Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 1
Service and support: Call your local service representative 614-00206-01_EN ENGLISH 9PX6KSP 9PXEBM240SP Installation and user manual Copyright © 2014 EATON All rights reserved.
Service and support: Call your local service representative 614-00206-01_EN ENGLISH 9PX6KSP 9PXEBM240SP Installation and user manual Copyright © 2014 EATON All rights reserved.
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 2
... are examples of symbols used in which case the user will be followed during installation and maintenance of this manual. Do not discard the UPS or the UPS batteries in the trash. SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. Operation of the UPS and batteries. Observe the warning associated with the instruction manual, may cause harmful interference to correct the interference...
... are examples of symbols used in which case the user will be followed during installation and maintenance of this manual. Do not discard the UPS or the UPS batteries in the trash. SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. Operation of the UPS and batteries. Observe the warning associated with the instruction manual, may cause harmful interference to correct the interference...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 3
...room AS DEFINED IN the standard for 6kVA models, in accordance with the National Electric Code. It should be performed or supervised by qualified service personnel. • The system has its own power source (the battery). Consequently, the power outlets may be energized even if the system...Contact with the same type and number of batteries in electrical shock. Product safety • The UPS connection instructions and operation described in the indicated order. • CAUTION - A disconnect switch shall be followed in the manual must be reduced if such grounds are ...
...room AS DEFINED IN the standard for 6kVA models, in accordance with the National Electric Code. It should be performed or supervised by qualified service personnel. • The system has its own power source (the battery). Consequently, the power outlets may be energized even if the system...Contact with the same type and number of batteries in electrical shock. Product safety • The UPS connection instructions and operation described in the indicated order. • CAUTION - A disconnect switch shall be followed in the manual must be reduced if such grounds are ...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 4
... provided with the UPS to carry the unit around. This charges the battery, thus avoiding possible irreversible damage. • During the replacement of the Battery Module, it at least two people (unpacking, lifting, installation in rack system). • For EBM, straps are NO USER SERVICEABLE PARTS inside the UPS. There are provided only for handling operations. •...
... provided with the UPS to carry the unit around. This charges the battery, thus avoiding possible irreversible damage. • During the replacement of the Battery Module, it at least two people (unpacking, lifting, installation in rack system). • For EBM, straps are NO USER SERVICEABLE PARTS inside the UPS. There are provided only for handling operations. •...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 5
... 6.4 User settings...25 7. UPS maintenance 35 9.1 Equipment care...35 9.2 Storing the equipment 35 9.3 When to terminal blocks 22 5.3 Hardwired Input/Output connection 22 6. Troubleshooting 40 10.1 Typical alarms and faults 40 10.2 Silencing the alarm...42 10.3 Service and support...42 11. Introduction 6 1.1 Environmental protection 6 2. Glossary 47 Page 5 ENGLISH Power cable connection 21 5.1 Installation requirements 21 5.2 Access to replace batteries 35 9.4 Replacing batteries...
... 6.4 User settings...25 7. UPS maintenance 35 9.1 Equipment care...35 9.2 Storing the equipment 35 9.3 When to terminal blocks 22 5.3 Hardwired Input/Output connection 22 6. Troubleshooting 40 10.1 Typical alarms and faults 40 10.2 Silencing the alarm...42 10.3 Service and support...42 11. Introduction 6 1.1 Environmental protection 6 2. Glossary 47 Page 5 ENGLISH Power cable connection 21 5.1 Installation requirements 21 5.2 Access to replace batteries 35 9.4 Replacing batteries...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 6
... our web site at powerquality.eaton.com or contact your UPS (Uninterruptible Power System). End of life EATON will process products at the end of ...of recyclable materials. Before installing your electrical equipment. Then follow the indications in compliance with companies in view of their service life in the symbols ...manual to an eco-design approach. Battery The product contains lead-acid batteries that you take the time to applicable local regulations concerning batteries. The battery may be processed according to read the booklet presenting the safety instructions...
