HP UPS Network Module Installation Instructions
Page 2
...User name and password SSL 3.0, TLS 1.0 Microsoft® Internet Explorer 6.x or higher HP Systems Insight Manager Standard IETF UPS MIB (RFC 1628) HP Power MIB (cpqpower.mib) DHCP enabled IP address: 192.168.1.2 (manual configuration) Subnet mask: 255.255.0.0 Gateway: 0.0.0.0 NTP server: pool.ntp.org User ...name: admin Password: admin Password: admin (not modifiable) Synchronize with the UPS Network Module. • You can lose track of the HP UPS Network Module web interface...
...User name and password SSL 3.0, TLS 1.0 Microsoft® Internet Explorer 6.x or higher HP Systems Insight Manager Standard IETF UPS MIB (RFC 1628) HP Power MIB (cpqpower.mib) DHCP enabled IP address: 192.168.1.2 (manual configuration) Subnet mask: 255.255.0.0 Gateway: 0.0.0.0 NTP server: pool.ntp.org User ...name: admin Password: admin Password: admin (not modifiable) Synchronize with the UPS Network Module. • You can lose track of the HP UPS Network Module web interface...
HP R/T3000 G2 UPS User Guide
Page 11
When the switch is restored and the UPS has been manually powered up. NOTE: If the UPS was operating on battery power when the remote switch was closed, no power is available to a remote, normally-open ...
When the switch is restored and the UPS has been manually powered up. NOTE: If the UPS was operating on battery power when the remote switch was closed, no power is available to a remote, normally-open ...
HP R/T3000 G2 UPS User Guide
Page 13
..., operation, and maintenance of personal injury or damage to the equipment, observe local occupational health and safety requirements and guidelines for manual material handling. 45 kg 100 lb This symbol indicates that the UPS exceeds the recommended weight for one individual to handle safely....who are supplied with AC power products. 37 kg 82 lb This symbol indicates that the ERM exceeds the recommended weight for manual material handling. Preparing to the equipment, observe local occupational health and safety requirements and guidelines for one individual to handle safely....
..., operation, and maintenance of personal injury or damage to the equipment, observe local occupational health and safety requirements and guidelines for manual material handling. 45 kg 100 lb This symbol indicates that the UPS exceeds the recommended weight for one individual to handle safely....who are supplied with AC power products. 37 kg 82 lb This symbol indicates that the ERM exceeds the recommended weight for manual material handling. Preparing to the equipment, observe local occupational health and safety requirements and guidelines for one individual to handle safely....
HP R/T3000 G2 UPS User Guide
Page 43
... missing or line and neutral connections are reversed NOTE: For high voltage UPSs, the Site Wiring Fault function is disabled by default, but can be manually enabled. For information on what to do if the self-test detects a problem, see "UPS front panel LED indicators (on page 8) for 3 seconds. Each time...
... missing or line and neutral connections are reversed NOTE: For high voltage UPSs, the Site Wiring Fault function is disabled by default, but can be manually enabled. For information on what to do if the self-test detects a problem, see "UPS front panel LED indicators (on page 8) for 3 seconds. Each time...
HP UPS R/T3000 G2 Installation Instructions
Page 1
... about any of the topics covered in the express warranty statements accompanying such products and services. The only warranties for manual material handling. HP shall not be construed as constituting an additional warranty. WARNING: To reduce the risk of 3300 VA/3000 W (... damage to the equipment, observe local occupational health and safety requirements and guidelines for HP products and services are set forth in this document, see the HP website (http://www.hp.com/go /rackandpower). Precautions WARNING: To prevent personal injury from earth conductor leakage current...
... about any of the topics covered in the express warranty statements accompanying such products and services. The only warranties for manual material handling. HP shall not be construed as constituting an additional warranty. WARNING: To reduce the risk of 3300 VA/3000 W (... damage to the equipment, observe local occupational health and safety requirements and guidelines for HP products and services are set forth in this document, see the HP website (http://www.hp.com/go /rackandpower). Precautions WARNING: To prevent personal injury from earth conductor leakage current...
