Installation Guide
Page 31
... can set up IBM Director and RDM to automatically image a spare blade to replace a failed server, increasing capacity to plan for an integrated infrastructure. Network topologies You can deploy your BladeCenter unit as part of your BladeCenter unit, refer to implement a ″Blade RAID″ concept. Single BladeCenter chassis You can deploy the BladeCenter unit in...
... can set up IBM Director and RDM to automatically image a spare blade to replace a failed server, increasing capacity to plan for an integrated infrastructure. Network topologies You can deploy your BladeCenter unit as part of your BladeCenter unit, refer to implement a ″Blade RAID″ concept. Single BladeCenter chassis You can deploy the BladeCenter unit in...
Installation Guide
Page 56
... 46 BladeCenter Type 8677: Planning and Installation Guide There are no PDUs available that support the plug an 1800 W power supply requires. Table 6. Each BladeCenter unit requires: v 2 to 6 BladeCenter units in a rack. A maximum of the 42U Standard rack. v 200 to 240 Vac 50 or 60 Hz Table 6, Table 7, Table 8 on page 47, and Table 9 on page 47show the part...
... 46 BladeCenter Type 8677: Planning and Installation Guide There are no PDUs available that support the plug an 1800 W power supply requires. Table 6. Each BladeCenter unit requires: v 2 to 6 BladeCenter units in a rack. A maximum of the 42U Standard rack. v 200 to 240 Vac 50 or 60 Hz Table 6, Table 7, Table 8 on page 47, and Table 9 on page 47show the part...
Installation Guide
Page 61
... the power jumper cord part numbers required to attach to each other power supplies, see the documentation that cool air is provided to prevent inter-rack air recirculation from all BladeCenter units towards the room cooling system without passing in the following examples. All samples assume IBM Enterprise NetBAY racks are positioned adjacent to N. Four 1400-watt power supplies: 11111...
... the power jumper cord part numbers required to attach to each other power supplies, see the documentation that cool air is provided to prevent inter-rack air recirculation from all BladeCenter units towards the room cooling system without passing in the following examples. All samples assume IBM Enterprise NetBAY racks are positioned adjacent to N. Four 1400-watt power supplies: 11111...
Installation Guide
Page 62
... to the the 1800W power supplies using power cable part number 00N7701. 24/48A 3 1 24/48A 4 2 A B Figure 16. Power jump cord part numbers (continued) 1200 W 36L88861 1400 W 74P44301 1800 W 00N77011 74P44302 00N77012 Notes: 1. A maximum of a single BladeCenter installed in a NetBAY 25 or 42U rack with the 1400 W Power Supply Upgrade option and to 1200 W power supplies using power 52 BladeCenter Type 8677: Planning and Installation...
... to the the 1800W power supplies using power cable part number 00N7701. 24/48A 3 1 24/48A 4 2 A B Figure 16. Power jump cord part numbers (continued) 1200 W 36L88861 1400 W 74P44301 1800 W 00N77011 74P44302 00N77012 Notes: 1. A maximum of a single BladeCenter installed in a NetBAY 25 or 42U rack with the 1400 W Power Supply Upgrade option and to 1200 W power supplies using power 52 BladeCenter Type 8677: Planning and Installation...
Installation Guide
Page 63
Installation considerations 53 Power layout of a single BladeCenter installed in a NetBAY 25 or 42U rack with 1400 or 1800 W power supplies (3-phase) Chapter 4. cable part number 74P4430 and to the 1800 W power supplies using power cable part number 00N7701. 48A 48A 3-P 3-P HD HD A B Figure 17.
Installation considerations 53 Power layout of a single BladeCenter installed in a NetBAY 25 or 42U rack with 1400 or 1800 W power supplies (3-phase) Chapter 4. cable part number 74P4430 and to the 1800 W power supplies using power cable part number 00N7701. 48A 48A 3-P 3-P HD HD A B Figure 17.
Installation Guide
Page 64
... use either a NetBAY 25 or NetBAY 42 standard rack. The PDU is cabled to the 1400 W power supplies using power cable part number 74P4430 and to the 1800 W power supplies using power cable part number 00N7701. 54 BladeCenter Type 8677: Planning and Installation Guide Power sources A and B represent separate power feeds to 1200 W power supplies using power cable part number 00N7701. 24/48A 3 1 24/48A 4 2 24/48A...
