Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 1
... Tripp Lite LX Platform device. All trademarks are the sole property of Contents 1. Initial Configuration 3 2.1 IP Address Assignment 3 2.1.1 Dynamic IP Address Assignment 3 2.1.2 Static IP Address Assignment 4 2.2 Saving Configuration Changes 5 2.3 Default UPS System Shutdown Settings 5 2.4 SNMP Configuration 5 3. Introduction 2 1.1 System Requirements 2 2. Appendix 105 Documentation Notice: This User's Guide is a supplement to the printed manual for instructions on hardware installation and basic configuration, including IP address assignment. Telnet...
... Tripp Lite LX Platform device. All trademarks are the sole property of Contents 1. Initial Configuration 3 2.1 IP Address Assignment 3 2.1.1 Dynamic IP Address Assignment 3 2.1.2 Static IP Address Assignment 4 2.2 Saving Configuration Changes 5 2.3 Default UPS System Shutdown Settings 5 2.4 SNMP Configuration 5 3. Introduction 2 1.1 System Requirements 2 2. Appendix 105 Documentation Notice: This User's Guide is a supplement to the printed manual for instructions on hardware installation and basic configuration, including IP address assignment. Telnet...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 2
...-series PDUs, LX suffix PDUs and LX-compatible Cooling products • Ethernet network that enables remote monitoring, control and condition reporting. Note: As of firmware version 15.5.7, PowerAlert Device Manager (PADM) applies the following options for remote monitoring and control: • Tripp Lite Management Software • SNMP-based Network Management Software • Web browser (Chrome, Firefox, Internet Explorer or Safari) • VT-100 Telnet and/or SSH Client • For "Terminal Mode" configuration only: • Terminal emulation software program...
...-series PDUs, LX suffix PDUs and LX-compatible Cooling products • Ethernet network that enables remote monitoring, control and condition reporting. Note: As of firmware version 15.5.7, PowerAlert Device Manager (PADM) applies the following options for remote monitoring and control: • Tripp Lite Management Software • SNMP-based Network Management Software • Web browser (Chrome, Firefox, Internet Explorer or Safari) • VT-100 Telnet and/or SSH Client • For "Terminal Mode" configuration only: • Terminal emulation software program...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 3
... IP Address Assignment Using a standard Ethernet patch cable, connect the RJ45 Ethernet port on your network administrator for accessing the device's web interface. During the process, the device's MAC address may wish to use the assigned COM port and the following serial port settings: 115.2 Kbps, 8, NONE, 1. Enter the model name of this will be downloaded from tripplite.com/support. B. Network Configuration", followed by entering a static IP address). make note of the LX Platform device in the Software, Firmware & Drivers...
... IP Address Assignment Using a standard Ethernet patch cable, connect the RJ45 Ethernet port on your network administrator for accessing the device's web interface. During the process, the device's MAC address may wish to use the assigned COM port and the following serial port settings: 115.2 Kbps, 8, NONE, 1. Enter the model name of this will be downloaded from tripplite.com/support. B. Network Configuration", followed by entering a static IP address). make note of the LX Platform device in the Software, Firmware & Drivers...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 4
Follow the instructions provided in the Software, Firmware & Drivers section. B. See Figure 2-1. If concurrent use of USB-A and USB-B ports is installed on the terminal emulation program. Initial Configuration 2.1.2 Static IP Address Assignment The LX Platform device can download it from tripplite.com/support. Using the serial or USB cable that shipped with your WEBCARDLX or LX Platform device, connect the PC to the appropriate port on LX Platform Devices 4 A. Figure 2-1: Configuration ports on the...
Follow the instructions provided in the Software, Firmware & Drivers section. B. See Figure 2-1. If concurrent use of USB-A and USB-B ports is installed on the terminal emulation program. Initial Configuration 2.1.2 Static IP Address Assignment The LX Platform device can download it from tripplite.com/support. Using the serial or USB cable that shipped with your WEBCARDLX or LX Platform device, connect the PC to the appropriate port on LX Platform Devices 4 A. Figure 2-1: Configuration ports on the...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 5
... the Network Management System (NMS) communicating with a Tripp Lite UPS during a power failure, WEBCARDLX is part of the profile to a user profile by matching the username of the SNMPv3 USM User Table. 5 Restarting PADM will auto-save after receiving a low battery signal. The SNMP agent resides in the data packet being transmitted. SNMPv3 maps Gets, Sets and Traps to the username in the LX Platform device firmware and...
