Fluke 902 HVAC Clamp Meter Datasheet
Page 2
... °F) • Probe material: K-type sensor with pvc body • Cable length: 1 m (39 in U.S.A. 10/2006 2645797 D-EN-N Rev B Ordering Information Fluke-902 HVAC Clamp Meter Included AA alkaline batteries (2) Users manual (w/safety information) Soft carrying case TL75 Test Leads (1 pair) 80BK Integrated DMM Temperature Probe (1) Optional accessories H3 Clamp Meter Holster • Rugged...
... °F) • Probe material: K-type sensor with pvc body • Cable length: 1 m (39 in U.S.A. 10/2006 2645797 D-EN-N Rev B Ordering Information Fluke-902 HVAC Clamp Meter Included AA alkaline batteries (2) Users manual (w/safety information) Soft carrying case TL75 Test Leads (1 pair) 80BK Integrated DMM Temperature Probe (1) Optional accessories H3 Clamp Meter Holster • Rugged...
FE 902 Users Manual
Page 1
All product names are trademarks of their respective companies. ® 902 HVAC Clamp Meter Users Manual PN 2547887 May 2006 Rev. 1, 3/07 © 2006-2007 Fluke Corporation. All rights reserved. Printed in China.
All product names are trademarks of their respective companies. ® 902 HVAC Clamp Meter Users Manual PN 2547887 May 2006 Rev. 1, 3/07 © 2006-2007 Fluke Corporation. All rights reserved. Printed in China.
FE 902 Users Manual
Page 7
902 Introduction The Fluke 902 is a hand-held battery-operated HVAC Clamp Meter ("the Meter") that measures: • AC current • DC current (up to 200 µA for flame rod testing) • AC and DC voltages • Capacitance • Resistance • Continuity • Temperature in both Celsius (°C) and Fahrenheit (°F) The Meter comes with: • Two AA alkaline batteries (installed) • Users Manual • Soft carrying case • TL75 Test Leads (one pair) • 80BK Integrated DMM Temperature Probe 1
902 Introduction The Fluke 902 is a hand-held battery-operated HVAC Clamp Meter ("the Meter") that measures: • AC current • DC current (up to 200 µA for flame rod testing) • AC and DC voltages • Capacitance • Resistance • Continuity • Temperature in both Celsius (°C) and Fahrenheit (°F) The Meter comes with: • Two AA alkaline batteries (installed) • Users Manual • Soft carrying case • TL75 Test Leads (one pair) • 80BK Integrated DMM Temperature Probe 1
FE 902 Users Manual
Page 8
902 Users Manual Contacting Fluke To contact Fluke, call one of the following telephone numbers: USA: 1-888-99-FLUKE (1-888-993-5853) Canada: 1-800-36-FLUKE (1-800-363-5853) Europe: +31 402-675-200 Japan: +81-3-3434-0181 Singapore: +65-738-5655 Anywhere in the world: +1-425-446-5500 Or visit Fluke's Web site at : http://register.fluke.com 2 Register the Meter at : www.fluke.com.
902 Users Manual Contacting Fluke To contact Fluke, call one of the following telephone numbers: USA: 1-888-99-FLUKE (1-888-993-5853) Canada: 1-800-36-FLUKE (1-800-363-5853) Europe: +31 402-675-200 Japan: +81-3-3434-0181 Singapore: +65-738-5655 Anywhere in the world: +1-425-446-5500 Or visit Fluke's Web site at : http://register.fluke.com 2 Register the Meter at : www.fluke.com.
FE 902 Users Manual
Page 9
... Do not use the Meter on a circuit with the conductor could result in the Users Manual; XWRead First: Safety Information To ensure safe operation and service of the Meter, follow these instructions: • Read the Users Manual before use and follow all safety instructions. • Use the Meter only as specified... or bus bars. Contact with voltages higher than 600 V or a frequency higher than 400 Hz fundamental. HVAC Clamp Meter Contacting Fluke Safety Information A "XW Warning" statement defines hazardous conditions and actions that could damage the Meter or the equipment under test.