... our web site at powerquality.eaton.com or contact your UPS (Uninterruptible Power System). End of life EATON will process products at the end of ...of recyclable materials. Before installing your electrical equipment. Then follow the indications in compliance with companies in view of their service life in the symbols ...manual to an eco-design approach. Battery The product contains lead-acid batteries that you take the time to applicable local regulations concerning batteries. The battery may be processed according to read the booklet presenting the safety instructions...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 7
... erratic. These power problems have the potential to increase battery service life, optimize recharge time, and provide a warning before the end of useful battery life. • Selectable High Efficiency mode of lost productivity and expensive repairs. causing hours of operation. • Standard communication options: Network-MS card (Web/SNMP), one RS-232 communication port, one USB communication port...
... erratic. These power problems have the potential to increase battery service life, optimize recharge time, and provide a warning before the end of useful battery life. • Selectable High Efficiency mode of lost productivity and expensive repairs. causing hours of operation. • Standard communication options: Network-MS card (Web/SNMP), one RS-232 communication port, one USB communication port...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 11
Installation for 9PX 6K SP 3.3 Checking the accessory kit • Verify that the following additional items are included with the UPS: 1 User manual 2 Safety instructions 3 Warranty sheet 4 Software CD-ROM 5 RS232 communication cable 6 USB communication cable 7 Cable gland for Input/Output connection 8 Cover for the terminal block 9 Network-MS communication card 10 Rack kit for 19-inch enclosures 11 Screwdriver 12 2 x internal battery pack 13 Feet 614-00206-01_EN Page 11 ENGLISH 3.
Installation for 9PX 6K SP 3.3 Checking the accessory kit • Verify that the following additional items are included with the UPS: 1 User manual 2 Safety instructions 3 Warranty sheet 4 Software CD-ROM 5 RS232 communication cable 6 USB communication cable 7 Cable gland for Input/Output connection 8 Cover for the terminal block 9 Network-MS communication card 10 Rack kit for 19-inch enclosures 11 Screwdriver 12 2 x internal battery pack 13 Feet 614-00206-01_EN Page 11 ENGLISH 3.
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 17
...-00206-01_EN Page 17 ENGLISH 4. Installation for rack mounting. This step requires two service personnel. Description Weights (lb/kg) 9PX EBM 240SP without internal battery 29 / 13 9PX EBM 240SP internal battery 52 / 23.4 To ease its rack mounting, you ordered other UPS accessories, refer to specific user manuals to check the rack installation with the UPS. •...
...-00206-01_EN Page 17 ENGLISH 4. Installation for rack mounting. This step requires two service personnel. Description Weights (lb/kg) 9PX EBM 240SP without internal battery 29 / 13 9PX EBM 240SP internal battery 52 / 23.4 To ease its rack mounting, you ordered other UPS accessories, refer to specific user manuals to check the rack installation with the UPS. •...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 25
... date Transfers the UPS on Bypass mode / Transfers the UPS on Line mode Starts a manual battery test Clears active fault Returns all supported languages. Audible alarm [Enabled] [Disabled on Bypass Input volt hysteresis Sets input voltage hysteresis from Bypass for high efficiency Overload prealarm [10%] ... [102%] Load % when overload alarm occurs Default settings [English] User selectable when UPS is powered for the first time. [US...
... date Transfers the UPS on Bypass mode / Transfers the UPS on Line mode Starts a manual battery test Clears active fault Returns all supported languages. Audible alarm [Enabled] [Disabled on Bypass Input volt hysteresis Sets input voltage hysteresis from Bypass for high efficiency Overload prealarm [10%] ... [102%] Load % when overload alarm occurs Default settings [English] User selectable when UPS is powered for the first time. [US...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 26
... Automatic battery test Low battery warning Restart bat. vents battery from Bypass in Standby mode. [Disabled] [Bypass for MBP] [Enabled] [Disabled] [Bypass for MBP, the UPS will turn OFF immediately after a complete battery discharge. [Enabled] [Enabled] [Disabled] The UPS automatically starts up time voltage threshold. HMI and settings Page 26 Submenu Cold start Forced reboot Auto restart Auto start on battery power. [Enabled...