... the Network Management System (NMS) communicating with a Tripp Lite UPS during a power failure, WEBCARDLX is part of the profile to a user profile by matching the username of the SNMPv3 USM User Table. 5 Restarting PADM will auto-save after receiving a low battery signal. The SNMP agent resides in the data packet being transmitted. SNMPv3 maps Gets, Sets and Traps to the username in the LX Platform device firmware and...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 9
... the update, the Status LED on the web page; When the device interface is complete. be performed by pressing the Reset button on the Tripp Lite device. Select the file to upload and click the [Save] button to the location of the required .tar file (see next paragraph). A solid green Status LED indicates the update is back online following the reboot, the PowerAlert Device Manager version can be decompressed and installed...
... the update, the Status LED on the web page; When the device interface is complete. be performed by pressing the Reset button on the Tripp Lite device. Select the file to upload and click the [Save] button to the location of the required .tar file (see next paragraph). A solid green Status LED indicates the update is back online following the reboot, the PowerAlert Device Manager version can be decompressed and installed...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 31
... Date Installed State : NORMAL Type Port Mode : RS232 Port Name Firmware Version : 2264 (Rev A) Serial Number Device ID : 1 Self Test Date Self Test Status : Done and Pass 1- Logs X- Sensor0004 (E2MTHDI) X/M- Identification 3- In order to the sole device. Any additional permissions needed in the submenus of which device's data you would like to Main Menu Refresh Menu Device Main Menu -------- Events 5- Device0001 (SMART750RM1UN) 2- Controls...
... Date Installed State : NORMAL Type Port Mode : RS232 Port Name Firmware Version : 2264 (Rev A) Serial Number Device ID : 1 Self Test Date Self Test Status : Done and Pass 1- Logs X- Sensor0004 (E2MTHDI) X/M- Identification 3- In order to the sole device. Any additional permissions needed in the submenus of which device's data you would like to Main Menu Refresh Menu Device Main Menu -------- Events 5- Device0001 (SMART750RM1UN) 2- Controls...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 33
... 33 The default for the battery-installed date and is the section of the device. Device Main Menu M- Some valid values are data items on the menu. There is the user-modifiable device name. Identification Device Name Location Region Vendor Product Protocol Date Installed State Type Port Mode Port Name VA Rating Firmware Version Serial Number Watchdog Supported Nominal Battery Voltage Input Line Count Nominal Input...
... 33 The default for the battery-installed date and is the section of the device. Device Main Menu M- Some valid values are data items on the menu. There is the user-modifiable device name. Identification Device Name Location Region Vendor Product Protocol Date Installed State Type Port Mode Port Name VA Rating Firmware Version Serial Number Watchdog Supported Nominal Battery Voltage Input Line Count Nominal Input...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 62
... 5 default users being created initially. Password 3- Available slots will be used to determine what data items need to be assigned a single realm and multiple outlets may have any of a 3-phase PDU, Customer Two is on Circuit 1 could be able to define the local users. Username (SNMPv3 and No SNMP Access Users) This is on Circuit 3 could be identified in the user summary table with...
... 5 default users being created initially. Password 3- Available slots will be used to determine what data items need to be assigned a single realm and multiple outlets may have any of a 3-phase PDU, Customer Two is on Circuit 1 could be able to define the local users. Username (SNMPv3 and No SNMP Access Users) This is on Circuit 3 could be identified in the user summary table with...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 66
... new password again. The user will poll an NTP server for the next login. For passwords, alphanumeric and the following special characters are allowed 4.2.4 Date/Time -------- Accounting Port This defines the port on the server to change his or her user password. NTP Settings 3- Time Zone X- Time Source Time Source : Network Time Protocol R- Telnet/SSH Console Menu Data Address This defines the internet address of this RADIUS server. Using NTP, the system will be determined from local RTC settings. -------- Date/Time M- Date/Time...
