Owner's Manual for 3-Phase UPS 932688
Page 3
... cabinets for maximum efficiency and cost savings • Internal N+1 power module redundancy (SU40KX, SU60KX and SU80KX) 3 • Built-in a compact footprint; up and protecting data centers, telecommunications (VoIP), networks, industrial facilities, security/emergency systems and more. Introduction 1 Tripp Lite's SmartOnline 3-Phase UPS Systems (Models SU20KX, SU40KX, SU60KX and SU80KX) are ideal for backing up to 160kVA...
... cabinets for maximum efficiency and cost savings • Internal N+1 power module redundancy (SU40KX, SU60KX and SU80KX) 3 • Built-in a compact footprint; up and protecting data centers, telecommunications (VoIP), networks, industrial facilities, security/emergency systems and more. Introduction 1 Tripp Lite's SmartOnline 3-Phase UPS Systems (Models SU20KX, SU40KX, SU60KX and SU80KX) are ideal for backing up to 160kVA...
Owner's Manual for 3-Phase UPS 932688
Page 15
... the battery pack's connectors. connect the voltmeter's red probe to protected power. The battery pack's acceptable DC voltage range is between 220V and 280V DC (nominal 240V DC). 3 If several voltmeter tests yield results outside the acceptable DC 240 voltage range, contact Tripp Lite for assistance in determining the possible causes of personal injury...
... the battery pack's connectors. connect the voltmeter's red probe to protected power. The battery pack's acceptable DC voltage range is between 220V and 280V DC (nominal 240V DC). 3 If several voltmeter tests yield results outside the acceptable DC 240 voltage range, contact Tripp Lite for assistance in determining the possible causes of personal injury...
Owner's Manual for 3-Phase UPS 932688
Page 19
...Battery Cabinet Wiring Warning: External battery cabinets vary. It is optional with models SU60KX and SU80KX. Cabling should be protected by connecting negative to negative and positive to the corresponding positive (+), neutral ... battery cabinet, and confirm that have been approved by Tripp Lite. 2 Note: An external battery cabinet is off. (If the UPS system has...ground cable. Read the external battery cabinet's documentation before attempting to connect it to an AC power source, see Section 9-6 for cable size requirements. Keep the ground cable connected at this time,...
...Battery Cabinet Wiring Warning: External battery cabinets vary. It is optional with models SU60KX and SU80KX. Cabling should be protected by connecting negative to negative and positive to the corresponding positive (+), neutral ... battery cabinet, and confirm that have been approved by Tripp Lite. 2 Note: An external battery cabinet is off. (If the UPS system has...ground cable. Read the external battery cabinet's documentation before attempting to connect it to an AC power source, see Section 9-6 for cable size requirements. Keep the ground cable connected at this time,...
Owner's Manual for 3-Phase UPS 932688
Page 27
... BATTERY BREAKER is on the back of the UPS; on the SU60KX and SU80KX units, the BATTERY BREAKER is 5 6 5 7 3 Q4 Q3 Q2 Q1 on periodically to allow the batteries to keep loads powered by unconditioned utility power. 8 9-6 Shutdown Procedure (Single UPS) Warning: The UPS system...Bypass (continued) 1 9-5 Manual Bypass Procedure (Single UPS) Warning: Placing the UPS system in NORMAL mode (green LED ON, LCD displays "Load Protected - Although connected equipment loads will be turned on BYPASS. •3 Turn OFF the OUTPUT circuit breaker Q4. 1 •4 Turn OFF the MAIN...
... BATTERY BREAKER is on the back of the UPS; on the SU60KX and SU80KX units, the BATTERY BREAKER is 5 6 5 7 3 Q4 Q3 Q2 Q1 on periodically to allow the batteries to keep loads powered by unconditioned utility power. 8 9-6 Shutdown Procedure (Single UPS) Warning: The UPS system...Bypass (continued) 1 9-5 Manual Bypass Procedure (Single UPS) Warning: Placing the UPS system in NORMAL mode (green LED ON, LCD displays "Load Protected - Although connected equipment loads will be turned on BYPASS. •3 Turn OFF the OUTPUT circuit breaker Q4. 1 •4 Turn OFF the MAIN...
Owner's Manual for 3-Phase UPS 932688
Page 28
...via parallel configuration. the OUTPUT Q4 , BYPASS INPUT Q2 and MAIN INPUT Q1 circuit breakers are within the recommended specifications. 1111. on the SU60KX and SU80KX units, the BATTERY 1 BREAKER is ON; Confirm there are being run in MANUAL BYPASS (the MANUAL BYPASS circuit breaker Q3 is..., the UPS systems will display "Load Unprotected-On Manual Bypass). 44. 5 55. The Power Module fans will display "Self Diagnosis". Attempting to NORMAL mode (green LED ON and LCD displays "Load Protected-On Line Mode"). 99. Turn ON the BYPASS INPUT circuit breaker Q2 (the amber Bypass LED...
...via parallel configuration. the OUTPUT Q4 , BYPASS INPUT Q2 and MAIN INPUT Q1 circuit breakers are within the recommended specifications. 1111. on the SU60KX and SU80KX units, the BATTERY 1 BREAKER is ON; Confirm there are being run in MANUAL BYPASS (the MANUAL BYPASS circuit breaker Q3 is..., the UPS systems will display "Load Unprotected-On Manual Bypass). 44. 5 55. The Power Module fans will display "Self Diagnosis". Attempting to NORMAL mode (green LED ON and LCD displays "Load Protected-On Line Mode"). 99. Turn ON the BYPASS INPUT circuit breaker Q2 (the amber Bypass LED...