HP UPS Best Practices
Page 1
... 6 Tower UPS Model Numbers ...6 UPS Options ...6 HP Rackmount UPS Advantages 6 HP Rackmount UPS Models...8 HP R1500 G2 Rackmount UPS 8 HP R3000 Rackmount UPS ...8 HP R/T3000 Rackmount UPS 9 HP R5500 Rackmount UPS ...10 HP Three-phase Rack-mountable UPS 11 HP Tower UPS Advantages...12 HP Tower UPS Models ...13 HP T750 G2 UPS...13 HP T1000 G3 and T1500 G3 UPSs 13...
... 6 Tower UPS Model Numbers ...6 UPS Options ...6 HP Rackmount UPS Advantages 6 HP Rackmount UPS Models...8 HP R1500 G2 Rackmount UPS 8 HP R3000 Rackmount UPS ...8 HP R/T3000 Rackmount UPS 9 HP R5500 Rackmount UPS ...10 HP Three-phase Rack-mountable UPS 11 HP Tower UPS Advantages...12 HP Tower UPS Models ...13 HP T750 G2 UPS...13 HP T1000 G3 and T1500 G3 UPSs 13...
HP UPS Best Practices
Page 3
...for an R3000 at 25ºC (77ºF). The current for the datacenter. It is reduced approximately 70 percent from overloading. Batteries must be properly supported during power outages, especially during high load conditions. Power supplies have an auto-sensing feature that less current ... For configurations involving multiple servers and/or additional critical storage/option products, simply add up the total watts of batteries decreases with a watt rating higher than 80 percent of a UPS HP has provided a sizing tool that the computer load should not discard the UPS or the UPS...
...for an R3000 at 25ºC (77ºF). The current for the datacenter. It is reduced approximately 70 percent from overloading. Batteries must be properly supported during power outages, especially during high load conditions. Power supplies have an auto-sensing feature that less current ... For configurations involving multiple servers and/or additional critical storage/option products, simply add up the total watts of batteries decreases with a watt rating higher than 80 percent of a UPS HP has provided a sizing tool that the computer load should not discard the UPS or the UPS...
HP UPS Best Practices
Page 4
...devices, the runtime for valuable data. Network administrators can manage scheduled shutdowns and sequential startups of receptacles on the network, check battery health and perform other load segment. however it will also provide a complete log of events and of UPS utility data, which...of the UPS. Without management software, a UPS will run until the batteries are depleted and then drop the attached load. In this manner, the HP UPS can monitor, manage and control a single UPS locally and remotely. HP Power Management Software also facilitates a prioritized startup of 27
...devices, the runtime for valuable data. Network administrators can manage scheduled shutdowns and sequential startups of receptacles on the network, check battery health and perform other load segment. however it will also provide a complete log of events and of UPS utility data, which...of the UPS. Without management software, a UPS will run until the batteries are depleted and then drop the attached load. In this manner, the HP UPS can monitor, manage and control a single UPS locally and remotely. HP Power Management Software also facilitates a prioritized startup of 27
HP UPS Best Practices
Page 6
... life Provides the fastest, safest recharge time Provides up to 60-day advanced notification when batteries are approaching the end of useful life Page 6 of 27 HP UPS Models Available Rackmount UPS Model Numbers AF419A R1500 G2 NA AF418A R1500 G2 INTL AF421A R1500 G2 JPN/TWN AF422A ...JPN AF414A R3000 High Volt INTL AF452A R/T3000 Low Volt NA/JPN AF453A R/T3000 High Volt NA/JPN AF454A R/T3000 High Volt INTL AF416A R5500 INTL AF426A R5500 NA/JPN AF431A R8000/3 NA AF432A R8000/3 INTL AF429A R12000/3 NA AF430A R12000/3 INTL AF438A RP36000/3 NA AF439A RP36000/3 INTL Tower UPS ...