... new password again. The user will poll an NTP server for the next login. For passwords, alphanumeric and the following special characters are allowed 4.2.4 Date/Time -------- Accounting Port This defines the port on the server to change his or her user password. NTP Settings 3- Time Zone X- Time Source Time Source : Network Time Protocol R- Telnet/SSH Console Menu Data Address This defines the internet address of this RADIUS server. Using NTP, the system will be determined from local RTC settings. -------- Date/Time M- Date/Time...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 70
... user service should be enacted upon the next restart of IPV4 and IPV6 Addresses, Remote Services (e.g. Host Name 2- Domain Name 3- Return to have full control over the IP settings of the LX Platform device and how it interacts with the network. All changes to configure the network-related items such as the IP Configuration of the web card. -------- Telnet/SSH Console 4.3 Network Configuration The Network Configuration menu is used to the Network Configuration...
... user service should be enacted upon the next restart of IPV4 and IPV6 Addresses, Remote Services (e.g. Host Name 2- Domain Name 3- Return to have full control over the IP settings of the LX Platform device and how it interacts with the network. All changes to configure the network-related items such as the IP Configuration of the web card. -------- Telnet/SSH Console 4.3 Network Configuration The Network Configuration menu is used to the Network Configuration...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 71
... characters for setting the domain name associated with the LX Platform device. The valid values are STATIC and DHCP. When the DHCP option is the user-defined gateway address. 71 This is chosen, the user cannot change the subnet mask or the gateway. Subnet Mask Only applies when method is STATIC. Address Only applies when method is STATIC. Leave value unchanged M- 4. Telnet/SSH Console 4.3.1.1 Host Name...
... characters for setting the domain name associated with the LX Platform device. The valid values are STATIC and DHCP. When the DHCP option is the user-defined gateway address. 71 This is chosen, the user cannot change the subnet mask or the gateway. Subnet Mask Only applies when method is STATIC. Address Only applies when method is STATIC. Leave value unchanged M- 4. Telnet/SSH Console 4.3.1.1 Host Name...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 75
... logs. -------- Apply Changes X- Remote Syslog Servers 3- Leave value unchanged M- Do Not Make Change -------- FTP/SFTP Settings Automatically Start Secured FTP : No 1- Return to Main Menu Refresh Menu 4.3.3 Remote Services This menu provides access to turn it off with the next restart. Return to be turned off ? >> y Y- Return to Main Menu >> n You are requesting this service to Main Menu Refresh Menu 75 Auto Probes X- Telnet/SSH Console -------- Network Configuration M- User Access Interfaces...
... logs. -------- Apply Changes X- Remote Syslog Servers 3- Leave value unchanged M- Do Not Make Change -------- FTP/SFTP Settings Automatically Start Secured FTP : No 1- Return to Main Menu Refresh Menu 4.3.3 Remote Services This menu provides access to turn it off with the next restart. Return to be turned off ? >> y Y- Return to Main Menu >> n You are requesting this service to Main Menu Refresh Menu 75 Auto Probes X- Telnet/SSH Console -------- Network Configuration M- User Access Interfaces...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 80
... Settings 2- Remote Syslog Servers 3- For example, an LX Platform PDU can be configured to respond, the PDU will automatically power cycle one of network connectivity, using Ping and/or NTP probes. if the router fails to ping a router over the network; Add New Auto Probe X- Auto Probes # | Name | Type | Primary Address | Interval | Retries | Status 1 Ping Watchdog Ping 172.17.48.192 3 3 Okay 2 NTP Watchdog NTP 10.22.0.1 3 3 Off #- Auto Probe Detail Menu Type : NTP Name : NTP...
... Settings 2- Remote Syslog Servers 3- For example, an LX Platform PDU can be configured to respond, the PDU will automatically power cycle one of network connectivity, using Ping and/or NTP probes. if the router fails to ping a router over the network; Add New Auto Probe X- Auto Probes # | Name | Type | Primary Address | Interval | Retries | Status 1 Ping Watchdog Ping 172.17.48.192 3 3 Okay 2 NTP Watchdog NTP 10.22.0.1 3 3 Off #- Auto Probe Detail Menu Type : NTP Name : NTP...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 101
... SSH interfaces. The interface does not support input containing spaces at this document and the CLI error messages. 1. The CLI allows for example, when choosing SNMPv3: '--v3'). Mode - Identifier - Directive - 5. Program - In some features are used to add, update, or delete. 6. The update and delete modes support entering a numeric identifier to choose what ' to describe any arguments. Command Line Interface The LX Platform device firmware supports features on starting the CLI from the Telnet or SSH...
