Owner's Manual for 3-Phase UPS 932688
Page 2
...22 8-3 Auto Bypass Mode (Single UPS) 22 8-4 Manual Bypass Mode (Single UPS) 22 8-5 Online Mode (Parallel UPS) 23 9 8-6 Battery Backup Mode (Parallel UPS) 23 8-7 Auto Bypass Mode (Parallel UPS) 23 8-8 Manual Bypass Mode (Parallel UPS) 24 8-9 Hot Standby Mode (...Bypass 25 9-1 Control Panel and Breaker Diagrams 25 9-2 Preliminary Checklist (Single UPS) 25 11 9-3 Normal Start-Up Procedure (Single UPS) 25 9-4 Battery Start-Up Procedure (Single UPS) 26 9-5 Manual Bypass Procedure (Single UPS) 27 9-6 Shutdown Procedure (Single UPS) 27 12 9-7 Preliminary Checklist (Parallel...
...22 8-3 Auto Bypass Mode (Single UPS) 22 8-4 Manual Bypass Mode (Single UPS) 22 8-5 Online Mode (Parallel UPS) 23 9 8-6 Battery Backup Mode (Parallel UPS) 23 8-7 Auto Bypass Mode (Parallel UPS) 23 8-8 Manual Bypass Mode (Parallel UPS) 24 8-9 Hot Standby Mode (...Bypass 25 9-1 Control Panel and Breaker Diagrams 25 9-2 Preliminary Checklist (Single UPS) 25 11 9-3 Normal Start-Up Procedure (Single UPS) 25 9-4 Battery Start-Up Procedure (Single UPS) 26 9-5 Manual Bypass Procedure (Single UPS) 27 9-6 Shutdown Procedure (Single UPS) 27 12 9-7 Preliminary Checklist (Parallel...
Owner's Manual for 3-Phase UPS 932688
Page 3
... 1 Tripp Lite's SmartOnline 3-Phase UPS Systems (Models SU20KX, SU40KX, SU60KX and SU80KX) are ideal for backing up to 160kVA in parallel configuration • High input power factor and high efficiency with separated rectifier and bypass input • All models support external battery cabinets... low noise • Simplified, easy-to 80kVA capacity in parallel or hot standby redundancy (1+1) capability for extended battery backup runtime 5 • High-resolution LCD status screen simplifies operation and delivers detailed operational information, including system block diagrams 6 7...
... 1 Tripp Lite's SmartOnline 3-Phase UPS Systems (Models SU20KX, SU40KX, SU60KX and SU80KX) are ideal for backing up to 160kVA in parallel configuration • High input power factor and high efficiency with separated rectifier and bypass input • All models support external battery cabinets... low noise • Simplified, easy-to 80kVA capacity in parallel or hot standby redundancy (1+1) capability for extended battery backup runtime 5 • High-resolution LCD status screen simplifies operation and delivers detailed operational information, including system block diagrams 6 7...
Owner's Manual for 3-Phase UPS 932688
Page 6
... equipment. The primary AC input supply is present and within standard operating parameters. 5 •B "BATTERY" LED: This amber light illuminates when the UPS system is in battery backup mode, discharging the batteries to provide power to restart the UPS system. Turn on the LCD screen. •E LCD Status...audible alarm will also sound. • C 6 • D "BYPASS" LED: This amber light illuminates when the UPS system is in battery backup mode when the EPO button is in bypass mode (auto bypass or manual bypass). Note: Switching the inverter OFF does not stop the converter ...
... equipment. The primary AC input supply is present and within standard operating parameters. 5 •B "BATTERY" LED: This amber light illuminates when the UPS system is in battery backup mode, discharging the batteries to provide power to restart the UPS system. Turn on the LCD screen. •E LCD Status...audible alarm will also sound. • C 6 • D "BYPASS" LED: This amber light illuminates when the UPS system is in battery backup mode when the EPO button is in bypass mode (auto bypass or manual bypass). Note: Switching the inverter OFF does not stop the converter ...
Owner's Manual for 3-Phase UPS 932688
Page 22
... power that conforms to normal parameters, then the UPS system automatically switches to auto bypass mode to continue supplying power to battery backup mode. This dual conversion technology isolates connected equipment from normal mode to connected equipment. If the UPS system detects a bypass...After 11 confirming that supports the operation of connected equipment. Warning: The UPS system must be de- 8 - When all times. 4 8-2 Battery Backup Mode (Single UPS) 5 When a blackout or other extreme power event occurs, the UPS system automatically switches from all power problems and ensures...
... power that conforms to normal parameters, then the UPS system automatically switches to auto bypass mode to continue supplying power to battery backup mode. This dual conversion technology isolates connected equipment from normal mode to connected equipment. If the UPS system detects a bypass...After 11 confirming that supports the operation of connected equipment. Warning: The UPS system must be de- 8 - When all times. 4 8-2 Battery Backup Mode (Single UPS) 5 When a blackout or other extreme power event occurs, the UPS system automatically switches from all power problems and ensures...
