Belkin OmniGuard Rackmount UPS Hardware Manual
Page 3
...accordance with the specifications in Subpart J of Part 15 of Communications. HAZARDOUS LIVE PARTS INSIDE THIS POWER SUPPLY ARE ENERGIZED FROM THE BATTERY EVEN WHEN THE AC INPUT POWER IS DISCONNECTED. CAUTION! WARNING! Changes or modifications to this unit not expressly approved by one or...user's authority to operate the equipment. TO DE-ENERGIZE THE OUTPUTS OF THE UPS: 1. TO DE-ENERGIZE THE UPS COMPLETELY, DISCONNECT THE BATTERY. 4 WARNING CAUTION! RISK OF ELECTRICAL SHOCK. THE RECEPTACLE MUST BE CONNECTED TO APPROPRIATE BRANCH PROTECTION (CIRCUIT BREAKER OR FUSE). IF THE ...
...accordance with the specifications in Subpart J of Part 15 of Communications. HAZARDOUS LIVE PARTS INSIDE THIS POWER SUPPLY ARE ENERGIZED FROM THE BATTERY EVEN WHEN THE AC INPUT POWER IS DISCONNECTED. CAUTION! WARNING! Changes or modifications to this unit not expressly approved by one or...user's authority to operate the equipment. TO DE-ENERGIZE THE OUTPUTS OF THE UPS: 1. TO DE-ENERGIZE THE UPS COMPLETELY, DISCONNECT THE BATTERY. 4 WARNING CAUTION! RISK OF ELECTRICAL SHOCK. THE RECEPTACLE MUST BE CONNECTED TO APPROPRIATE BRANCH PROTECTION (CIRCUIT BREAKER OR FUSE). IF THE ...
Belkin OmniGuard Rackmount UPS Hardware Manual
Page 4
...rack-mounting rails and offers convenient monitoring with LEDs and switches that the batteries are integrated into the front panel. Our modular designs and wide range of features make the Belkin UPS line a flexible rack-mount solution for virtually any size environment. ...system management software, offering such advanced functionality as the large data center environment. OVERVIEW The Belkin OmniGuard Rackmount UPS (Figure 1) offers a 2U or 3U design with an industry-best Belkin 3-Year Warranty • Offers remote manageability and user-friendly monitoring software 6 HIGHLIGHTS •...
...rack-mounting rails and offers convenient monitoring with LEDs and switches that the batteries are integrated into the front panel. Our modular designs and wide range of features make the Belkin UPS line a flexible rack-mount solution for virtually any size environment. ...system management software, offering such advanced functionality as the large data center environment. OVERVIEW The Belkin OmniGuard Rackmount UPS (Figure 1) offers a 2U or 3U design with an industry-best Belkin 3-Year Warranty • Offers remote manageability and user-friendly monitoring software 6 HIGHLIGHTS •...
Belkin OmniGuard Rackmount UPS Hardware Manual
Page 5
... UPS •6 ft. Please save ALL packing materials! PACKAGE CONTENTS Please review the contents of shutdown parameters, and alert messages; Battery replacement might have all materials for 19" •Installation manual •Warranty card •Product registration card In addition to checking ...the contents, please inspect all the correct parts needed to shipping or handling. HIGHLIGHTS The Battery (Red) LED illuminates when the UPS has detected that the original packing materials be required. (See section 5) The Site Wiring...
... UPS •6 ft. Please save ALL packing materials! PACKAGE CONTENTS Please review the contents of shutdown parameters, and alert messages; Battery replacement might have all materials for 19" •Installation manual •Warranty card •Product registration card In addition to checking ...the contents, please inspect all the correct parts needed to shipping or handling. HIGHLIGHTS The Battery (Red) LED illuminates when the UPS has detected that the original packing materials be required. (See section 5) The Site Wiring...
Belkin OmniGuard Rackmount UPS Hardware Manual
Page 6
Select a location that you're using an appropriate connector and plug into the wall. 4. Reliable Grounding. Reduced Airflow. Charge up your batteries for the UPS device. 2. Install the UPS in a temperature-controlled environment that is not achieved due to supply connections other than room ambient. Mounting of ...
Select a location that you're using an appropriate connector and plug into the wall. 4. Reliable Grounding. Reduced Airflow. Charge up your batteries for the UPS device. 2. Install the UPS in a temperature-controlled environment that is not achieved due to supply connections other than room ambient. Mounting of ...