... life Provides the fastest, safest recharge time Provides up to 60-day advanced notification when batteries are approaching the end of useful life Page 6 of 27 HP UPS Models Available Rackmount UPS Model Numbers AF419A R1500 G2 NA AF418A R1500 G2 INTL AF421A R1500 G2 JPN/TWN AF422A ...JPN AF414A R3000 High Volt INTL AF452A R/T3000 Low Volt NA/JPN AF453A R/T3000 High Volt NA/JPN AF454A R/T3000 High Volt INTL AF416A R5500 INTL AF426A R5500 NA/JPN AF431A R8000/3 NA AF432A R8000/3 INTL AF429A R12000/3 NA AF430A R12000/3 INTL AF438A RP36000/3 NA AF439A RP36000/3 INTL Tower UPS ...
HP UPS Best Practices
Page 7
...the R3000 delivers an unprecedented 2700 watts in the industry, reducing total cost of ownership and system downtime HP pre-failure warranty replaces batteries free of charge within 3-year period $250,000 computer load protection guarantee provides additional peace of mind Page ...this inconsistent voltage and delivers clean, consistent output, without consuming valuable rack space. R3000 models occupy just 2U (3.5 inches); and R5500 occupies only 3U (5.25 inches), leaving more space for data center customers who want to maximize power distribution and space efficiencies in ...
...the R3000 delivers an unprecedented 2700 watts in the industry, reducing total cost of ownership and system downtime HP pre-failure warranty replaces batteries free of charge within 3-year period $250,000 computer load protection guarantee provides additional peace of mind Page ...this inconsistent voltage and delivers clean, consistent output, without consuming valuable rack space. R3000 models occupy just 2U (3.5 inches); and R5500 occupies only 3U (5.25 inches), leaving more space for data center customers who want to maximize power distribution and space efficiencies in ...
HP UPS Best Practices
Page 8
... up to be utilized by servers, storage and networking equipment. The R3000 uses a unique transformer-less technology to increase runtime. The HP R3000 UPS also has the capability to 2700 watts of true power for data exchange. Page 8 of valuable rack space, while delivering... key benefits such as Enhanced Battery Management, Load Segment Control, and serial and USB ports for unprecedented power density. The densest, most power-packed UPS available, the HP R3000 delivers more watts per U than any other UPS, enabling more valuable...
... up to be utilized by servers, storage and networking equipment. The R3000 uses a unique transformer-less technology to increase runtime. The HP R3000 UPS also has the capability to 2700 watts of true power for data exchange. Page 8 of valuable rack space, while delivering... key benefits such as Enhanced Battery Management, Load Segment Control, and serial and USB ports for unprecedented power density. The densest, most power-packed UPS available, the HP R3000 delivers more watts per U than any other UPS, enabling more valuable...
HP UPS Best Practices
Page 9
... Uninterruptible Power System (UPS) packs up to support multiple tower servers, wiring closets, and blade enclosures such as the HP c3000 BladeSystem. Proven Digital Signal Processor (DSP) technology clean, reliable power protection in an energy efficient transformer-less design while ...generated heat. R/T3000 shown with pre-failure warning insures that the HP R/T3000 will protect your power needs. An industry leading 3 year warranty and enhanced battery management with tower conversion kit installed Page 9 of 27 The HP R/T3000 UPS includes a Rack to Tower Conversion Kit for non rack...
... Uninterruptible Power System (UPS) packs up to support multiple tower servers, wiring closets, and blade enclosures such as the HP c3000 BladeSystem. Proven Digital Signal Processor (DSP) technology clean, reliable power protection in an energy efficient transformer-less design while ...generated heat. R/T3000 shown with pre-failure warning insures that the HP R/T3000 will protect your power needs. An industry leading 3 year warranty and enhanced battery management with tower conversion kit installed Page 9 of 27 The HP R/T3000 UPS includes a Rack to Tower Conversion Kit for non rack...
HP UPS Best Practices
Page 10
... serviceability with Digital Signal Processing technology (DSP); HP R5500 Rackmount UPS The R5500 UPS provides more power protection per U than any other HP UPS, and supports any rackmount server application requiring up to 4 ERMs with Enhanced Battery Management (EBM); longer runtime with hot-swappable electronics and batteries. extended battery runtime with optional Extended Runtime Modules (now supports...
