Planning Guides
Page 1
...the accompanying installation instructions. See following pages for proper applications and cutout information. 2. This appliance must be install in conjunction with a single Dacor approved cabinet, remote or in accordance with CABP3 blower installed A - For detailed information on the remote and in raised position 7 1/2"...1/2" (13 mm) thick stiffener across back 1 13/16" (46 mm) Top cap with approved Dacor cooktops. All tolerances: +1/16", -0, (+1.6 mm, -0) unless otherwise stated Model Number RV30 RV36 RV46 Vent shown in -line blowers, refer to change without notice.
...the accompanying installation instructions. See following pages for proper applications and cutout information. 2. This appliance must be install in conjunction with a single Dacor approved cabinet, remote or in accordance with CABP3 blower installed A - For detailed information on the remote and in raised position 7 1/2"...1/2" (13 mm) thick stiffener across back 1 13/16" (46 mm) Top cap with approved Dacor cooktops. All tolerances: +1/16", -0, (+1.6 mm, -0) unless otherwise stated Model Number RV30 RV36 RV46 Vent shown in -line blowers, refer to change without notice.
Planning Guides
Page 2
...local codes permit. ■■ Install 3 conductor wiring/conduit with minimum current carrying capacity of the raised vent itself and a single Dacor approved remote blower or internal cabinet blower. General System Layout The vent system consists of 8 Amps to supply power to the internal cabinet ...label. ■■ The suggested location of the junction box supplying power to the power supply junction box. Raised Vent Model No. RV30 RV36 RV46 Approved Blowers CABP3, ILHSF8, ILHSF10, REMP3, REMP16 Duct Sizes 3 1/4"x10", 8" round, 10" round WARNING • Failure to install an ...
...local codes permit. ■■ Install 3 conductor wiring/conduit with minimum current carrying capacity of the raised vent itself and a single Dacor approved remote blower or internal cabinet blower. General System Layout The vent system consists of 8 Amps to supply power to the internal cabinet ...label. ■■ The suggested location of the junction box supplying power to the power supply junction box. Raised Vent Model No. RV30 RV36 RV46 Approved Blowers CABP3, ILHSF8, ILHSF10, REMP3, REMP16 Duct Sizes 3 1/4"x10", 8" round, 10" round WARNING • Failure to install an ...
Planning Guides
Page 3
... and the electrical and gas supplies for the cooktop and vent must be taken into consideration when determining the layout. Document # PG08-003 RV30, RV36, RV46 30", 36", 46" Wide, Raised Vent General System Layout (continued) ■■ The raised vent exhaust may be provided for inspection and service. Allow room... of Layout with Remote Blower, Roof Exhaust Cooktop Backsplash Wall Example of the vent must be connected to wall cap 12" (305 mm) Min. www.Dacor.com Phone: (800) 793-0093 8.9 Example of the unit.
... and the electrical and gas supplies for the cooktop and vent must be taken into consideration when determining the layout. Document # PG08-003 RV30, RV36, RV46 30", 36", 46" Wide, Raised Vent General System Layout (continued) ■■ The raised vent exhaust may be provided for inspection and service. Allow room... of Layout with Remote Blower, Roof Exhaust Cooktop Backsplash Wall Example of the vent must be connected to wall cap 12" (305 mm) Min. www.Dacor.com Phone: (800) 793-0093 8.9 Example of the unit.
Planning Guides
Page 4
RV30, RV36, RV46 Document # PG08-003 30", 36", 46" Wide, Raised Vent General System Layout (continued) Revised 03/29/10 Page 4/7 PLANNING GUIDE Cooktop Cabinet back Raised vent ... with in-line Blower, Duct Work Under Floor, wall Exhaust Specifications subject to accompanying installation instructions. Install all appliances according to change without notice. www.Dacor.com Phone: (800) 793-0093 8.10
RV30, RV36, RV46 Document # PG08-003 30", 36", 46" Wide, Raised Vent General System Layout (continued) Revised 03/29/10 Page 4/7 PLANNING GUIDE Cooktop Cabinet back Raised vent ... with in-line Blower, Duct Work Under Floor, wall Exhaust Specifications subject to accompanying installation instructions. Install all appliances according to change without notice. www.Dacor.com Phone: (800) 793-0093 8.10
Planning Guides
Page 5
...the rear cabinet wall. ■■ When planning new duct work with a remote blower or internal cabinet blower. Specifications subject to change without notice. www.Dacor.com Phone: (800) 793-0093 8.11 Doing so will work , always look for proper operation. For models REMP3 or REMP16, see the instructions later...duct between blower air flow rates can increase the duct size over the run if desired. Document # PG08-003 Planning the Duct Work RV30, RV36, RV46 30", 36", 46" Wide, Raised Vent Revised 03/29/10 Page 5/7 PLANNING GUIDE WARNING • To reduce the risk of fire and to ...
...the rear cabinet wall. ■■ When planning new duct work with a remote blower or internal cabinet blower. Specifications subject to change without notice. www.Dacor.com Phone: (800) 793-0093 8.11 Doing so will work , always look for proper operation. For models REMP3 or REMP16, see the instructions later...duct between blower air flow rates can increase the duct size over the run if desired. Document # PG08-003 Planning the Duct Work RV30, RV36, RV46 30", 36", 46" Wide, Raised Vent Revised 03/29/10 Page 5/7 PLANNING GUIDE WARNING • To reduce the risk of fire and to ...
Planning Guides
Page 6
Install all appliances according to change without notice. www.Dacor.com B 6" (152 mm) 9" (229 mm) C 12" (205 mm) 9" (229 mm) Phone: (800) 793-0093 8.12 Bottom Exhaust Raised vent Countertop center line B 11 5/8" (295 ... configutation with vertical center line of chassis Internal cabinet blower mounting location Exhaust Locations and Dimensions for CABP3 Internal Cabinet Blower Model RV30 RV36 RV46 A 2" (51 mm) 5" (127 mm) Specifications subject to accompanying installation instructions. Left Exhaust DUCT Exhaust Locations and Side Dimensions for in any ...