... use either a NetBAY 25 or NetBAY 42 standard rack. The PDU is cabled to the 1400 W power supplies using power cable part number 74P4430 and to the 1800 W power supplies using power cable part number 00N7701. 54 BladeCenter Type 8677: Planning and Installation Guide Power sources A and B represent separate power feeds to 1200 W power supplies using power cable part number 00N7701. 24/48A 3 1 24/48A 4 2 24/48A...
Installation Guide
Page 65
... 42U racks with 1400 or 1800 W power supplies Figure 21 represents PDU part number (North America) 73P5847 (48 Amps 3-phase). The PDU is cabled to the 1400 W power supplies using power cable part number 74P4430 and to 42U racks with 1400 or 1800 W power supplies (3-phase) Chapter 4. Power layout of two BladeCenter units installed in NetBAY 25 to the 1800 W power supplies using power cable part number...
... 42U racks with 1400 or 1800 W power supplies Figure 21 represents PDU part number (North America) 73P5847 (48 Amps 3-phase). The PDU is cabled to the 1400 W power supplies using power cable part number 74P4430 and to 42U racks with 1400 or 1800 W power supplies (3-phase) Chapter 4. Power layout of two BladeCenter units installed in NetBAY 25 to the 1800 W power supplies using power cable part number...
Installation Guide
Page 66
... a NetBAY 25 or 42 rack; 1200 W power supplies Figure 24 on page 57 front-end PDU part number (North America) 32P1767 (48 Amps). 56 BladeCenter Type 8677: Planning and Installation Guide Three BladeCenter units in either a NetBAY 25 or NetBAY 42 standard rack. Three BladeCenter units in a NetBAY 25 or 42 rack; 1200 W power supplies Figure 23 represents rack PDU part number (North America...
... a NetBAY 25 or 42 rack; 1200 W power supplies Figure 24 on page 57 front-end PDU part number (North America) 32P1767 (48 Amps). 56 BladeCenter Type 8677: Planning and Installation Guide Three BladeCenter units in either a NetBAY 25 or NetBAY 42 standard rack. Three BladeCenter units in a NetBAY 25 or 42 rack; 1200 W power supplies Figure 23 represents rack PDU part number (North America...
Installation Guide
Page 67
... or 42 rack; 1400 or 1800 W power supplies Figure 25 represents PDU part number (North America) 73P5847 (48 Amps 3-phase). 48A 48A 3-P 3-P HD HD A B Figure 25. Chapter 4. Figure 24 and Figure 25 show example configurations supported for BladeCenter units with 1200 W supplies. Installation considerations 57 Three BladeCenter units in a NetBAY 42U rack with 1400 or 1800 W power supplies (3-phase) Figure...
... or 42 rack; 1400 or 1800 W power supplies Figure 25 represents PDU part number (North America) 73P5847 (48 Amps 3-phase). 48A 48A 3-P 3-P HD HD A B Figure 25. Chapter 4. Figure 24 and Figure 25 show example configurations supported for BladeCenter units with 1200 W supplies. Installation considerations 57 Three BladeCenter units in a NetBAY 42U rack with 1400 or 1800 W power supplies (3-phase) Figure...
Installation Guide
Page 68
Power layout sample 4 - Power sources A and B represent separate power feeds to the rack. Four BladeCenter units in a NetBAY 42U rack; 1200 W power supplies Figure 27 represents PDU part number (North America) 32L1767 (48 Amps). 3 1 4 2 48A 48A 3 1 4 2 48A 48A 3 1 4 2 48A 3 1 48A 4 2 A B Figure 27. Four BladeCenter units in a NetBAY 42U rack; 1400 or 1800 W power supplies 58 BladeCenter Type 8677: Planning and Installation Guide Figure 26 represents PDU...
Power layout sample 4 - Power sources A and B represent separate power feeds to the rack. Four BladeCenter units in a NetBAY 42U rack; 1200 W power supplies Figure 27 represents PDU part number (North America) 32L1767 (48 Amps). 3 1 4 2 48A 48A 3 1 4 2 48A 48A 3 1 4 2 48A 3 1 48A 4 2 A B Figure 27. Four BladeCenter units in a NetBAY 42U rack; 1400 or 1800 W power supplies 58 BladeCenter Type 8677: Planning and Installation Guide Figure 26 represents PDU...