... serviceability with Digital Signal Processing technology (DSP); HP R5500 Rackmount UPS The R5500 UPS provides more power protection per U than any other HP UPS, and supports any rackmount server application requiring up to 4 ERMs with Enhanced Battery Management (EBM); longer runtime with hot-swappable electronics and batteries. extended battery runtime with optional Extended Runtime Modules (now supports...
HP UPS Best Practices
Page 12
... and switch membrane is among the longest in the industry, reducing total cost of ownership and system downtime HP pre-failure warranty replaces batteries free of charge within 3-year period $250,000 computer load protection guarantee provides additional peace of mind Page... blackout Serial and USB ports for data exchange with the host computer Hot-swappable batteries for servers, storage devices, computer equipment, and other network environments, HP's Tower UPS models are designed with a host of key benefits including: Increased power rating ...
... and switch membrane is among the longest in the industry, reducing total cost of ownership and system downtime HP pre-failure warranty replaces batteries free of charge within 3-year period $250,000 computer load protection guarantee provides additional peace of mind Page... blackout Serial and USB ports for data exchange with the host computer Hot-swappable batteries for servers, storage devices, computer equipment, and other network environments, HP's Tower UPS models are designed with a host of key benefits including: Increased power rating ...
HP UPS Best Practices
Page 13
...intuitive front panel display, hot-swappable batteries and prioritized shutdown using bundled HP Power Manager management software. With serial and USB connectivity for multiple configuration options, the HP T750 G2 UPS provides four output receptacles. HP T750 Japan T1000 Japan and T1500 Japan... a host of key benefits including increased power rating, intuitive front panel display, hot-swappable batteries and prioritized shutdown using bundled HP Power Manager management software. HP T1000 G3 and T1500 G3 UPSs Providing advanced power protection and increased uptime for servers, storage...
...intuitive front panel display, hot-swappable batteries and prioritized shutdown using bundled HP Power Manager management software. With serial and USB connectivity for multiple configuration options, the HP T750 G2 UPS provides four output receptacles. HP T750 Japan T1000 Japan and T1500 Japan... a host of key benefits including increased power rating, intuitive front panel display, hot-swappable batteries and prioritized shutdown using bundled HP Power Manager management software. HP T1000 G3 and T1500 G3 UPSs Providing advanced power protection and increased uptime for servers, storage...
HP UPS Best Practices
Page 14
Run Time per HP UPS Model Backup times** (in minutes) T750 G2 and T750 Japan Load, percent 50% 100% Load, Watts 250 500 T1000 G3 and T1000 Japan Load, ... R/T3000 High Volt Models Load, percent 20% 50% 80% 100% With Standby Battery 40 minutes 12 minutes 6 minutes 4 minutes Estimated battery runtime at 100% battery charge 15 minutes 5 minutes Estimated battery runtime at 100% battery charge 15 minutes 5 minutes Estimated battery runtime at 100% battery charge 15 minutes 5 minutes With 1 ERM 120 minutes 45 minutes 30 minutes...
Run Time per HP UPS Model Backup times** (in minutes) T750 G2 and T750 Japan Load, percent 50% 100% Load, Watts 250 500 T1000 G3 and T1000 Japan Load, ... R/T3000 High Volt Models Load, percent 20% 50% 80% 100% With Standby Battery 40 minutes 12 minutes 6 minutes 4 minutes Estimated battery runtime at 100% battery charge 15 minutes 5 minutes Estimated battery runtime at 100% battery charge 15 minutes 5 minutes Estimated battery runtime at 100% battery charge 15 minutes 5 minutes With 1 ERM 120 minutes 45 minutes 30 minutes...
HP UPS Best Practices
Page 15
... 7.7 18 28 37 47 N+1 3 24 9 21 32 43 54 N+1 2 12 13 30 44 59 76 N+1 ** NOTE: Backup times are estimated for typical applications. R5500 Load (VA/W) With Standby Battery 1000/900 59 minutes 2000/1800 26 minutes 2200/1980 21 minutes 2500/2250 19 minutes 2700/2430 17 minutes 3000/2700 15...