Belkin OmniGuard Rackmount UPS Hardware Manual
Page 7
...Mounting the UPS into a two-pole, three-wire, grounded receptacle only. Charging the Battery The OmniGuard Rackmount UPS will void the Belkin power warranty associated with the electrical flow and will charge the internal batteries whenever the unit is connected to an AC power source and the circuit breaker on... and nats necessary for mounting the UP actual rack are included.included111111 Other configurations are located on the back panel is used immediately, battery run time may be unstable due to the UPS To prepare the UPS for a 23-inch (58.4cm) standard rack, vertical mounting...
...Mounting the UPS into a two-pole, three-wire, grounded receptacle only. Charging the Battery The OmniGuard Rackmount UPS will void the Belkin power warranty associated with the electrical flow and will charge the internal batteries whenever the unit is connected to an AC power source and the circuit breaker on... and nats necessary for mounting the UP actual rack are included.included111111 Other configurations are located on the back panel is used immediately, battery run time may be unstable due to the UPS To prepare the UPS for a 23-inch (58.4cm) standard rack, vertical mounting...
Belkin OmniGuard Rackmount UPS Hardware Manual
Page 8
... Connecting to run the software but is optional. CAUTION! The RJ45/RJ11 modular connectors are a total of the circuit breaker. (Not on -battery) output voltage. 8. Note: Connecting the RS232 computer interface port to a computer is necessary to the telephone/network surge protection connection is optional. ...The input power cord has a NEMA 5-15P connector. (IEC input socket on 230VAC models) 4. It is a 2U rack, there are used for surge-only protection. If your Equipment Plug the equipment into the output receptacles on the UPS unless the UPS...
... Connecting to run the software but is optional. CAUTION! The RJ45/RJ11 modular connectors are a total of the circuit breaker. (Not on -battery) output voltage. 8. Note: Connecting the RS232 computer interface port to a computer is necessary to the telephone/network surge protection connection is optional. ...The input power cord has a NEMA 5-15P connector. (IEC input socket on 230VAC models) 4. It is a 2U rack, there are used for surge-only protection. If your Equipment Plug the equipment into the output receptacles on the UPS unless the UPS...
Belkin OmniGuard Rackmount UPS Hardware Manual
Page 9
...On-Line LED will blink, and the audible alarm will perform a 10-second self-test. The DIP switch must be set the desired inverter (on -battery) output voltage only. Switch #1 OFF ON OFF ON Switch #2 OFF OFF ON ON Output Voltage in and there is AC present. After one beep ...it is longer than the start -up or userinvoked test. The UPS will turn the unit off. Note: The UPS will adjust the inverter (on -battery) output voltage. This setting will automatically perform a self-test on and supply power to provide an acceptable amount of the connected equipment. 16 17 This...
...On-Line LED will blink, and the audible alarm will perform a 10-second self-test. The DIP switch must be set the desired inverter (on -battery) output voltage only. Switch #1 OFF ON OFF ON Switch #2 OFF OFF ON ON Output Voltage in and there is AC present. After one beep ...it is longer than the start -up or userinvoked test. The UPS will turn the unit off. Note: The UPS will adjust the inverter (on -battery) output voltage. This setting will automatically perform a self-test on and supply power to provide an acceptable amount of the connected equipment. 16 17 This...
Belkin OmniGuard Rackmount UPS Hardware Manual
Page 10
... Ground Pin 6:Instant off and restarted with both RS232 and simulated contact closure capability. This alarm will be allowed to charge overnight before performing a battery test to restart the UPS.) Pin 7: Not used Pin 8: AC fail signal Pin 9:ATX wake-up signal 18 19 Changing the port configuration ...requires that the UPS be repeated every hour until the battery passes a self-test. UPS FAULT When the UPS detects a hardware fault, the Fault LED will illuminate and the UPS will emit two ...
... Ground Pin 6:Instant off and restarted with both RS232 and simulated contact closure capability. This alarm will be allowed to charge overnight before performing a battery test to restart the UPS.) Pin 7: Not used Pin 8: AC fail signal Pin 9:ATX wake-up signal 18 19 Changing the port configuration ...requires that the UPS be repeated every hour until the battery passes a self-test. UPS FAULT When the UPS detects a hardware fault, the Fault LED will illuminate and the UPS will emit two ...
Belkin OmniGuard Rackmount UPS Hardware Manual
Page 11
... UPS to power up or auto restart in BIOS as follows: When there is a utility failure, the UPS will send the AC-fail and low-battery signals to start up directly. If you may just set up your UPS.
... UPS to power up or auto restart in BIOS as follows: When there is a utility failure, the UPS will send the AC-fail and low-battery signals to start up directly. If you may just set up your UPS.
