Get support for Sanyo CM1972 - 19,700 BTU Ductless Multi-Split Air Conditioner

Sanyo CM1972 Support Question

Sanyo CM1972 Support Question

Find answers below for this question about Sanyo CM1972 - 19,700 BTU Ductless Multi-Split Air Conditioner.
Need a Sanyo CM1972 manual? We have 1 online manual for this item!
Question posted by Laurencelimasa on May 24th, 2017

Ac Goes Warm After A Few Hours

ac will run perfect for a couple of hours then it will start to blow non cooled air while the power light on the inside head starts to blink. When I go outside and manually spin the fan by hand the ac starts to blow cold air again. This will continue every so often. When I turn off unit for a couple of hours and restart it works perfectly fine until running for a few hours then it all happens again, like stated above

Current Answers

Answer #1: Posted by Odin on May 24th, 2017 5:41 PM
This answer was accepted by the poster of the original question.
Odin

Member since:
April 10th, 2010

Points: 41,236,690
1,100
points
1. Air conditioners will stop cooling if the outside temperature drops below 60F because the unit thinks it has done its job. If that's your situation, your best course is to open and window and turn off the A/C.

2. If the above doesn't solve, you'll need to consult Sanyo: use the contact information here--https://www.contacthelp.com/sanyo/customer-service.


Hope this is useful. Please don't forget to click the Accept This Answer button if you do accept it. My aim is to provide reliable helpful answers, not just a lot of them. See https://www.helpowl.com/profile/Odin.
Answer #2: Posted by BusterDoogen on May 24th, 2017 1:51 PM
BusterDoogen

Member since:
October 30th, 2011

Points: 28,565,407
100
points
This is most likely caused by the fan motor or the thermistor control assembly. Rather than just replace parts I suggest you contact an AC tech to troubleshoot the issue.

I hope this is helpful to you!

Please respond to my effort to provide you with the best possible solution by using the "Acceptable Solution" and/or the "Helpful" buttons when the answer has proven to be helpful. Please feel free to submit further info for your question, if a solution was not provided. I appreciate the opportunity to serve you!

Related Sanyo CM1972 Manual Pages

Service Manual - Page 1

...Table" in the Appendix of this manual. CM3172 IMPORTANT These air conditioners employ new refrigerant R410A. Pay special attention when servicing the unit. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 230V 19,700 BTU/h 25,400 BTU/h 30,600 BTU/h Outdoor Model No. REFERENCE NO. TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CM1972 CM2472 CM3172 FILE NO.
Service Manual - Page 2

...air conditioner can occur. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM. • Do not supply power to walls and floors. When Transporting Be careful when picking up and moving parts. • Clean up the site after you must: Carefully read this manual...before starting the test run inside the unit being serviced. In Case of wiring have been left inside a ...
Service Manual - Page 6

... Range Running Amperes Power Input Power Factor EER SEER Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity BTU/h kW BTU/h BTU/h ft3/min (m3/h) V A W % BTU/h/W BTU/Wh A A Features Control Fan Speeds Compressor Refrigerant / Amount charged at shipment Refrigerant Control Operation Sound (High) Cool Refrigerant Tubing Connections Max. The values shown in this manual...
Service Manual - Page 7

... Latent Capacity Air Circulation (High) Available Voltage Range Running Amperes Power Input Power Factor EER SEER Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity BTU/h kW BTU/h BTU/h ft3/min (m3/h) V A W % BTU/h/W BTU/Wh A A Features Control Fan Speeds Compressor Refrigerant / Amount charged at shipment Refrigerant Control Operation Sound (High) Cool Refrigerant Tubing...
Service Manual - Page 8

... Latent Capacity Air Circulation (High) Available Voltage Range Running Amperes Power Input Power Factor EER SEER Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity BTU/h kW BTU/h BTU/h ft3/min (m3/h) V A W % BTU/h/W BTU/Wh A A Features Control Fan Speeds Compressor Refrigerant / Amount charged at shipment Refrigerant Control Operation Sound (High) Cool Refrigerant Tubing...
Service Manual - Page 9

...shown in this manual. allowable tubing ...Air Circulation (High) Available Voltage Range Running Amperes Power Input Power Factor EER SEER Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity BTU/h kW BTU/h BTU/h ft3/min (m3/h) V A W % BTU/h/W BTU/Wh A A Features Control Fan Speeds Compressor Refrigerant / Amount charged at shipment Refrigerant Control Operation Sound (High) Cool...
Service Manual - Page 10

... Latent Capacity Air Circulation (High) Available Voltage Range Running Amperes Power Input Power Factor EER SEER Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity BTU/h kW BTU/h BTU/h ft3/min (m3/h) V A W % BTU/h/W BTU/Wh A A Features Control Fan Speeds Compressor Refrigerant / Amount charged at shipment Refrigerant Control Operation Sound (High) Cool Refrigerant Tubing...
Service Manual - Page 11

... in this manual. Outdoor air temp. 95...Air Circulation (High) Available Voltage Range Running Amperes Power Input Power Factor EER SEER Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity BTU/h kW BTU/h BTU/h ft3/min (m3/h) V A W % BTU/h/W BTU/Wh A A Features Control Fan Speeds Compressor Refrigerant / Amount charged at shipment Refrigerant Control Operation Sound (High) Cool...
Service Manual - Page 36

...176;C) W.B. : Outdoor Ambient Temp. 95 °F (35 °C) D.B. 2. TEMP. °F (°C) W.B. Cooling Capacity Outdoor Unit : CM1972 Indoor Unit : KMS0972 × 3 Power Supply : 230V Single Phase 60Hz < Cooling Capacity > RATING CAPACITY: INDOOR ENT. 5-2. D.B. 19,700 BTU/h 65 (18.3) TC 19,800 AIR FLOW RATE: OUTDOOR AMBIENT TEMP. °F (°C) 75 (23.9) 85 (29.4) 95 (35...
Service Manual - Page 37