Owner's Manual for 3-Phase UPS 932688
Page 23
... total load is 2 shared by two UPS systems. If one of the remaining UPS system, it will switch to auto bypass mode. 3 4 5 8-6 Battery Backup Mode (Parallel UPS) 6 Similar to auto bypass mode for a single UPS system (Section 8-2), except the total connected equipment load is shared by the remaining UPS..., the total connected equipment load is supported by the parallel (1+1) UPS systems. 7 8 9 10 8-7 Auto Bypass Mode (Parallel UPS) Similar to on battery backup mode for a single UPS system (Section 8-3), except with parallel (1+1) UPS systems. 11 12 13 14 23 8 -
... total load is 2 shared by two UPS systems. If one of the remaining UPS system, it will switch to auto bypass mode. 3 4 5 8-6 Battery Backup Mode (Parallel UPS) 6 Similar to auto bypass mode for a single UPS system (Section 8-2), except the total connected equipment load is shared by the remaining UPS..., the total connected equipment load is supported by the parallel (1+1) UPS systems. 7 8 9 10 8-7 Auto Bypass Mode (Parallel UPS) Similar to on battery backup mode for a single UPS system (Section 8-3), except with parallel (1+1) UPS systems. 11 12 13 14 23 8 -
Owner's Manual for 3-Phase UPS 932688
Page 27
...minute or two), then turn OFF the BATTERY BREAKER. On the 40K unit, the BATTERY BREAKER (for an extended period of the UPS; on the SU60KX and SU80KX units, the BATTERY BREAKER is 5 6 5 7 3 Q4 Q3 Q2 Q1 on the back of the battery cabinet). The UPS should be energized. ... OFF the 3 5 4 Q4 Q3 Q2 Q1 12 BATTERY BREAKER (on the SU20KX and SU40KX units, the BATTERY BREAKER is on and the batteries should transfer to Bypass Mode?". Failure to recharge. The unit's LCD will not receive battery backup in NORMAL mode (green LED ON, LCD displays "Load...
...minute or two), then turn OFF the BATTERY BREAKER. On the 40K unit, the BATTERY BREAKER (for an extended period of the UPS; on the SU60KX and SU80KX units, the BATTERY BREAKER is 5 6 5 7 3 Q4 Q3 Q2 Q1 on the back of the battery cabinet). The UPS should be energized. ... OFF the 3 5 4 Q4 Q3 Q2 Q1 12 BATTERY BREAKER (on the SU20KX and SU40KX units, the BATTERY BREAKER is on and the batteries should transfer to Bypass Mode?". Failure to recharge. The unit's LCD will not receive battery backup in NORMAL mode (green LED ON, LCD displays "Load...
Owner's Manual for 3-Phase UPS 932688
Page 31
...switch A of each UPS system. Note: Qualified service personnel may prefer to bypass mode, and their 1 LCD screens will not receive battery backup during a utility power failure. 2 •1 For the first UPS system you wish to perform maintenance or repair. Connected equipment loads are... "LOAD NOT POWERED". Q1 5 Output Manual Bypass Main 2 Bypass Input Input 6 •3 Confirm that was turned off will turn OFF the A battery breaker on local codes and the nature of each UPS system. The LCD screen will shut down . 3 A 4 •2 Switch off completely....
...switch A of each UPS system. Note: Qualified service personnel may prefer to bypass mode, and their 1 LCD screens will not receive battery backup during a utility power failure. 2 •1 For the first UPS system you wish to perform maintenance or repair. Connected equipment loads are... "LOAD NOT POWERED". Q1 5 Output Manual Bypass Main 2 Bypass Input Input 6 •3 Confirm that was turned off will turn OFF the A battery breaker on local codes and the nature of each UPS system. The LCD screen will shut down . 3 A 4 •2 Switch off completely....
