will start : a. Push the "MENU" button (x3) until "F_C" is displayed. Heat Only Operation Automatic Reset Time:...
...can switch to °F or °C. Once the heating mode has been programmed, it will be displayed for service 18 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS Fahrenheit Versus Celsius: The control will vary from 15 minutes to several hours depending on ambient air conditions. This time ...set point and the high limit temperature. Check TROUBLE SHOOTING SECTION in the mode that temperature was last selected (i.e. The fan will operate in this manual. 11. The heater will start : a. Push the "MENU" button (x3) until "F_C" is displayed. Heat Only Operation Automatic Reset Time:...
Heat Pump - Installation and Operation Manual
Page 21
...temperatures in display. 8. When the unit starts, confirm that you can switch to operate for 10-15 minutes in this manual. 12. Allow the Heat Pump to °F or °C. Check TROUBLE SHOOTING SECTION in order for cooling mode. ...air is initiated. 1. Defrost Function: The Defrost function is provided to Performance Monitoring / Troubleshooting section in this manual or Call for five seconds, and will activate Heating or Cooling as shown in the mode that air is being...HE" is not exact and each unit will be displayed for service 20 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
...temperatures in display. 8. When the unit starts, confirm that you can switch to operate for 10-15 minutes in this manual. 12. Allow the Heat Pump to °F or °C. Check TROUBLE SHOOTING SECTION in order for cooling mode. ...air is initiated. 1. Defrost Function: The Defrost function is provided to Performance Monitoring / Troubleshooting section in this manual or Call for five seconds, and will activate Heating or Cooling as shown in the mode that air is being...HE" is not exact and each unit will be displayed for service 20 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Heat Pump - Installation and Operation Manual
Page 22
...the warranty. Adjustment Knob Two-Speed Pump: In a few cases the pressure from around the heater. 3. In these guidelines to leave this manual in water it remains vital that the heat exchanger be replaced. 5. Be sure to help maximize heater life: 1. Periodically check the fan discharge... a qualified service technician. The following factors are such that shrubs grow and in your heater and heat exchanger. 21 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS Remember that the required 1-pound minimum pressure cannot be run at high speed to compensate for long life when installed...
...the warranty. Adjustment Knob Two-Speed Pump: In a few cases the pressure from around the heater. 3. In these guidelines to leave this manual in water it remains vital that the heat exchanger be replaced. 5. Be sure to help maximize heater life: 1. Periodically check the fan discharge... a qualified service technician. The following factors are such that shrubs grow and in your heater and heat exchanger. 21 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS Remember that the required 1-pound minimum pressure cannot be run at high speed to compensate for long life when installed...
Heat Pump - Installation and Operation Manual
Page 23
... union and allow all air prior to check your system and if necessary, adjust the water pressure switch as described in WATER TESTING SECTION OF MANUAL. 2. Use a 4-way pool/spa water test kit to starting the heater. Use the following guidelines to the water pressure switch for proper ...to STANDBY mode using valves, then perform draining the heat exchanger. 1. Re-install the drain plug or reattach the water union. 22 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS 1. Make sure your pool/spa will keep the pool/spa safe and sanitary, and will result in the heater. In regions ...
... union and allow all air prior to check your system and if necessary, adjust the water pressure switch as described in WATER TESTING SECTION OF MANUAL. 2. Use a 4-way pool/spa water test kit to starting the heater. Use the following guidelines to the water pressure switch for proper ...to STANDBY mode using valves, then perform draining the heat exchanger. 1. Re-install the drain plug or reattach the water union. 22 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS 1. Make sure your pool/spa will keep the pool/spa safe and sanitary, and will result in the heater. In regions ...
Heat Pump - Installation and Operation Manual
Page 24
...the hole in the piping are properly positioned, and the time clocks are properly set point to complete the procedure. 23 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS If adjustment is needed, the procedure is recommended that a PERIODIC INSPECTION also be certain that could result in the ... from the printed circuit board. 4. Turn pump, and heater power "OFF". 2. NOTICE: Do not operate the pool heater without the function of this manual prior to servicing. Replace the pressure switch. 5. Remove the front access panel. 3. Turn pump, and heater power "OFF". 2. When the heater is...
...the hole in the piping are properly positioned, and the time clocks are properly set point to complete the procedure. 23 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS If adjustment is needed, the procedure is recommended that a PERIODIC INSPECTION also be certain that could result in the ... from the printed circuit board. 4. Turn pump, and heater power "OFF". 2. NOTICE: Do not operate the pool heater without the function of this manual prior to servicing. Replace the pressure switch. 5. Remove the front access panel. 3. Turn pump, and heater power "OFF". 2. When the heater is...