... 7.7 18 28 37 47 N+1 3 24 9 21 32 43 54 N+1 2 12 13 30 44 59 76 N+1 ** NOTE: Backup times are estimated for typical applications. R5500 Load (VA/W) With Standby Battery 1000/900 59 minutes 2000/1800 26 minutes 2200/1980 21 minutes 2500/2250 19 minutes 2700/2430 17 minutes 3000/2700 15...
HP UPS Best Practices
Page 18
...anomaly, the UPS software will shut down a system. Every server with older batteries, there may need to run time required to configure a UPS in #4 above). If a delay is allotted for at http://h18004.www1.hp.com/products/servers/platforms/rackandpower.html. 4. Page 18 of each rest mode... refer to 100% capacity, it is not completed, the ERM will measure the battery voltage degradation over a 10-day period. in which one must be held in HP Power Manager does not initiate a battery test on the UPS model, you may need to 100% capacity, the initial ...
...anomaly, the UPS software will shut down a system. Every server with older batteries, there may need to run time required to configure a UPS in #4 above). If a delay is allotted for at http://h18004.www1.hp.com/products/servers/platforms/rackandpower.html. 4. Page 18 of each rest mode... refer to 100% capacity, it is not completed, the ERM will measure the battery voltage degradation over a 10-day period. in which one must be held in HP Power Manager does not initiate a battery test on the UPS model, you may need to 100% capacity, the initial ...
HP UPS R3000 User Guide
Page 3
Contents Component identification ...6 UPS R3000 overview ...6 UPS front panel ...6 UPS front panel controls ...7 UPS front panel LED indicators...8 HP UPS R3000 models ...8 UPS R3000 NA and R3000j JPN rear panel 9 UPS R3000h NA and R3000h JPN rear panel 10 UPS R3000 ...13 Tools and materials ...13 Selecting a site ...14 Readying the equipment ...14 Installing the mounting rails ...14 Installing the UPS ...18 Connecting the battery leads ...19 Attaching the UPS front bezel ...19 Connecting the serial communications port 19 Connecting the REPO port...20 Connecting the ground bonding cable 22...
Contents Component identification ...6 UPS R3000 overview ...6 UPS front panel ...6 UPS front panel controls ...7 UPS front panel LED indicators...8 HP UPS R3000 models ...8 UPS R3000 NA and R3000j JPN rear panel 9 UPS R3000h NA and R3000h JPN rear panel 10 UPS R3000 ...13 Tools and materials ...13 Selecting a site ...14 Readying the equipment ...14 Installing the mounting rails ...14 Installing the UPS ...18 Connecting the battery leads ...19 Attaching the UPS front bezel ...19 Connecting the serial communications port 19 Connecting the REPO port...20 Connecting the ground bonding cable 22...
HP UPS R3000 User Guide
Page 4
......33 Replacing the UPS option card ...34 Replacing the batteries ...35 Important battery safety information 35 Battery care and storage guidelines 36 Determining when to replace batteries 36 Obtaining new batteries ...36 UPS battery replacement procedure 36 Testing the new battery module...38 Replacing the UPS ...38 Replacing the ERM......41 UPS is in Auto-Bypass mode ...42 General alarm condition ...42 Bypass is out of range ...43 Battery condition ...43 UPS is on battery...43 Input voltage is out of range ...43 Utility power condition...44 Internal UPS fault condition ...44 REPO condition ...
......33 Replacing the UPS option card ...34 Replacing the batteries ...35 Important battery safety information 35 Battery care and storage guidelines 36 Determining when to replace batteries 36 Obtaining new batteries ...36 UPS battery replacement procedure 36 Testing the new battery module...38 Replacing the UPS ...38 Replacing the ERM......41 UPS is in Auto-Bypass mode ...42 General alarm condition ...42 Bypass is out of range ...43 Battery condition ...43 UPS is on battery...43 Input voltage is out of range ...43 Utility power condition...44 Internal UPS fault condition ...44 REPO condition ...
