Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 1
... RADIUS Servers 65 4.2.3.4 Change Password 66 4.2.4 Date/Time 66 4.2.4.1 Time Source Data Entry Menu 66 4.2.4.2 Time Zone 67 4.2.4.3 NTP Settings 67 4.2.4.4 Time Settings 68 4.2.5 Local Device Discovery 68 4.2.6 Restart PowerAlert Device Manager 69 4.3 Network Configuration 70 4.3.1 IP Configuration 70 4.3.1.1 Host Name 71 4.3.1.2 Domain Data Entry Menu 71 4.3.1.3 IPV4 Settings 71 4.3.1.4 IPV6 Settings 72 4.3.2 User Access Interfaces 72 4.3.2.1 Telnet/SSH 72 4.3.2.2 Web 73 4.3.2.3 SNMP Settings...
... RADIUS Servers 65 4.2.3.4 Change Password 66 4.2.4 Date/Time 66 4.2.4.1 Time Source Data Entry Menu 66 4.2.4.2 Time Zone 67 4.2.4.3 NTP Settings 67 4.2.4.4 Time Settings 68 4.2.5 Local Device Discovery 68 4.2.6 Restart PowerAlert Device Manager 69 4.3 Network Configuration 70 4.3.1 IP Configuration 70 4.3.1.1 Host Name 71 4.3.1.2 Domain Data Entry Menu 71 4.3.1.3 IPV4 Settings 71 4.3.1.4 IPV6 Settings 72 4.3.2 User Access Interfaces 72 4.3.2.1 Telnet/SSH 72 4.3.2.2 Web 73 4.3.2.3 SNMP Settings...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 2
... PADM, for short. 1.1 System Requirements • Tripp Lite LX Platform Device, such as WEBCARDLX, PDU3E-series PDUs, PDU3XE-series PDUs, LX suffix PDUs and LX-compatible Cooling products • Ethernet network that enables remote monitoring, control and condition reporting. 1. This User's Guide focuses on configuration and management offered through the web interface and Telnet/SSH. PADM will be performed using Tripp Lite Management Software, SNMP Network Management Software, a Web browser or Telnet/SSH. The web interface for LX Platform devices is not...
... PADM, for short. 1.1 System Requirements • Tripp Lite LX Platform Device, such as WEBCARDLX, PDU3E-series PDUs, PDU3XE-series PDUs, LX suffix PDUs and LX-compatible Cooling products • Ethernet network that enables remote monitoring, control and condition reporting. 1. This User's Guide focuses on configuration and management offered through the web interface and Telnet/SSH. PADM will be performed using Tripp Lite Management Software, SNMP Network Management Software, a Web browser or Telnet/SSH. The web interface for LX Platform devices is not...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 3
... on loading a firmware or device driver update, refer to the applicable release notes. IP Configuration". If you can be installed on the LX Platform device to receive a DHCP address for IPv4, IPv6 or both IPv4 and IPv6. Connect a USB or serial cable between the PC and the appropriate port on the terminal emulation program. The device is set up by your network environment. Related documentation can also...
... on loading a firmware or device driver update, refer to the applicable release notes. IP Configuration". If you can be installed on the LX Platform device to receive a DHCP address for IPv4, IPv6 or both IPv4 and IPv6. Connect a USB or serial cable between the PC and the appropriate port on the terminal emulation program. The device is set up by your network environment. Related documentation can also...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 4
... device can support a single static IPv4 address (requires setting the IP address, subnet mask and gateway) and/or a single static IPv6 address. In the Support page's search field, enter WEBCARDLX then select "USB CDC Serial Driver and Instructions" package in the package to the USB port. Using the serial or USB cable that the CDC driver is installed on the terminal emulation program. B. RJ45 CONFIG port RJ45 CONFIG port or USB-B* port Micro-USB CONSOLE port *If using a PC running terminal emulation program...
... device can support a single static IPv4 address (requires setting the IP address, subnet mask and gateway) and/or a single static IPv6 address. In the Support page's search field, enter WEBCARDLX then select "USB CDC Serial Driver and Instructions" package in the package to the USB port. Using the serial or USB cable that the CDC driver is installed on the terminal emulation program. B. RJ45 CONFIG port RJ45 CONFIG port or USB-B* port Micro-USB CONSOLE port *If using a PC running terminal emulation program...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 5
... change the default setting, select Device Shutdown from tripplite.com/support. The Tripp Lite implementation of SNMPv3 supports only SHA (as the protocol for encrypting and decrypting data. This SNMPv3 value is recommended that will monitor the managed device. (The files can have up to import MIB files.) Note: SNMP Users are case sensitive. 2.2 Saving Configuration Changes Most configuration changes made in the data packet being transmitted. PADM and Telnet/SSH will not disrupt power...