Owner's Manual for 3-Phase UPS 932688
Page 33
...1 10-1 Control Panel Diagram •A "NORMAL" (Green) LED: Illuminated when the UPS input B power is normal. • C "BATTERY" (Amber) LED: Illuminated when the UPS is in Battery Backup mode. •D "BYPASS" (Amber) LED: Illuminated when the UPS is in E Manual Bypass mode. •F "FAULT" (Red) ...EPO button will completely remove power from the UPS output. 2 E FI K A B G C 3 D HJ Control Panel 4 5 6 10-2 Display Hierarchy The Tripp Lite E3 Series UPS features a user-friendly LCD screen to show messages and display UPS Status screens. 7 8 9 10 11 12 13 14 33
...1 10-1 Control Panel Diagram •A "NORMAL" (Green) LED: Illuminated when the UPS input B power is normal. • C "BATTERY" (Amber) LED: Illuminated when the UPS is in Battery Backup mode. •D "BYPASS" (Amber) LED: Illuminated when the UPS is in E Manual Bypass mode. •F "FAULT" (Red) ...EPO button will completely remove power from the UPS output. 2 E FI K A B G C 3 D HJ Control Panel 4 5 6 10-2 Display Hierarchy The Tripp Lite E3 Series UPS features a user-friendly LCD screen to show messages and display UPS Status screens. 7 8 9 10 11 12 13 14 33
Owner's Manual for 3-Phase UPS 932688
Page 36
The loads are supplied by 6 battery power. 7 8 9 6 •7 The UPS is in online (normal) mode. 10 - Display and Configuration (continued) 1 10-3-1 Status Display (continued) •5 The UPS system is operating in battery backup mode. Connected 2 equipment loads will receive battery backup power if the mains (utility or generator) power source fails. 3 4 5 5 •6 The UPS is performing the "battery test". 10 11 12 13 7 14 36
The loads are supplied by 6 battery power. 7 8 9 6 •7 The UPS is in online (normal) mode. 10 - Display and Configuration (continued) 1 10-3-1 Status Display (continued) •5 The UPS system is operating in battery backup mode. Connected 2 equipment loads will receive battery backup power if the mains (utility or generator) power source fails. 3 4 5 5 •6 The UPS is performing the "battery test". 10 11 12 13 7 14 36
Owner's Manual for 3-Phase UPS 932688
Page 57
...working normally. 3 The UPS system is lower than 220V. Battery ground fault The battery has a grounding error. The bypass input is abnormal (frequency / phase). 4 The battery voltage is in battery backup mode, and battery voltage is lower than the reference value. External parallel communication ...more information.) 8 The temperature of the internal components is in battery backup mode. 11 - Power module warning An internal power module has an error, but the UPS system can be enabled, contact Tripp Lite. 9 10 11 12 13 14 57 Bypass static switch fault...
...working normally. 3 The UPS system is lower than 220V. Battery ground fault The battery has a grounding error. The bypass input is abnormal (frequency / phase). 4 The battery voltage is in battery backup mode, and battery voltage is lower than the reference value. External parallel communication ...more information.) 8 The temperature of the internal components is in battery backup mode. 11 - Power module warning An internal power module has an error, but the UPS system can be enabled, contact Tripp Lite. 9 10 11 12 13 14 57 Bypass static switch fault...
Owner's Manual for 3-Phase UPS 932688
Page 59
... : 10 minutes; ≤150% : 1 minute Audible Warning Battery Backup Intermittent UPS Abnormal Continuous Display LED LCD UPS Status: Normal • Bypass • Backup • Fault 7 Input/Output • Bypass • Inverter • Frequency • Loading • Battery Voltage UPS abnormal messages with intelligent self-diagnosis. Interface Standard RS...SU20KX 267 kg 600 kg/m2 SU40KX 412 kg 927 kg/m2 SU60KX 210 kg 475 kg/m2 SU80KX 244 kg 552 kg/m2 Model Weight Floor Loading 59 BP480V26B (40 12V batteries; 26AH each) 470 kg (1036 lb) 1064 kg/m2 BP480V40C ...
... : 10 minutes; ≤150% : 1 minute Audible Warning Battery Backup Intermittent UPS Abnormal Continuous Display LED LCD UPS Status: Normal • Bypass • Backup • Fault 7 Input/Output • Bypass • Inverter • Frequency • Loading • Battery Voltage UPS abnormal messages with intelligent self-diagnosis. Interface Standard RS...SU20KX 267 kg 600 kg/m2 SU40KX 412 kg 927 kg/m2 SU60KX 210 kg 475 kg/m2 SU80KX 244 kg 552 kg/m2 Model Weight Floor Loading 59 BP480V26B (40 12V batteries; 26AH each) 470 kg (1036 lb) 1064 kg/m2 BP480V40C ...
Owner's Manual for 3-Phase UPS 932688
Page 60
...allow the exclusion or limitation of incidental or consequential 9 damages, so the above limitations or exclusions may cause irreversible battery damage. 3 Service Your Tripp Lite product is suitable, adequate or safe for recycling when this manual to the dealer. Before returning your unit's model...and Service 1 Storage The UPS system must have other general purchaser information. Do not rely on the UPS system to provide backup power to Tripp Lite or an authorized Tripp Lite service center is required for a period of 2 years (except U.S., Canada and Mexico: 8 1 year) from the date...
...allow the exclusion or limitation of incidental or consequential 9 damages, so the above limitations or exclusions may cause irreversible battery damage. 3 Service Your Tripp Lite product is suitable, adequate or safe for recycling when this manual to the dealer. Before returning your unit's model...and Service 1 Storage The UPS system must have other general purchaser information. Do not rely on the UPS system to provide backup power to Tripp Lite or an authorized Tripp Lite service center is required for a period of 2 years (except U.S., Canada and Mexico: 8 1 year) from the date...