Owners Manual
Page 1
All rights reserved. 1 Owner's Manual SmartOnline® SVTX 3-Phase UPS Systems Models: SVT10KX, SVT20KX, SVT30KX (Series Number: AG-0149) (Series Number: AG-014A) (Series Number: AG-014B) Input: 220/230/240V (Ph-N), 380/400/415V (Ph-Ph), 30 4-Wire + PE Español p.33 • Français p.65 p.97 1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support Copyright © 2016 Tripp Lite.
All rights reserved. 1 Owner's Manual SmartOnline® SVTX 3-Phase UPS Systems Models: SVT10KX, SVT20KX, SVT30KX (Series Number: AG-0149) (Series Number: AG-014A) (Series Number: AG-014B) Input: 220/230/240V (Ph-N), 380/400/415V (Ph-Ph), 30 4-Wire + PE Español p.33 • Français p.65 p.97 1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support Copyright © 2016 Tripp Lite.
Owners Manual
Page 2
... 29 7.1 Storage...29 7.2 Maintenance...29 7.3 Battery...29 7.4 Fan...29 8. Operation...11 4.1 Button Operation...11 4.2 LED Indicators and LCD Panel...11 4.3 Audible Alarm...13 4.4 Single UPS Operation...13 4.5 Parallel UPS Operation...15 4.6 LCD Panel Abbreviations...16 4.7 LCD Settings...17 4.8 Operating Mode/Status Description...22 4.9 Fault Codes...26 4.10 Warning Indicator...26 4.11 Warning Code...27 5. Specifications...30 9. Warranty...32 2
... 29 7.1 Storage...29 7.2 Maintenance...29 7.3 Battery...29 7.4 Fan...29 8. Operation...11 4.1 Button Operation...11 4.2 LED Indicators and LCD Panel...11 4.3 Audible Alarm...13 4.4 Single UPS Operation...13 4.5 Parallel UPS Operation...15 4.6 LCD Panel Abbreviations...16 4.7 LCD Settings...17 4.8 Operating Mode/Status Description...22 4.9 Fault Codes...26 4.10 Warning Indicator...26 4.11 Warning Code...27 5. Specifications...30 9. Warranty...32 2
Owners Manual
Page 3
...-quality incoming power without removing power from power fluctuations and interruptions. Introduction Tripp Lite's SmartOnline SVTKX-Series Uninterruptible Power Supply (UPS) is ideally suited for protecting critical electrical equipment for increased capacity and fault tolerance • ECO mode allowing the UPS to operate on bypass in 10kVA, 20kVA and 30kVA models, these UPS systems are designed to support the load...
...-quality incoming power without removing power from power fluctuations and interruptions. Introduction Tripp Lite's SmartOnline SVTKX-Series Uninterruptible Power Supply (UPS) is ideally suited for protecting critical electrical equipment for increased capacity and fault tolerance • ECO mode allowing the UPS to operate on bypass in 10kVA, 20kVA and 30kVA models, these UPS systems are designed to support the load...
Owners Manual
Page 4
... or effectiveness is connected. Blown fuses should be replaced only with insulated handles. Disconnect and turn off or put into manual bypass and fuses should be removed from the battery supply. The batteries are no user-serviceable parts inside. • Batteries can reasonably be live even when the UPS is operating from all Tripp Lite SmartOnline SVT 3-Phase 10kVA, 20kVA and 30kVA...
... or effectiveness is connected. Blown fuses should be replaced only with insulated handles. Disconnect and turn off or put into manual bypass and fuses should be removed from the battery supply. The batteries are no user-serviceable parts inside. • Batteries can reasonably be live even when the UPS is operating from all Tripp Lite SmartOnline SVT 3-Phase 10kVA, 20kVA and 30kVA...
Owners Manual
Page 5
... with local electrical codes and regulations. 2.7...Installation Do not connect appliances or devices that any maintenance bypass panel used is connected to a DC energy source (battery). Do not install...Owner's Manual and the safety instructions carefully before being installed. The isolation device must be provided in the original packaging to carry the UPS input current. • This UPS should be completely dry before installing or using the unit. 2.4 Transportation and Storage Transport the UPS system only in the building wiring installation. Isolate Uninterruptible Power...
... with local electrical codes and regulations. 2.7...Installation Do not connect appliances or devices that any maintenance bypass panel used is connected to a DC energy source (battery). Do not install...Owner's Manual and the safety instructions carefully before being installed. The isolation device must be provided in the original packaging to carry the UPS input current. • This UPS should be completely dry before installing or using the unit. 2.4 Transportation and Storage Transport the UPS system only in the building wiring installation. Isolate Uninterruptible Power...