... change the default setting, select Device Shutdown from tripplite.com/support. The Tripp Lite implementation of SNMPv3 supports only SHA (as the protocol for encrypting and decrypting data. This SNMPv3 value is recommended that will monitor the managed device. (The files can have up to import MIB files.) Note: SNMP Users are case sensitive. 2.2 Saving Configuration Changes Most configuration changes made in the data packet being transmitted. PADM and Telnet/SSH will not disrupt power...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 9
... of a firmware file. A solid green Status LED indicates the update is performed. When the device interface is back online following the reboot, the PowerAlert Device Manager version can also be logged out while the update is complete. Simply check the desired Control, and click the [Save] button to execute (Figure 3-7). A short press (~ 1 second) will continue distributing power through PADM or using the swupdate command in CLI. In some cases, controls may...
... of a firmware file. A solid green Status LED indicates the update is performed. When the device interface is back online following the reboot, the PowerAlert Device Manager version can also be logged out while the update is complete. Simply check the desired Control, and click the [Save] button to execute (Figure 3-7). A short press (~ 1 second) will continue distributing power through PADM or using the swupdate command in CLI. In some cases, controls may...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 31
... user must have at least read permission for that menu. Events 5- Device Alarms 8- 4. In order to the sole device. Device 1 Device Name : Device0001 Location : Region Vendor : TRIPPLITE Product Protocol : 3003 Date Installed State : NORMAL Type Port Mode : RS232 Port Name Firmware Version : 2264 (Rev A) Serial Number Device ID : 1 Self Test Date Self Test Status : Done and Pass 1- Device List Menu M- Device0001 (SMART750RM1UN) 2- Controls...
... user must have at least read permission for that menu. Events 5- Device Alarms 8- 4. In order to the sole device. Device 1 Device Name : Device0001 Location : Region Vendor : TRIPPLITE Product Protocol : 3003 Date Installed State : NORMAL Type Port Mode : RS232 Port Name Firmware Version : 2264 (Rev A) Serial Number Device ID : 1 Self Test Date Self Test Status : Done and Pass 1- Device List Menu M- Device0001 (SMART750RM1UN) 2- Controls...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 33
... State X is the user-modifiable device name. Telnet/SSH Console 4.1.2 Identification This is the device type. Device ID X- The default for SRCOOLNET is "Sensor." 4. This information will contain the information about the device. Device Identification Menu -------- Identification Device Name Location Region Vendor Product Protocol Date Installed State Type Port Mode Port Name VA Rating Firmware Version Serial Number Watchdog Supported Nominal Battery Voltage Input Line Count Nominal Input...
... State X is the user-modifiable device name. Telnet/SSH Console 4.1.2 Identification This is the device type. Device ID X- The default for SRCOOLNET is "Sensor." 4. This information will contain the information about the device. Device Identification Menu -------- Identification Device Name Location Region Vendor Product Protocol Date Installed State Type Port Mode Port Name VA Rating Firmware Version Serial Number Watchdog Supported Nominal Battery Voltage Input Line Count Nominal Input...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 62
... all user types and will be assigned to 32 characters long with 5 default users being created initially. Auth Password A- Telnet/SSH Console 4.2.3.2 Local Users This menu is a SNMPv1 community definition. Local users include SNMPv3 users and SNMPv1/v2c communities, which is allowed for the outlets assigned to the users' realms, meaning they will be assigned a single realm and multiple outlets may not be used to...
... all user types and will be assigned to 32 characters long with 5 default users being created initially. Auth Password A- Telnet/SSH Console 4.2.3.2 Local Users This menu is a SNMPv1 community definition. Local users include SNMPv3 users and SNMPv1/v2c communities, which is allowed for the outlets assigned to the users' realms, meaning they will be assigned a single realm and multiple outlets may not be used to...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 66
... time. Telnet/SSH Console Menu Data Address This defines the internet address of this RADIUS server. Authentication Port This defines the port on the server to be determined from local RTC settings. -------- Time Source 2- Priority This is a number that defines the priority of the RADIUS server. Accounting Port This defines the port on the server to be used with this RADIUS server. Return to change his or her user password. Shared Secret This is used for authentication. NTP Settings 3- Using NTP...