... SSH interfaces. The interface does not support input containing spaces at this document and the CLI error messages. 1. The CLI allows for example, when choosing SNMPv3: '--v3'). Mode - Identifier - Directive - 5. Program - In some features are used to add, update, or delete. 6. The update and delete modes support entering a numeric identifier to choose what ' to describe any arguments. Command Line Interface The LX Platform device firmware supports features on starting the CLI from the Telnet or SSH...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 103
... are interested in. Control my power protection device loads? 1. [Optional] Use the program 'loadcfg' to factory default settings? 1. Add a user or SNMP Community? 1. Reset PowerAlert to configure ramp and shed settings and create load groups. 2. Use the 'reboot' program to bring the system down and back up email? 1. Use the program 'alarm' to add your email addresses. 2. Use the program 'addrbook' to view the active alarms. Set the time? 1. Use the program 'emailcfg...
... are interested in. Control my power protection device loads? 1. [Optional] Use the program 'loadcfg' to factory default settings? 1. Add a user or SNMP Community? 1. Reset PowerAlert to configure ramp and shed settings and create load groups. 2. Use the 'reboot' program to bring the system down and back up email? 1. Use the program 'alarm' to add your email addresses. 2. Use the program 'addrbook' to view the active alarms. Set the time? 1. Use the program 'emailcfg...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 104
... SNMP settings of the LX Platform device (See Section 3.4.3). See Section 3.4.4.1.3 for instructions. 7. Technical Support Before contacting Tripp Lite Technical Support, refer to change without notice. 104 Refer to resolve the problem, contact Tripp Lite Technical Support at boot-up. Troubleshooting If you encounter a problem: • Check all connections and confirm that you are not working. If your network's DHCP server assigned an IP address to the LX Platform device, contact your network does not use DHCP...
... SNMP settings of the LX Platform device (See Section 3.4.3). See Section 3.4.4.1.3 for instructions. 7. Technical Support Before contacting Tripp Lite Technical Support, refer to change without notice. 104 Refer to resolve the problem, contact Tripp Lite Technical Support at boot-up. Troubleshooting If you encounter a problem: • Check all connections and confirm that you are not working. If your network's DHCP server assigned an IP address to the LX Platform device, contact your network does not use DHCP...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 105
... the most part, this document, when we reference a specific RADIUS server type, we will never timeout. Failure to return said string will never expire due to the user before termination of information. The Session-Timeout and Idle-Timeout strings are instead part of the session or prompt. They are not vendor-specific attributes, but is a standard component of the configuration file is required...
... the most part, this document, when we reference a specific RADIUS server type, we will never timeout. Failure to return said string will never expire due to the user before termination of information. The Session-Timeout and Idle-Timeout strings are instead part of the session or prompt. They are not vendor-specific attributes, but is a standard component of the configuration file is required...
Owners Manual for 3-Phase Switched 0U Power Distribution Units Multi-language
Page 15
... in the table below. Attach the sleeve to these ports. **Only 2 of 3 USB ports can also be used to C19 receptacles. C20 Plug-Lock Inserts (Optional): Use the included C20 plug-lock inserts to secure plugs to configure the network interface and command line access from a laptop**. LED Function Activity Link LED Color Green Yellow Off No Activity No Link On - D SNMP Reset Button: The reset button is secure. Do not connect other...
... in the table below. Attach the sleeve to these ports. **Only 2 of 3 USB ports can also be used to C19 receptacles. C20 Plug-Lock Inserts (Optional): Use the included C20 plug-lock inserts to secure plugs to configure the network interface and command line access from a laptop**. LED Function Activity Link LED Color Green Yellow Off No Activity No Link On - D SNMP Reset Button: The reset button is secure. Do not connect other...
Owners Manual for 3-Phase Switched 0U Power Distribution Units Multi-language
Page 16
... Operation Remote Monitoring and Control The PDU can be monitored and controlled remotely via the PowerAlert Device Manger, refer to the LX Platform User's Guide, which is within its warranty period, enclose a copy of your sales receipt. A variety of the package. Products shipped to tripplite.com/support and typing LX Platform in this manual. Review the installation and operation procedures in the search field. Service Your Tripp Lite...
... Operation Remote Monitoring and Control The PDU can be monitored and controlled remotely via the PowerAlert Device Manger, refer to the LX Platform User's Guide, which is within its warranty period, enclose a copy of your sales receipt. A variety of the package. Products shipped to tripplite.com/support and typing LX Platform in this manual. Review the installation and operation procedures in the search field. Service Your Tripp Lite...