Install all appliances according to change without notice. www.Dacor.com B 6" (152 mm) 9" (229 mm) C 12" (205 mm) 9" (229 mm) Phone: (800) 793-0093 8.12 Bottom Exhaust Raised vent Countertop center line B 11 5/8" (295 ... configutation with vertical center line of chassis Internal cabinet blower mounting location Exhaust Locations and Dimensions for CABP3 Internal Cabinet Blower Model RV30 RV36 RV46 A 2" (51 mm) 5" (127 mm) Specifications subject to accompanying installation instructions. Left Exhaust DUCT Exhaust Locations and Side Dimensions for in any ...
Planning Guides
Page 7
Document # PG08-003 RV30, RV36, RV46 30", 36", 46" Wide, Raised Vent Revised 03/29/10 Page 7/7 PLANNING GUIDE Calculating the Maximum Duct Run Length ■■ Do not use duct ... internal cabinet blower. ** The equivalent lengths of roof and wall caps vary with the vent system and the number of elbows and transitions used. www.Dacor.com Phone: (800) 793-0093 8.13 Equivalent Number of straight duct that is : 60 feet - 34 feet = 24 feet. Blower Maximum Duct Straight Length Blower...
Document # PG08-003 RV30, RV36, RV46 30", 36", 46" Wide, Raised Vent Revised 03/29/10 Page 7/7 PLANNING GUIDE Calculating the Maximum Duct Run Length ■■ Do not use duct ... internal cabinet blower. ** The equivalent lengths of roof and wall caps vary with the vent system and the number of elbows and transitions used. www.Dacor.com Phone: (800) 793-0093 8.13 Equivalent Number of straight duct that is : 60 feet - 34 feet = 24 feet. Blower Maximum Duct Straight Length Blower...
Installation Instructions
Page 1
See the installation instructions for optional cabinet blower (Dacor model CABP3) Part No. 85515 Rev. H Use these downdraft raised vents only with approved Dacor ® cooktops. Installation Instructions Downdraft Raised Vent Models: RV30, RV36, RV46 Includes installation instructions for the particular cooktop model being installed to determine suitability.
See the installation instructions for optional cabinet blower (Dacor model CABP3) Part No. 85515 Rev. H Use these downdraft raised vents only with approved Dacor ® cooktops. Installation Instructions Downdraft Raised Vent Models: RV30, RV36, RV46 Includes installation instructions for the particular cooktop model being installed to determine suitability.
Installation Instructions
Page 2
... or the Dacor Customer Service Team. All specifications subject to 4:00 p.m. The product data label also specifies the power supply requirements. Pacific Time RV30 = 30-inch wide raised vent RV36 = 36-inch wide raised vent RV46 = 46-inch wide raised vent Tested in the Cutout 11 ...Electrical Installation 12 Final Installation 14 Verifying Proper Operation 14 Installation Checklist 14 Technical Data 15 RV Raised Vent Wiring Diagram 15 CABP3 Cabinet Blower Ratings 15 Before You Begin... For repairs to Dacor appliances...
... or the Dacor Customer Service Team. All specifications subject to 4:00 p.m. The product data label also specifies the power supply requirements. Pacific Time RV30 = 30-inch wide raised vent RV36 = 36-inch wide raised vent RV46 = 46-inch wide raised vent Tested in the Cutout 11 ...Electrical Installation 12 Final Installation 14 Verifying Proper Operation 14 Installation Checklist 14 Technical Data 15 RV Raised Vent Wiring Diagram 15 CABP3 Cabinet Blower Ratings 15 Before You Begin... For repairs to Dacor appliances...
Installation Guide
Page 1
Installation Downdraft Raised Vent Models: RV30, RV36, RV46 Instructions Includes installation instructions for the particular cooktop model being installed to determine suitability. H Use these downdraft raised vents only with approved Dacor ® cooktops. See the installation instructions for optional cabinet blower (Dacor model CABP3) Part No. 85515 Rev.
Installation Downdraft Raised Vent Models: RV30, RV36, RV46 Instructions Includes installation instructions for the particular cooktop model being installed to determine suitability. H Use these downdraft raised vents only with approved Dacor ® cooktops. See the installation instructions for optional cabinet blower (Dacor model CABP3) Part No. 85515 Rev.
Installation Guide
Page 2
...-3226 (U.S.A. For repairs to 5:00 P.M.Pacific Time Web site: www.Dacor.com Dacor Distinctive Service (repairs under warranty call , have questions or problems with installation, contact your Dacor dealer or the Dacor Customer Service Team. The product data label also specifies the power supply requirements...Identification" If you begin the installation process. and Canada) Monday - If You Need Help... Dacor Customer Service RV30 = 30-inch wide raised vent RV36 = 36-inch wide raised vent RV46 = 46-inch wide raised vent Phone: (800) 793-0093 (U.S.A. Important Safety Instructions 1 ...
...-3226 (U.S.A. For repairs to 5:00 P.M.Pacific Time Web site: www.Dacor.com Dacor Distinctive Service (repairs under warranty call , have questions or problems with installation, contact your Dacor dealer or the Dacor Customer Service Team. The product data label also specifies the power supply requirements...Identification" If you begin the installation process. and Canada) Monday - If You Need Help... Dacor Customer Service RV30 = 30-inch wide raised vent RV36 = 36-inch wide raised vent RV46 = 46-inch wide raised vent Phone: (800) 793-0093 (U.S.A. Important Safety Instructions 1 ...