HP UPS R3000 User Guide
Page 5
...51 Hardware options ...51 Technical support...52 Before you contact HP ...52 HP contact information...52 Warranty information...53 Limited warranty ...53 $250,000 Computer Load Protection Guarantee 53 Pre-Failure Battery Warranty...53 Recommended duration of use...54 Regulatory compliance notices ...... in private households in the European Union 57 Japanese notice ...58 BSMI notice ...59 Korean notice ...59 Battery replacement notice ...59 Taiwan battery recycling notice ...60 Power cord statement for Japan ...60 Electrostatic discharge ...61 Preventing electrostatic discharge ...61 Grounding...
...51 Hardware options ...51 Technical support...52 Before you contact HP ...52 HP contact information...52 Warranty information...53 Limited warranty ...53 $250,000 Computer Load Protection Guarantee 53 Pre-Failure Battery Warranty...53 Recommended duration of use...54 Regulatory compliance notices ...... in private households in the European Union 57 Japanese notice ...58 BSMI notice ...59 Korean notice ...59 Battery replacement notice ...59 Taiwan battery recycling notice ...60 Power cord statement for Japan ...60 Electrostatic discharge ...61 Preventing electrostatic discharge ...61 Grounding...
HP UPS R3000 User Guide
Page 6
NOTE: To download the latest versions of UPS firmware and software. Component identification UPS R3000 overview The HP UPS R3000 features a 2U rack-mount design and offers power protection for loads up to the latest versions of UPS firmware and software, see the HP website (http://www.hp.com/go/rackandpower). UPS front panel Item 1 2 3 Description Battery compartment Control buttons LED display Component identification 6 To benefit from the latest product enhancements, update to 3000 VA/2700 W.
NOTE: To download the latest versions of UPS firmware and software. Component identification UPS R3000 overview The HP UPS R3000 features a 2U rack-mount design and offers power protection for loads up to the latest versions of UPS firmware and software, see the HP website (http://www.hp.com/go/rackandpower). UPS front panel Item 1 2 3 Description Battery compartment Control buttons LED display Component identification 6 To benefit from the latest product enhancements, update to 3000 VA/2700 W.
HP UPS R3000 User Guide
Page 8
... panel LED indicators The front panel is shown with the bezel removed. HP UPS R3000 models UPS model R3000 NA ("UPS R3000 NA and R3000j JPN rear panel" on page 41)" . Item LED description 1 Configure Mode On 2 General Alarm 3 On Battery 4 Battery Fault 5 Site Wiring Fault 6 Utility 7 Overload 8 76% to 100% load 9 51...
... panel LED indicators The front panel is shown with the bezel removed. HP UPS R3000 models UPS model R3000 NA ("UPS R3000 NA and R3000j JPN rear panel" on page 41)" . Item LED description 1 Configure Mode On 2 General Alarm 3 On Battery 4 Battery Fault 5 Site Wiring Fault 6 Utility 7 Overload 8 76% to 100% load 9 51...
HP UPS R3000 User Guide
Page 11
... does not utilize the orderly shutdown procedure initiated by power management software. • The REPO feature shuts down UPS units operating under either utility or battery power. When properly wired, the REPO feature enables the power at the UPS output receptacles to be connected to a remote, normally open switch (not supplied...
... does not utilize the orderly shutdown procedure initiated by power management software. • The REPO feature shuts down UPS units operating under either utility or battery power. When properly wired, the REPO feature enables the power at the UPS output receptacles to be connected to a remote, normally open switch (not supplied...
HP UPS R3000 User Guide
Page 12
... Item 1 2 3 Description ERM input connector (from another ERM output) Circuit breaker ERM output connector (to a single switch. NOTE: If the UPS was operating on battery power when the remote switch was closed, no power is available to the load devices until utility power is held. However, if the On button... is pressed and a REPO is detected, battery start and the UPS assumes the load. The electronics module fan spins and the General Alarm LED and an audible alarm are active as long...
... Item 1 2 3 Description ERM input connector (from another ERM output) Circuit breaker ERM output connector (to a single switch. NOTE: If the UPS was operating on battery power when the remote switch was closed, no power is available to the load devices until utility power is held. However, if the On button... is pressed and a REPO is detected, battery start and the UPS assumes the load. The electronics module fan spins and the General Alarm LED and an audible alarm are active as long...