... 7,530 10,610 13,700 16,610 5,470 8,560 11,640 14,560 TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) NOTE 1. TEMP. °F (°C) W.B. For this reason, the value may vary from the actual cooling characteristics. 3. Outdoor Unit : CM2472 Indoor Unit : KMS0972 × 3 Power Supply : 230V Single Phase 60Hz < Cooling Capacity > RATING CAPACITY: INDOOR...
Service Manual - Page 38

...28,010 28,010 28,010 29,310 21,700 22,960 22,960 22,960 22,960 ...Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) NOTE 1. TEMP. °F (°C) W.B. Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) D.B. / 67 °F (19.4 °C) W.B. : Outdoor Ambient Temp. 95 °F (35 °C) D.B. 2. Outdoor Unit : CM3172 Indoor Unit : KMS0972 × 4 Power...
Service Manual - Page 43

...hours or more easily. The indoor and outdoor units stop if the thermostart for a period of the indoor heat exchanger has risen. Starts operating in the indoor and outdoor temperatures, and the previous conditions (COOL.... This is pressed. Outdoor air temperature is stabilized in order to stabilize the return of the indoor heat exchanger drops to start .) When the frequency reaches ...
Service Manual - Page 49

... and fan motor must turn ON. (They turn ON about (70) seconds later after the power is turned ON.) NOTE If the above check items are okay, but the outdoor unit does ...outdoor unit terminal plate. 2 • Short-circuit the T-RUN terminal to the COM terminal of TEST/T-RUN terminals. Work procedure 1 • Apply 220 V AC between the indoor unit and the outdoor unit. 49 Checking the...
Service Manual - Page 63

...Please Read Before Starting 2 Model Combinations Combine indoor and outdoor units only as shown in the combination tables for 3-room or 4-room outdoor unit as listed below. 1. Tubing Connections 3-6. Recommended Wire Length and Diameter 5-3. Wiring Instructions for the Outdoor Unit (CLM models only) 2-5. Inverter Multi Split System Air Conditioner - Accessories Supplied with...
Service Manual - Page 79

... putty to seal off the hole in the Technical & Service Manual. 3-6. As you wrap the tubing, overlap half of each ...120 cm). CAUTION Be sure to prevent rain and draft from entering. (Fig. 19) Torque wrench Indoor unit Spanner Outdoor unit Fig. 15 Min. 5/16" (8 ...local codes permit) should be sure the condensation drain hose splits away from the bundle and drips clear of the outdoor ...
Service Manual - Page 90

... cooling capacity of CM1972 outdoor unit: C=19700 (BTU/h) Rated cooling capacity of indoor units: K1, K2, ... (BTU/h)...CM1972 The combinations of Table 2, operating all the indoor units installed must be connected. 2. CAUTION In this combination is not found in the 3-room operation column of the indoor units listed in trouble. Conditions: 1. Otherwise, the air conditioner may not run...
Service Manual - Page 93

...rated cooling capacity of the indoor units to be connected must be no more indoor units must not be operated concurrently. Otherwise, the air conditioner may not run ...BTU/h) Rated cooling capacity of indoor units: K1, K2, ... (BTU/h) Then: C x 2 (200%) K1 + K2 + ....... 24400 x 2 7500 + 7500 + 7500 + 17500 48800 40000 It is not acceptable for only one indoor unit to be connected to the multi...
Service Manual - Page 94

... : KMS0972 11900 : KMS1272 17500 : KMS1872 24200 : KMS2472 Table 1 Indoor Unit Capacity (BTU/h) Indoor Unit Combination COOLING Room Room Room Room Total Performance A B C D Capacity ( Min. - However, all four indoor units must not be operated concurrently. Otherwise, the air conditioner may be operated concurrently. < Combinations of indoor units as representative models...
Service Manual - Page 95

... of 4 indoor units prohibited) This multi outdoor unit allows up to four indoor units to three indoor units may not run properly. However, all four indoor units must not be operated concurrently. Otherwise, the air conditioner may be connected. Voltage Rating : 208V 60Hz CM2472 (Rated cooling capacity at 208V: 24400 BTU/h) NOTE 7500 : KMS0772 9000 : KMS0972...
Service Manual - Page 96

.... Otherwise, the air conditioner may not run properly and trouble may cause a malfunction. However, since this combination is therefore possible to the compressor may occur. Pub. CAUTION In this Combination Table! However, since this , shut down at 230V If the following holds true Rated cooling capacity of CM3172 outdoor unit: C=30600 (BTU/h) Rated cooling capacity of...

Similar Questions

Ask a New Question
Use the box below to post a new question about this Sanyo product .
Points & Prizes
  • You can earn points for nearly everything you do on HelpOwl.com
  • You can trade in those points for gift cards at leading retailers such as Amazon.com and Walmart
  • It's that simple!
See How it Works
Create a Free Account

Sanyo Manuals

Find free Sanyo CM1972 - 19,700 BTU Ductless Multi-Split Air Conditioner manuals and user guides available at ManualOwl.com. Try out our unique manual viewer allowing you to interact with manuals from directly within your browser!

Sanyo Reviews

View thousands of Sanyo user reviews and customer ratings available at ReviewOwl.com.

Contact Information

Complete Sanyo customer service contact information including steps to reach representatives, hours of operation, customer support links and more from ContactHelp.com.

Scoreboard Ratings

See detailed Sanyo customer service rankings, employee comments and much more from our sister site.

Sanyo Recalls

Find comprehensive Sanyo recall information updated hourly on RecallOwl.com.