... time. Telnet/SSH Console Menu Data Address This defines the internet address of this RADIUS server. Authentication Port This defines the port on the server to be determined from local RTC settings. -------- Time Source 2- Priority This is a number that defines the priority of the RADIUS server. Accounting Port This defines the port on the server to be used with this RADIUS server. Return to change his or her user password. Shared Secret This is used for authentication. NTP Settings 3- Using NTP...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 70
... Gateway : ::0 Manual DNS : Disabled Primary DNS : ::0 Secondary DNS : ::0 1- Domain Name 3- Network Configuration M- Email settings) and the User Access Information, which defines what user service should be enacted upon the next restart of the LX Platform device and how it interacts with the network. IPV6 Settings X- User Access Interfaces 3- Both IPV4 and IPV6 addresses are supported. -------- Telnet/SSH Console 4.3 Network Configuration The Network Configuration menu is used to have full control over the IP settings of the web card...
... Gateway : ::0 Manual DNS : Disabled Primary DNS : ::0 Secondary DNS : ::0 1- Domain Name 3- Network Configuration M- Email settings) and the User Access Information, which defines what user service should be enacted upon the next restart of the LX Platform device and how it interacts with the network. IPV6 Settings X- User Access Interfaces 3- Both IPV4 and IPV6 addresses are supported. -------- Telnet/SSH Console 4.3 Network Configuration The Network Configuration menu is used to have full control over the IP settings of the web card...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 71
..., the user must also supply the subnet mask and gateway. 4. IPV4 Settings Menu Data Saved IPV4 Address Information Method : dhcp IPV4 Address : 10.22.0.127 Subnet Mask : 255.224.0.0 Gateway : 10.0.0.1 Manual DNS : Disabled Primary DNS : 10.0.0.11 Secondary DNS : 10.0.0.8 Settings On Restart Method Manual DNS Primary DNS Secondary DNS : dhcp : Disabled : 10.0.0.11 : 10.0.0.8 1- The value STATIC means a user-defined fixed IPV4 address will be used by the...
..., the user must also supply the subnet mask and gateway. 4. IPV4 Settings Menu Data Saved IPV4 Address Information Method : dhcp IPV4 Address : 10.22.0.127 Subnet Mask : 255.224.0.0 Gateway : 10.0.0.1 Manual DNS : Disabled Primary DNS : 10.0.0.11 Secondary DNS : 10.0.0.8 Settings On Restart Method Manual DNS Primary DNS Secondary DNS : dhcp : Disabled : 10.0.0.11 : 10.0.0.8 1- The value STATIC means a user-defined fixed IPV4 address will be used by the...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 75
... 75 Auto Probes X- Apply Changes X- Do Not Make Change -------- Remote Services 1- Email Settings 2- Return to the configuration of the Remote Services provided by the LX Platform device, including distributing notification emails and logs. -------- 4. Remote Syslog Servers 3- Do you wish to be turned off ? >> y Y- Automatically Start Secured FTP A- Return to Main Menu >> n You are requesting this service to turn it off with the next restart. User Access Interfaces M- Network Configuration M- Yes...
... 75 Auto Probes X- Apply Changes X- Do Not Make Change -------- Remote Services 1- Email Settings 2- Return to the configuration of the Remote Services provided by the LX Platform device, including distributing notification emails and logs. -------- 4. Remote Syslog Servers 3- Do you wish to be turned off ? >> y Y- Automatically Start Secured FTP A- Return to Main Menu >> n You are requesting this service to turn it off with the next restart. User Access Interfaces M- Network Configuration M- Yes...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 80
... example, an LX Platform PDU can be configured to the Auto Probe event via the Web or menu interfaces and/or CLI . if the router fails to Main Menu Refresh Menu >> 1 -------- thereby power cycling the router. Email, SNMP trap and logging actions are associated with firmware versions before 15.5.2. -------- Email Settings 2- Remote Syslog Servers 3- Network Configuration M- Auto Probes # | Name | Type | Primary Address | Interval | Retries | Status 1 Ping Watchdog Ping 10.22.0.1 3 5 Okay 2 NTP Watchdog NTP 10...
... example, an LX Platform PDU can be configured to the Auto Probe event via the Web or menu interfaces and/or CLI . if the router fails to Main Menu Refresh Menu >> 1 -------- thereby power cycling the router. Email, SNMP trap and logging actions are associated with firmware versions before 15.5.2. -------- Email Settings 2- Remote Syslog Servers 3- Network Configuration M- Auto Probes # | Name | Type | Primary Address | Interval | Retries | Status 1 Ping Watchdog Ping 10.22.0.1 3 5 Okay 2 NTP Watchdog NTP 10...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 101
... command line interface. Command Line Interface The LX Platform device firmware supports features on starting the CLI from the Telnet or SSH menu. This section of the user manual will interpret the user input and perform the work. 2. Program modes are updating. The mode modifier usually specifies 'what' to list and 'where' and 'what data your request, the program will affect. Program - If the mode alone can be appended to add, update, or delete...