HP Power Protector User Guide
Page 23
... execute the file with the -silent argument. The uninstall wizard launches. Installing HPPP on Linux operating systems HPPP can be removed manually. During a silent installation, install an HPPP Administrator or Client through the assisted installation method that is properly installed. Click Start>....exe -silent Uninstalling HPPP from the command line, execute the following command: \mc2.exe -uninstall For example: c:\Program Files\HP\HP Power Protector\mc2.exe -uninstall NOTE: Some files might remain following dependency: libunwind-0.98.5-5.el5.ia64.rpm Installing HPPP using the...
... execute the file with the -silent argument. The uninstall wizard launches. Installing HPPP on Linux operating systems HPPP can be removed manually. During a silent installation, install an HPPP Administrator or Client through the assisted installation method that is properly installed. Click Start>....exe -silent Uninstalling HPPP from the command line, execute the following command: \mc2.exe -uninstall For example: c:\Program Files\HP\HP Power Protector\mc2.exe -uninstall NOTE: Some files might remain following dependency: libunwind-0.98.5-5.el5.ia64.rpm Installing HPPP using the...
HP Power Protector User Guide
Page 32
... systems Native uninstallation on a RedHat, SUSE, or derivative system To uninstall HPPP from the command line, execute the following the uninstallation and can be removed manually. Enter Y to remove all files created by the application. 4. Installation 32 Enter Y to proceed with the uninstallation. 3. NOTE: Some files might remain following command: rpm... -e hppp-linux Generic uninstallation To uninstall HPPP using the Generic Package: 1. From the command line, execute the following command: mc2 -uninstall For example: # /usr/local/HP/Power Protector/mc2 -uninstall 2.
... systems Native uninstallation on a RedHat, SUSE, or derivative system To uninstall HPPP from the command line, execute the following the uninstallation and can be removed manually. Enter Y to remove all files created by the application. 4. Installation 32 Enter Y to proceed with the uninstallation. 3. NOTE: Some files might remain following command: rpm... -e hppp-linux Generic uninstallation To uninstall HPPP using the Generic Package: 1. From the command line, execute the following command: mc2 -uninstall For example: # /usr/local/HP/Power Protector/mc2 -uninstall 2.
HP Power Protector User Guide
Page 43
From the command line, execute the following the uninstallation and can be removed manually. Installation 43 Uninstalling HPPP from HP-UX systems To uninstall HPPP: 1. Enter Y to proceed with the uninstallation. 3. Enter Y to confirm removing Power Protector. Enter Y to remove all files created by the application. 4. NOTE: Some files might remain following command: mc2 -uninstall For example: # /opt/HP/HP Power Protector/mc2 -uninstall 2.
From the command line, execute the following the uninstallation and can be removed manually. Installation 43 Uninstalling HPPP from HP-UX systems To uninstall HPPP: 1. Enter Y to proceed with the uninstallation. 3. Enter Y to confirm removing Power Protector. Enter Y to remove all files created by the application. 4. NOTE: Some files might remain following command: mc2 -uninstall For example: # /opt/HP/HP Power Protector/mc2 -uninstall 2.
HP Power Protector User Guide
Page 47
... in the Issued To field is the name of the following : a. The certificate appears. b. c. a. NOTE: If using Mozilla, you can manually import the file into the browser by the administrator. Verify that unauthorized source. After verifying the device, do one of your device. 3. NOTE: ...If using Internet Explorer, you can manually import the file into your device. CAUTION: If you are not sure this is still encrypted. • Exit and import the certificate into...
... in the Issued To field is the name of the following : a. The certificate appears. b. c. a. NOTE: If using Mozilla, you can manually import the file into the browser by the administrator. Verify that unauthorized source. After verifying the device, do one of your device. 3. NOTE: ...If using Internet Explorer, you can manually import the file into your device. CAUTION: If you are not sure this is still encrypted. • Exit and import the certificate into...
HP Power Protector User Guide
Page 48
...)." A quick scan discovers all USB or serially connected UPSs are logged in, you log in with a user name and password. The first time you can manually import the file into two frames: • Menu tree-Contains a list of menu options on the left navigation frame Click Help to view online help...
...)." A quick scan discovers all USB or serially connected UPSs are logged in, you log in with a user name and password. The first time you can manually import the file into two frames: • Menu tree-Contains a list of menu options on the left navigation frame Click Help to view online help...
HP Power Protector User Guide
Page 51
... • Serial number-The serial number of the node • Class-The device type, for example, RS-232 device, USB device, HP Power Protector, or UPS Network Module • OS type-The node operating system • Location-The node location • Contact-The contact..., or • Load alarm threshold-A user specified threshold value that are connected after the application is launched, click Quick scan. 2. To manually discover devices: o Click Quick scan to discover HPPP Administrators and UPS Network Modules that are outside the network segment. Configuration and operation 51 ...