... Automatic battery test Low battery warning Restart bat. vents battery from Bypass in Standby mode. [Disabled] [Bypass for MBP] [Enabled] [Disabled] [Bypass for MBP, the UPS will turn OFF immediately after a complete battery discharge. [Enabled] [Enabled] [Disabled] The UPS automatically starts up time voltage threshold. HMI and settings Page 26 Submenu Cold start Forced reboot Auto restart Auto start on battery power. [Enabled...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 29
... mode. If Enabled, the UPS transfers to Bypass even if Bypass AC source is recommended to Bypass. Deep discharge protection This setting is out of Extended Battery Module is enabled. 10 ms or 20 ms can be modified. Warranty is void if deep discharge protection is activated if the battery capacity goes below 20%. The battery test may be set manually...
... mode. If Enabled, the UPS transfers to Bypass even if Bypass AC source is recommended to Bypass. Deep discharge protection This setting is out of Extended Battery Module is enabled. 10 ms or 20 ms can be modified. Warranty is void if deep discharge protection is activated if the battery capacity goes below 20%. The battery test may be set manually...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 35
... the atmosphere is disconnected and turned off. If the UPS requires any type of service life varies, depending on the shipping carton label. The length of transportation, verify that the batteries charge for 48 hours after long-term storage. Replace batteries at least every 4 years to...clean and dust free. The batteries are rated for a long period, recharge the battery every 6 months by connecting the UPS to order new batteries. 614-00206-01_EN Page 35 Contact your service representative to utility power. The EBM charge to replace the batteries. However, Eaton recommends that ...
... the atmosphere is disconnected and turned off. If the UPS requires any type of service life varies, depending on the shipping carton label. The length of transportation, verify that the batteries charge for 48 hours after long-term storage. Replace batteries at least every 4 years to...clean and dust free. The batteries are rated for a long period, recharge the battery every 6 months by connecting the UPS to order new batteries. 614-00206-01_EN Page 35 Contact your service representative to utility power. The EBM charge to replace the batteries. However, Eaton recommends that ...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 36
..., and notes before replacing batteries. • Servicing should be reduced if such grounds are removed during installation and maintenance (applicable to connecting or disconnecting battery terminals. Remove watches, rings, or other metal objects, 2. Released electrolyte is required. If service personnel prefer to remove input power to alter wiring can present a risk of batteries, 4. Attempting to change the batteries, see "UPS...
..., and notes before replacing batteries. • Servicing should be reduced if such grounds are removed during installation and maintenance (applicable to connecting or disconnecting battery terminals. Remove watches, rings, or other metal objects, 2. Released electrolyte is required. If service personnel prefer to remove input power to alter wiring can present a risk of batteries, 4. Attempting to change the batteries, see "UPS...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 37
... side of the battery. Use two hands to "Testing new batteries" on page 39 for proper disposal. • Verify that the replacement batteries have the same rating as the batteries being replaced. • Put the new battery pack into the UPS. Push the battery pack firmly to ...ensure a proper connection. • Screw back the metal protection cover and the front panel, then clip the center cover. • Continue to support the battery...
... side of the battery. Use two hands to "Testing new batteries" on page 39 for proper disposal. • Verify that the replacement batteries have the same rating as the batteries being replaced. • Put the new battery pack into the UPS. Push the battery pack firmly to ...ensure a proper connection. • Screw back the metal protection cover and the front panel, then clip the center cover. • Continue to support the battery...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 38
Press any button to support the battery packs. 2. The front panel displays "Battery test in Normal mode with no active alarms, and the bypass voltage is in progress" and the percentage of the left and right battery packs, and slide the packs out slowly on page 39 for each EBM. Page 38 To ease EBM replacement: You can remove the...