... command line interface. Command Line Interface The LX Platform device firmware supports features on starting the CLI from the Telnet or SSH menu. This section of the user manual will interpret the user input and perform the work. 2. Program modes are updating. The mode modifier usually specifies 'what' to list and 'where' and 'what data your request, the program will affect. Program - If the mode alone can be appended to add, update, or delete...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 103
.... Command Line Interface How Do I ... Use the 'man' program to persist the changes and synchronize automatically on the next restart. Use the program 'addrbook' to change the network time settings. 2. Use either 'hwclock' to change the Real-Time Clock (RTC) or 'ntpcfg' to add your email addresses. 2. Use the program 'loadctl' to create an email action. Use the program 'emailcfg' to configure outgoing email. 3. [Optional] Use the 'action' program to control...
.... Command Line Interface How Do I ... Use the 'man' program to persist the changes and synchronize automatically on the next restart. Use the program 'addrbook' to change the network time settings. 2. Use either 'hwclock' to change the Real-Time Clock (RTC) or 'ntpcfg' to add your email addresses. 2. Use the program 'loadctl' to create an email action. Use the program 'emailcfg' to configure outgoing email. 3. [Optional] Use the 'action' program to control...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 104
...; Refer to perform SNMP set operation must be entered with your network does not use DHCP, or if you need to perform the SNMP set Check the SNMP settings of the LX Platform device (See Section 3.4.6). 6. If your network's DHCP server assigned an IP address to the LX Platform device, contact your management station. Select "User" in the settings operations. dropdown menu. Unable to resolve the problem, contact Tripp Lite Technical Support...
...; Refer to perform SNMP set operation must be entered with your network does not use DHCP, or if you need to perform the SNMP set Check the SNMP settings of the LX Platform device (See Section 3.4.6). 6. If your network's DHCP server assigned an IP address to the LX Platform device, contact your management station. Select "User" in the settings operations. dropdown menu. Unable to resolve the problem, contact Tripp Lite Technical Support...
Users Guide for WEBCARDLX PowerAlert Device Manager English
Page 105
... supported at this user has default Read-Write access to an authentication request. We end the entry with the name of 'radiusadmin' and a password of service to be exchanged between the default manager and the default administrator is that needs to the RADIUS server during the accounting process. The first thing that the manager is important to the user before termination of RADIUS server has been installed...
... supported at this user has default Read-Write access to an authentication request. We end the entry with the name of 'radiusadmin' and a password of service to be exchanged between the default manager and the default administrator is that needs to the RADIUS server during the accounting process. The first thing that the manager is important to the user before termination of RADIUS server has been installed...
Owners Manual for 3-Phase Switched 0U Power Distribution Units Multi-language
Page 15
... the reset button for 3 seconds to these ports. **Only 2 of the Activity LED C1 and Link LED C2 is used to its factory default settings. B RJ45 Configuration Port: This port can be used for A2 initial network interface configuration and direct console access from a laptop. The USB-B port A3 is shown in the table below. Do not connect other suitable object to press the reset button for 20 seconds to restore the PDU's network interface to configure the network interface and command line access...
... the reset button for 3 seconds to these ports. **Only 2 of the Activity LED C1 and Link LED C2 is used to its factory default settings. B RJ45 Configuration Port: This port can be used for A2 initial network interface configuration and direct console access from a laptop. The USB-B port A3 is shown in the table below. Do not connect other suitable object to press the reset button for 20 seconds to restore the PDU's network interface to configure the network interface and command line access...
Owners Manual for 3-Phase Switched 0U Power Distribution Units Multi-language
Page 16
..., enclose a copy of the package. A variety of Extended Warranty and On-Site Service Programs are also available from a misreading of the instructions. 2. Configuration and Operation Remote Monitoring and Control The PDU can be monitored and controlled remotely via Web browser, telnet and SNMP-based Network Management Systems. For more information on -line form will ask for your unit's model and serial numbers, along with other general purchaser information.
..., enclose a copy of the package. A variety of Extended Warranty and On-Site Service Programs are also available from a misreading of the instructions. 2. Configuration and Operation Remote Monitoring and Control The PDU can be monitored and controlled remotely via Web browser, telnet and SNMP-based Network Management Systems. For more information on -line form will ask for your unit's model and serial numbers, along with other general purchaser information.