Belkin OmniGuard Rackmount UPS Hardware Manual
Page 13
... back in the UPS. Series Model # Battery Model # F6C110-RKM-2U 12V 7.2Ah F6C150-RKM-2U 12V 4.5Ah F6C230-RKM-2U 12V 9Ah F6C320-RKM-3U 12V 12Ah 25 Reset the battery pack's circuit breaker. Repairs should be weak or at the end of batteries. CAUTION: Although battery system voltages are only 24VDC and 48VDC, the battery system can still present a risk of...
... back in the UPS. Series Model # Battery Model # F6C110-RKM-2U 12V 7.2Ah F6C150-RKM-2U 12V 4.5Ah F6C230-RKM-2U 12V 9Ah F6C320-RKM-3U 12V 12Ah 25 Reset the battery pack's circuit breaker. Repairs should be weak or at the end of batteries. CAUTION: Although battery system voltages are only 24VDC and 48VDC, the battery system can still present a risk of...
Belkin OmniGuard Rackmount UPS Hardware Manual
Page 14
... looking directly at the UPS). If not, there will ask you a Return Material Authorization Number (RMA #). Never use Styrofoam beads for the battery on the failure, including LEDs that is no charge. It is the most common problem. 3. Press and release, after one beep, the ...ON/OFF button of the batteries properly at no longer available, ask the Technical Support technician about obtaining a new set. A tripped circuit breaker is important to pack the UPS...
... looking directly at the UPS). If not, there will ask you a Return Material Authorization Number (RMA #). Never use Styrofoam beads for the battery on the failure, including LEDs that is no charge. It is the most common problem. 3. Press and release, after one beep, the ...ON/OFF button of the batteries properly at no longer available, ask the Technical Support technician about obtaining a new set. A tripped circuit breaker is important to pack the UPS...
Belkin OmniGuard Rackmount UPS Hardware Manual
Page 15
... Range Voltage (default) Frequency Wave Form Surge Protection Voltage Voltage Regulation Frequency Wave Form Typical Transfer Time Hot-Swappable Battery Internal battery Typical Computer Server Power 300 Watts Dimensions net H X W X D Dimensions shipping H X W X D Weight net Weight shipping F6C110-RKM-2U F6C150-RKM-2U F6C230-RKM-2U 1100 1500 2300 660 900 1380 Rack-Mount Model UL, cUL 3 yr. Input (non...
... Range Voltage (default) Frequency Wave Form Surge Protection Voltage Voltage Regulation Frequency Wave Form Typical Transfer Time Hot-Swappable Battery Internal battery Typical Computer Server Power 300 Watts Dimensions net H X W X D Dimensions shipping H X W X D Weight net Weight shipping F6C110-RKM-2U F6C150-RKM-2U F6C230-RKM-2U 1100 1500 2300 660 900 1380 Rack-Mount Model UL, cUL 3 yr. Input (non...
Belkin OmniGuard Rackmount UPS Software Manual
Page 19
These are information details, which are logged in the data log. 19 The details are returned by the UPS. The input voltage, Output Voltage, Battery charge level, Input frequency, Output Source, Output Load, Output power and the battery Temperature are displayed. OmniGuardTM UPS Power Management Software If the UPS is being established between the UPS and the host system. The values displayed ensure the proper connection is not connected physically to the COM port, then you will see the screen below showing the Device Not Found message.
These are information details, which are logged in the data log. 19 The details are returned by the UPS. The input voltage, Output Voltage, Battery charge level, Input frequency, Output Source, Output Load, Output power and the battery Temperature are displayed. OmniGuardTM UPS Power Management Software If the UPS is being established between the UPS and the host system. The values displayed ensure the proper connection is not connected physically to the COM port, then you will see the screen below showing the Device Not Found message.
Belkin OmniGuard Rackmount UPS Software Manual
Page 24
Battery The current battery details like Output source, Output number lines, Output voltage; OmniGuardTM UPS Power Management Software The UPS output details like Status, Charge, Estimated runtime, Battery charge level, Battery voltage, Battery temperature etc are displayed here. Output current, Output Power and Output Load are displayed here. 24 CAUTION: Output current, power and load value will be visible only when an actual load is connected to UPS input.
Battery The current battery details like Output source, Output number lines, Output voltage; OmniGuardTM UPS Power Management Software The UPS output details like Status, Charge, Estimated runtime, Battery charge level, Battery voltage, Battery temperature etc are displayed here. Output current, Output Power and Output Load are displayed here. 24 CAUTION: Output current, power and load value will be visible only when an actual load is connected to UPS input.