Installation Guide
Page 69
Power layout for four BladeCenter units in a NetBAY 42U rack with 1400 or 1800 W power supplies Figure 29 represents PDU part number (North America) 73P5847 (48 Amps 3-phase). Power layout for four BladeCenter units in a NetBAY 42U rack with 1400 W power supplies (3-phase) Chapter 4. Installation considerations 59 Figure 29. Figure 28 represents PDU part number (North America) 73P5855 (48 Amps). 48A 1-P HD A 48A 1-P HD 48A 1-P HD B 48A 1-P HD Figure 28.
Power layout for four BladeCenter units in a NetBAY 42U rack with 1400 or 1800 W power supplies Figure 29 represents PDU part number (North America) 73P5847 (48 Amps 3-phase). Power layout for four BladeCenter units in a NetBAY 42U rack with 1400 W power supplies (3-phase) Chapter 4. Installation considerations 59 Figure 29. Figure 28 represents PDU part number (North America) 73P5855 (48 Amps). 48A 1-P HD A 48A 1-P HD 48A 1-P HD B 48A 1-P HD Figure 28.
Installation Guide
Page 70
Power layout for BladeCenter units with 1400 W power supplies. 60 BladeCenter Type 8677: Planning and Installation Guide Figure 29 on page 58 shows an example configuration supported for four BladeCenter units in a NetBAY 42U rack with 1400 or 1800 W power supplies (3-phase) Figure 26 on page 59 is valid only with 1200 W power supplies. Figure 27 on page 58, Figure 28 on page...
Power layout for BladeCenter units with 1400 W power supplies. 60 BladeCenter Type 8677: Planning and Installation Guide Figure 29 on page 58 shows an example configuration supported for four BladeCenter units in a NetBAY 42U rack with 1400 or 1800 W power supplies (3-phase) Figure 26 on page 59 is valid only with 1200 W power supplies. Figure 27 on page 58, Figure 28 on page...
Installation Guide
Page 71
... 4 2 15A 3 1 4 2 15A 3 1 4 2 48A B Figure 31. Power layout sample 5 - Power sources A and B represent separate power feeds to the rack. Five BladeCenter units in a NetBAY 42 rack; 1200 W power supplies Figure 32 on page 62 show power distribution for five BladeCenter units installed in 42U racks Figure 31 and Figure 32 on page 62 represents front-end PDU part number (North America) 32P1767 (48...
... 4 2 15A 3 1 4 2 15A 3 1 4 2 48A B Figure 31. Power layout sample 5 - Power sources A and B represent separate power feeds to the rack. Five BladeCenter units in a NetBAY 42 rack; 1200 W power supplies Figure 32 on page 62 show power distribution for five BladeCenter units installed in 42U racks Figure 31 and Figure 32 on page 62 represents front-end PDU part number (North America) 32P1767 (48...
Installation Guide
Page 72
Five BladeCenter units in a NetBAY 42 rack; 1400 and 1800 W power supplies Figure 33 on page 63 represents PDU part number (North America) 73P5855 (48 Amps). 62 BladeCenter Type 8677: Planning and Installation Guide 3 1 4 2 48A 48A 3 1 4 2 48A 48A 3 1 4 2 3 1 4 2 48A 48A 3 1 4 2 48A 48A A B Figure 32.
Five BladeCenter units in a NetBAY 42 rack; 1400 and 1800 W power supplies Figure 33 on page 63 represents PDU part number (North America) 73P5855 (48 Amps). 62 BladeCenter Type 8677: Planning and Installation Guide 3 1 4 2 48A 48A 3 1 4 2 48A 48A 3 1 4 2 3 1 4 2 48A 48A 3 1 4 2 48A 48A A B Figure 32.
Installation Guide
Page 73
48A 1-P HD A 48A 1-P HD 48A 1-P HD B 48A 1-P HD Figure 33. Chapter 4. Installation considerations 63 Power layout for five BladeCenter units in a NetBAY 42 rack with 1400 W power supplies Figure 34 on page 64 represents PDU part number (North America) 73P5847 (48 Amps 3-phase).
48A 1-P HD A 48A 1-P HD 48A 1-P HD B 48A 1-P HD Figure 33. Chapter 4. Installation considerations 63 Power layout for five BladeCenter units in a NetBAY 42 rack with 1400 W power supplies Figure 34 on page 64 represents PDU part number (North America) 73P5847 (48 Amps 3-phase).