... Do not use the Meter on a circuit with the conductor could result in the Users Manual; XWRead First: Safety Information To ensure safe operation and service of the Meter, follow these instructions: • Read the Users Manual before use and follow all safety instructions. • Use the Meter only as specified... or bus bars. Contact with voltages higher than 600 V or a frequency higher than 400 Hz fundamental. HVAC Clamp Meter Contacting Fluke Safety Information A "XW Warning" statement defines hazardous conditions and actions that could damage the Meter or the equipment under test.
FE 902 Users Manual
Page 10
... readings, the Meter locks and no measurements can lead to electrical shock and injury, replace the batteries as soon as the low battery indicator (B) appears. 902 Users Manual • Use caution when working with a damp cloth and mild detergent only. Such voltages pose a shock hazard. • Clean the case with voltages above 60...
... readings, the Meter locks and no measurements can lead to electrical shock and injury, replace the batteries as soon as the low battery indicator (B) appears. 902 Users Manual • Use caution when working with a damp cloth and mild detergent only. Such voltages pose a shock hazard. • Clean the case with voltages above 60...
FE 902 Users Manual
Page 11
... Current) ~ ; See Users Manual. Risk of danger. T Double insulation B Battery ) Complies with Canadian and US Standards P Conforms to relevant Australian standards Inspected and licensed by TÜV Product Services 5 N10140 s Do not dispose of this manual. , May be used on the Meter or in this product as unsorted municipal waste. Contact Fluke or a qualified recycler...
... Current) ~ ; See Users Manual. Risk of danger. T Double insulation B Battery ) Complies with Canadian and US Standards P Conforms to relevant Australian standards Inspected and licensed by TÜV Product Services 5 N10140 s Do not dispose of this manual. , May be used on the Meter or in this product as unsorted municipal waste. Contact Fluke or a qualified recycler...
FE 902 Users Manual
Page 12
COM CAT µAV 600V efu0001.eps Figure 1. 902 HVAC Clamp Meter Features 6 902 Users Manual Getting Acquainted with the Meter Refer to Figures 1 and 2 and Tables 1 and 2 to become more acquainted with the Meter's features.
COM CAT µAV 600V efu0001.eps Figure 1. 902 HVAC Clamp Meter Features 6 902 Users Manual Getting Acquainted with the Meter Refer to Figures 1 and 2 and Tables 1 and 2 to become more acquainted with the Meter's features.
FE 902 Users Manual
Page 16
V 2. When the voltage drops below 30 V, Zdisappears. 10 Turn the rotary switch to choose AC or DC voltage. The Meter reading appears on the display. Press A to . 3. The display reflects the chosen voltage mode. 4. Note When a measured voltage is above 30 V, Zappears on the display. Use the test leads to take the measurement. 902 Users Manual Using the Meter AC and DC Voltage Measurement To measure AC or DC voltage: 1. Insert the test leads into the Meter.
V 2. When the voltage drops below 30 V, Zdisappears. 10 Turn the rotary switch to choose AC or DC voltage. The Meter reading appears on the display. Press A to . 3. The display reflects the chosen voltage mode. 4. Note When a measured voltage is above 30 V, Zappears on the display. Use the test leads to take the measurement. 902 Users Manual Using the Meter AC and DC Voltage Measurement To measure AC or DC voltage: 1. Insert the test leads into the Meter.
FE 902 Users Manual
Page 18
... wire between the flame sensor probe and control-module wire. 5. Turn heating unit on and check the reading on the Meter to G. 4. Refer to Figure 3): 1. 902 Users Manual Microamps µA Measurement The µA dc (G) function on the Meter is primarily for what the desired reading should be. 12 Break this connection. 3. Using alligator...
... wire between the flame sensor probe and control-module wire. 5. Turn heating unit on and check the reading on the Meter to G. 4. Refer to Figure 3): 1. 902 Users Manual Microamps µA Measurement The µA dc (G) function on the Meter is primarily for what the desired reading should be. 12 Break this connection. 3. Using alligator...