... • Serial number-The serial number of the node • Class-The device type, for example, RS-232 device, USB device, HP Power Protector, or UPS Network Module • OS type-The node operating system • Location-The node location • Contact-The contact..., or • Load alarm threshold-A user specified threshold value that are connected after the application is launched, click Quick scan. 2. To manually discover devices: o Click Quick scan to discover HPPP Administrators and UPS Network Modules that are outside the network segment. Configuration and operation 51 ...
HP Power Protector User Guide
Page 72
... for example, RS-232 device, USB device, or HPPP Administrator • Link-A hyperlinked icon that directs you to the web interface for the HP UPS Network Module, if installed, or the HPPP Administrator ( Communication Loss) HTTP Connection, HTTPS Connection, or • Battery state-The current state...from the UPS battery • Entire UPS-The status of the UPS ( On, Off, Unknown, Internal Failure, On Automatic Bypass, Manual Bypass, Overload) • Load segment-The load segment status ( On, Off, or Unknown) HPPP Client UPS information includes: Configuration and operation 72
... for example, RS-232 device, USB device, or HPPP Administrator • Link-A hyperlinked icon that directs you to the web interface for the HP UPS Network Module, if installed, or the HPPP Administrator ( Communication Loss) HTTP Connection, HTTPS Connection, or • Battery state-The current state...from the UPS battery • Entire UPS-The status of the UPS ( On, Off, Unknown, Internal Failure, On Automatic Bypass, Manual Bypass, Overload) • Load segment-The load segment status ( On, Off, or Unknown) HPPP Client UPS information includes: Configuration and operation 72
HP Power Protector User Guide
Page 73
...device type, for example, RS-232 device, USB device, or HPPP Administrator • Link-A hyperlinked icon that directs you to the web interface for the HP UPS Network Module, if installed, or the HPPP Administrator ( Communication Loss) HTTP Connection, HTTPS Connection, or • Battery state-The current state of ... backup time available from the UPS battery • Entire UPS-The status of the UPS ( On, Off, Unknown, Internal Failure, On Automatic Bypass, Manual Bypass, Overload) • Load segment-The load segment status ( On, Off, or Unknown) Configuration and operation 73
...device type, for example, RS-232 device, USB device, or HPPP Administrator • Link-A hyperlinked icon that directs you to the web interface for the HP UPS Network Module, if installed, or the HPPP Administrator ( Communication Loss) HTTP Connection, HTTPS Connection, or • Battery state-The current state of ... backup time available from the UPS battery • Entire UPS-The status of the UPS ( On, Off, Unknown, Internal Failure, On Automatic Bypass, Manual Bypass, Overload) • Load segment-The load segment status ( On, Off, or Unknown) Configuration and operation 73
HP Power Protector User Guide
Page 88
... application • Events-Displays the list of the following: o Search for each panel you want to display. 3. The Select panels screen appears. 2. Click Save. To manually remove an application from the Notified Applications list, see "Device Discovery screen (on the screen. Click the icon. Select the checkbox for an application using...
... application • Events-Displays the list of the following: o Search for each panel you want to display. 3. The Select panels screen appears. 2. Click Save. To manually remove an application from the Notified Applications list, see "Device Discovery screen (on the screen. Click the icon. Select the checkbox for an application using...
HP Power Protector User Guide
Page 96
... Battery Cleared • UPS On Boost • UPS On Boost Cleared • UPS On Buck • UPS On Buck Cleared • UPS On Manual Bypass • UPS On Manual Bypass Cleared • UPS Output Is Off • UPS Output Is On • UPS Output Overload • UPS Output Overload Cleared • UPS...
... Battery Cleared • UPS On Boost • UPS On Boost Cleared • UPS On Buck • UPS On Buck Cleared • UPS On Manual Bypass • UPS On Manual Bypass Cleared • UPS Output Is Off • UPS Output Is On • UPS Output Overload • UPS Output Overload Cleared • UPS...