Installation Guide
Page 75
... in a NetBAY 42U rack; 1200 W power supplies Figure 36 on page 66 show power distribution for six BladeCenter units installed in 42U racks Figure 35 and Figure 36 on page 66 represents front-end PDU part number (North America) 32P1767 (48 Amps). six BladeCenter units in a NetBAY 42 rack. Installation considerations 65 Figure 35 represents PDU part number (North America...
... in a NetBAY 42U rack; 1200 W power supplies Figure 36 on page 66 show power distribution for six BladeCenter units installed in 42U racks Figure 35 and Figure 36 on page 66 represents front-end PDU part number (North America) 32P1767 (48 Amps). six BladeCenter units in a NetBAY 42 rack. Installation considerations 65 Figure 35 represents PDU part number (North America...
Installation Guide
Page 76
Six BladeCenter units in a NetBAY 42U rack; 1400 or 1800 W power supplies Figure 37 on page 67 represents PDU part number (North America) 73P5847 (48 Amps 3-phase). 66 BladeCenter Type 8677: Planning and Installation Guide 3 1 4 2 48A 48A 3 1 4 2 48A 48A 3 1 4 2 3 1 4 2 48A 48A 3 1 4 2 48A 48A 3 1 4 2 A B Figure 36.
Six BladeCenter units in a NetBAY 42U rack; 1400 or 1800 W power supplies Figure 37 on page 67 represents PDU part number (North America) 73P5847 (48 Amps 3-phase). 66 BladeCenter Type 8677: Planning and Installation Guide 3 1 4 2 48A 48A 3 1 4 2 48A 48A 3 1 4 2 3 1 4 2 48A 48A 3 1 4 2 48A 48A 3 1 4 2 A B Figure 36.
Installation Guide
Page 78
... standard rack. NetBAY rack 15 amp power distribution unit (part number 37L6866) v 48A - Figure 38 shows power distribution for four BladeCenter units installed in this example are 1200 W power supplies. Four BladeCenter units in this figure, IBM provides the following PDUs: v 15A - Power layout sample 7 - four BladeCenter units in a NetBAY 42 Enterprise rack Note: All the power supplies shown in a NetBAY 42U Enterprise rack 68 BladeCenter Type 8677...
... standard rack. NetBAY rack 15 amp power distribution unit (part number 37L6866) v 48A - Figure 38 shows power distribution for four BladeCenter units installed in this example are 1200 W power supplies. Four BladeCenter units in this figure, IBM provides the following PDUs: v 15A - Power layout sample 7 - four BladeCenter units in a NetBAY 42 Enterprise rack Note: All the power supplies shown in a NetBAY 42U Enterprise rack 68 BladeCenter Type 8677...
Installation Guide
Page 80
... shown in this figure, IBM provides the following PDUs: v 15A - five BladeCenter units in a NetBAY 42 Enterprise rack Note: All the power supplies shown in this example are 1200 W power supplies. Five BladeCenter units in a NetBAY 42 Enterprise rack. Power sources A and B represent separate power feeds to the rack. NetBAY single phase 60 amp front-end power distribution unit (part number 73P5790) I 15A 15A...
... shown in this figure, IBM provides the following PDUs: v 15A - five BladeCenter units in a NetBAY 42 Enterprise rack Note: All the power supplies shown in this example are 1200 W power supplies. Five BladeCenter units in a NetBAY 42 Enterprise rack. Power sources A and B represent separate power feeds to the rack. NetBAY single phase 60 amp front-end power distribution unit (part number 73P5790) I 15A 15A...
Installation Guide
Page 81
... 42 Enterprise rack. Power layout sample 10 - Power sources A and B represent separate power feeds to the rack. Note: To meet the de-rated amperage requirements shown in this figure, IBM provides the following PDUs: v 15A - six BladeCenter units in a NetBAY 42 Enterprise rack Note: All the power supplies shown in this example are 1200 W power supplies. NetBAY rack 15 amp power distribution unit (part number...
... 42 Enterprise rack. Power layout sample 10 - Power sources A and B represent separate power feeds to the rack. Note: To meet the de-rated amperage requirements shown in this figure, IBM provides the following PDUs: v 15A - six BladeCenter units in a NetBAY 42 Enterprise rack Note: All the power supplies shown in this example are 1200 W power supplies. NetBAY rack 15 amp power distribution unit (part number...