FE 902 Users Manual
Page 20
The display reflects the chosen temperature mode. 4. The reading appears on the display. Position the probe to earth. 14 XW Warning To avoid possible electric shock DO NOT apply the probe tip to any conductor that is greater than 30 V ac, 42 V peak or 60 V dc to take the measurement. 902 Users Manual 1. Connect the 80BK Integrated DMM Temperature Probe to select °C or °F. Press A to the input jacks noting correct polarity of the probe. 2. Turn the rotary switch to F. 3. Note To meet stated accuracy, the 80BK and Meter must be at the same temperature.
The display reflects the chosen temperature mode. 4. The reading appears on the display. Position the probe to earth. 14 XW Warning To avoid possible electric shock DO NOT apply the probe tip to any conductor that is greater than 30 V ac, 42 V peak or 60 V dc to take the measurement. 902 Users Manual 1. Connect the 80BK Integrated DMM Temperature Probe to select °C or °F. Press A to the input jacks noting correct polarity of the probe. 2. Turn the rotary switch to F. 3. Note To meet stated accuracy, the 80BK and Meter must be at the same temperature.
FE 902 Users Manual
Page 22
... to AC current (K). Turn the rotary switch to capacitance (L). When measuring, be properly seated within the jaws, below the horizontal line located on the clamp. 902 Users Manual Capacitance Turn off circuit power, then disconnect and discharge the capacitor before making current measurements. • Do not hold the Meter anywhere beyond the tactile...
... to AC current (K). Turn the rotary switch to capacitance (L). When measuring, be properly seated within the jaws, below the horizontal line located on the clamp. 902 Users Manual Capacitance Turn off circuit power, then disconnect and discharge the capacitor before making current measurements. • Do not hold the Meter anywhere beyond the tactile...
FE 902 Users Manual
Page 24
... off . MAX is displayed and the highest reading detected since entering MIN MAX is displayed. 3. Put the Meter into the desired measurement function and range. 2. 902 Users Manual Backlight Press C to toggle the backlight on . To disable the automatic 2-minute backlight timeout, hold down Cwhile turning the Meter on and off after 2 minutes...
... off . MAX is displayed and the highest reading detected since entering MIN MAX is displayed. 3. Put the Meter into the desired measurement function and range. 2. 902 Users Manual Backlight Press C to toggle the backlight on . To disable the automatic 2-minute backlight timeout, hold down Cwhile turning the Meter on and off after 2 minutes...
FE 902 Users Manual
Page 26
Clean the instrument case with the plastics used in this manual should be performed only by qualified personnel. W Caution To avoid damaging the Meter, do not use aromatic hydrocarbons or chlorinated solvents for cleaning. Cleaning the Meter XWWarning To avoid electrical shock, remove any input signals before cleaning. 902 Users Manual Maintenance XWWarning To avoid possible electric shock or personal injury, repairs or servicing not covered in the Meter. These solutions will react with a damp cloth and mild detergent. 20
Clean the instrument case with the plastics used in this manual should be performed only by qualified personnel. W Caution To avoid damaging the Meter, do not use aromatic hydrocarbons or chlorinated solvents for cleaning. Cleaning the Meter XWWarning To avoid electrical shock, remove any input signals before cleaning. 902 Users Manual Maintenance XWWarning To avoid possible electric shock or personal injury, repairs or servicing not covered in the Meter. These solutions will react with a damp cloth and mild detergent. 20
FE 902 Users Manual
Page 30
902 Users Manual General Specifications Operating Temperature -10 °C to +50 °C Storage Temperature -40 °C to +60 °C Operating Humidity Non condensing (< 10 °C) 90 % RH (10 ...
902 Users Manual General Specifications Operating Temperature -10 °C to +50 °C Storage Temperature -40 °C to +60 °C Operating Humidity Non condensing (< 10 °C) 90 % RH (10 ...