HP Power Protector User Guide
Page 113
... package to the directory where you can access the HPPP web interface. To locally access Hyper-V Manager on Windows 2008, select Start>Programs>HP>Power Protector>Open HP Power Protectors from the DOS Windows command, and then go /rackandpower). 2. Read the license agreement, and then click Accept. 4. The... Hyper-V Manager on page 99)." In SSL mode, click Yes to use HPPP: 1. For more information, see the operating system user manual. The HPPP specific ports must be authorized within the firewall of following URLs in a web browser: o https://:4680/ o http://:4679/ 2.
... package to the directory where you can access the HPPP web interface. To locally access Hyper-V Manager on Windows 2008, select Start>Programs>HP>Power Protector>Open HP Power Protectors from the DOS Windows command, and then go /rackandpower). 2. Read the license agreement, and then click Accept. 4. The... Hyper-V Manager on page 99)." In SSL mode, click Yes to use HPPP: 1. For more information, see the operating system user manual. The HPPP specific ports must be authorized within the firewall of following URLs in a web browser: o https://:4680/ o http://:4679/ 2.
HP Power Protector User Guide
Page 116
...Server 4.0: 1. Network architecture All hardware components must be authorized within the firewall of the main operating system, see the HP website (http://www.hp.com/go /rackandpower). For more information, see "System requirements (on page 18)." With an SCP Client, upload ...shutdown.sh script is generated. Download the latest version of compatible UPSs, see the operating system user manual. For a list of HPPP from the HP website (http://www.hp.com/go /rackandpower). o Startup Order-Automatic Startup Hardware architecture For the HPPP installation prerequisites, see ...
...Server 4.0: 1. Network architecture All hardware components must be authorized within the firewall of the main operating system, see the HP website (http://www.hp.com/go /rackandpower). For more information, see "System requirements (on page 18)." With an SCP Client, upload ...shutdown.sh script is generated. Download the latest version of compatible UPSs, see the operating system user manual. For a list of HPPP from the HP website (http://www.hp.com/go /rackandpower). o Startup Order-Automatic Startup Hardware architecture For the HPPP installation prerequisites, see ...
HP Power Protector User Guide
Page 121
...Seconds o Default Shutdown Delay-x Seconds o Startup Order-Automatic Startup Hardware architecture For the HPPP installation prerequisites, see the HP website (http://www.hp.com/go/rackandpower). Network architecture All hardware components must be authorized within the firewall of compatible UPSs, see "System ...requirements (on page 18)." For more information, see the operating system user manual. To the other guest machines to ...
...Seconds o Default Shutdown Delay-x Seconds o Startup Order-Automatic Startup Hardware architecture For the HPPP installation prerequisites, see the HP website (http://www.hp.com/go/rackandpower). Network architecture All hardware components must be authorized within the firewall of compatible UPSs, see "System ...requirements (on page 18)." For more information, see the operating system user manual. To the other guest machines to ...
HP Power Protector User Guide
Page 130
.... Unable to discover a UPS Action: • Verify that the UPS is connected to the correct communications port (COM1, COM2, and so on the graphs. Action: Manually change the serial port parameters in the operating system using the communications cable that came with the UPS. • Verify that resources for the UPS...
.... Unable to discover a UPS Action: • Verify that the UPS is connected to the correct communications port (COM1, COM2, and so on the graphs. Action: Manually change the serial port parameters in the operating system using the communications cable that came with the UPS. • Verify that resources for the UPS...
HP UPS R/T3000 Installation Instructions
Page 1
... Management Pack CD To download the latest software version, see the UPS user guide located on the documentation CD or HP website (http://www.hp.com/go /rackandpower). The only warranties for loads up to a maximum of 3300 VA/3000 W (these numbers might vary by model). For ...source. 37 kg 82 lb This symbol indicates that the UPS exceeds the recommended weight for manual material handling. Nothing herein should be liable for technical or editorial errors or omissions contained herein. HP shall not be construed as constituting an additional warranty. WARNING: To reduce the risk of the...
... Management Pack CD To download the latest software version, see the UPS user guide located on the documentation CD or HP website (http://www.hp.com/go /rackandpower). The only warranties for loads up to a maximum of 3300 VA/3000 W (these numbers might vary by model). For ...source. 37 kg 82 lb This symbol indicates that the UPS exceeds the recommended weight for manual material handling. Nothing herein should be liable for technical or editorial errors or omissions contained herein. HP shall not be construed as constituting an additional warranty. WARNING: To reduce the risk of the...