Press any button to support the battery packs. 2. The front panel displays "Battery test in Normal mode with no active alarms, and the bypass voltage is in progress" and the percentage of the left and right battery packs, and slide the packs out slowly on page 39 for each EBM. Page 38 To ease EBM replacement: You can remove the...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 40
... are preventive alarms intended to charge the batteries. Scroll through the listed events or faults. LED is affected. No battery LED is On. Power overload LED is On. If the condition persists, contact your service representative. Apply utility power for specific output overload ranges). Example = "Battery low". • Faults are properly connected. Battery low The UPS is in ABM cycling mode. Beep continuous...
... are preventive alarms intended to charge the batteries. Scroll through the listed events or faults. LED is affected. No battery LED is On. Power overload LED is On. If the condition persists, contact your service representative. Apply utility power for specific output overload ranges). Example = "Battery low". • Faults are properly connected. Battery low The UPS is in ABM cycling mode. Beep continuous...
Eaton 9PX6KSP 9PXEBM240SP Installation and User Manual
Page 42
... condition. 10. If the alarm status changes, the alarm beeps again, overriding the previous alarm silencing. 10.3 Service and support If you have the following information ready when you call your Local Distributor or your local service representative and ask for service: • Model number • Serial number • Firmware version number • Date of failure or problem • Symptoms of...
... condition. 10. If the alarm status changes, the alarm beeps again, overriding the previous alarm silencing. 10.3 Service and support If you have the following information ready when you call your Local Distributor or your local service representative and ask for service: • Model number • Serial number • Firmware version number • Date of failure or problem • Symptoms of...
Product Datasheet
Page 1
...Eaton's 9PX6KSP split-phase 9PX UPS system Package Includes q 9PXEBM240SP 240V Extended Battery Module q External battery cable q Rack-mounting hardware q Tower support stands q Quick start guide Specifications OVERVIEW UPC Code INPUT UPS Input Cord Length (ft.) UPS Input Cord...Installation Options You can mount the 9PXEBM240SP in medical, light industrial, automation and other mission-critical IT applications where space is included for even longer runtime System Requirements Compatible only with highcurrent DC connectors is limited. Input Cord, 3U Rack/Tower MODEL NUMBER: 9PXEBM240SP...
...Eaton's 9PX6KSP split-phase 9PX UPS system Package Includes q 9PXEBM240SP 240V Extended Battery Module q External battery cable q Rack-mounting hardware q Tower support stands q Quick start guide Specifications OVERVIEW UPC Code INPUT UPS Input Cord Length (ft.) UPS Input Cord...Installation Options You can mount the 9PXEBM240SP in medical, light industrial, automation and other mission-critical IT applications where space is included for even longer runtime System Requirements Compatible only with highcurrent DC connectors is limited. Input Cord, 3U Rack/Tower MODEL NUMBER: 9PXEBM240SP...
Product Datasheet
Page 2
... (Europe); Eaton is a registered trademark. Hot-swappable, user replaceable batteries. All Rights Reserved. All other trademarks are the property of their respective owners. 2 / 2 RoHS WARRANTY & SUPPORT Product Warranty Period (U.S. & Canada) Extended Service Plans 2-year limited warranty ADVANCED DEPOT EXCHANGE5-YEAR DEPOT REPAIR: 9SW5Y-18000BCExpedited parts coverage for 5 yearsParts, electronics and UPS batteries coverageNext business day shippingTechnical support5-YEAR ON...
... (Europe); Eaton is a registered trademark. Hot-swappable, user replaceable batteries. All Rights Reserved. All other trademarks are the property of their respective owners. 2 / 2 RoHS WARRANTY & SUPPORT Product Warranty Period (U.S. & Canada) Extended Service Plans 2-year limited warranty ADVANCED DEPOT EXCHANGE5-YEAR DEPOT REPAIR: 9SW5Y-18000BCExpedited parts coverage for 5 yearsParts, electronics and UPS batteries coverageNext business day shippingTechnical support5-YEAR ON...