Owners Manual
Page 6
... IEC/EN 61000-2-2 Warning: This is any time, as this will cancel the protective earth of the UPS system. Installation and Setup 3.1 Unpacking and Inspection Unpack the unit and inspect the contents. Make sure to inspect the unit prior to prevent disturbances...installation. The shipping packaging contains: • One (1) UPS • One (1) Owner's Manual • One (1) Parallel Cable (For SVT20KX and SVT30KX model) • One (1) Share Current Cable (For SVT20KX and SVT30KX model) Note: Do not turn on the UPS or the building wiring terminals at any damage or missing parts...
... IEC/EN 61000-2-2 Warning: This is any time, as this will cancel the protective earth of the UPS system. Installation and Setup 3.1 Unpacking and Inspection Unpack the unit and inspect the contents. Make sure to inspect the unit prior to prevent disturbances...installation. The shipping packaging contains: • One (1) UPS • One (1) Owner's Manual • One (1) Parallel Cable (For SVT20KX and SVT30KX model) • One (1) Share Current Cable (For SVT20KX and SVT30KX model) Note: Do not turn on the UPS or the building wiring terminals at any damage or missing parts...
Owners Manual
Page 7
... 7 97 10 10 7 7 8 9 9 8 8 Diagram 1: SVT10KX Rear Panel Diagram 2: SVT20KX Rear Panel Diagram 3: SVT30KX Rear Panel 1 Emergency Power Off (EPO) Connector 2 RS-232 Port 3 Share Current Port (For SVT20KX / SVT30KX Model) 4 SNMP Accessory Slot 5 Parallel Ports (For SVT20KX / SVT30KX Model) 6 Fans 7 External Battery Connector 8 Input/Output Terminal Conduit Cover Box 9 Line Input Circuit Breaker 10 Maintenance Bypass Switch (For Service Personnel Use Only...
... 7 97 10 10 7 7 8 9 9 8 8 Diagram 1: SVT10KX Rear Panel Diagram 2: SVT20KX Rear Panel Diagram 3: SVT30KX Rear Panel 1 Emergency Power Off (EPO) Connector 2 RS-232 Port 3 Share Current Port (For SVT20KX / SVT30KX Model) 4 SNMP Accessory Slot 5 Parallel Ports (For SVT20KX / SVT30KX Model) 6 Fans 7 External Battery Connector 8 Input/Output Terminal Conduit Cover Box 9 Line Input Circuit Breaker 10 Maintenance Bypass Switch (For Service Personnel Use Only...
Owners Manual
Page 8
... be performed by qualified service personnel only, following all the precautions listed in this manual and adhering to installation, as shown below. Potentially lethal high voltage exists within the batteries, even when not connected to installation. Figure 3-2 SVT10KX SVT20KX Figure 3-3: Location of 1Nm. 8 SVT30KX Battery connection should be connected prior to local electrical codes. The red wire for all...
... be performed by qualified service personnel only, following all the precautions listed in this manual and adhering to installation, as shown below. Potentially lethal high voltage exists within the batteries, even when not connected to installation. Figure 3-2 SVT10KX SVT20KX Figure 3-3: Location of 1Nm. 8 SVT30KX Battery connection should be connected prior to local electrical codes. The red wire for all...
Owners Manual
Page 9
... hazards of wire color should only be able to installation. It is correct. Terminal Block Wiring Diagram (All Models) Warning: Make sure the UPS is correct, not reversed and not short-circuited. 9 The wire current spec, color, position, connection and conductance reliability should be turned on the external battery terminal block and make sure the correct...
... hazards of wire color should only be able to installation. It is correct. Terminal Block Wiring Diagram (All Models) Warning: Make sure the UPS is correct, not reversed and not short-circuited. 9 The wire current spec, color, position, connection and conductance reliability should be turned on the external battery terminal block and make sure the correct...
Owners Manual
Page 10
...SVT20KX / SVT30KX Models) 3.6 External Battery Connection The UPS comes with the local codes/regulations and installed using the following instructions by a qualified service technician only. Breaker specification for SVT20KX / SVT30KX is only for your battery pack Owner's Manual. Note: The parallel system cannot use a common external battery pack. Adding external batteries...'s external A battery connector A where the battery pack connects. Ensure the cables are needed only to an independent battery pack. This UPS supports Tripp Lite external battery model BP240V135*. Small ...
...SVT20KX / SVT30KX Models) 3.6 External Battery Connection The UPS comes with the local codes/regulations and installed using the following instructions by a qualified service technician only. Breaker specification for SVT20KX / SVT30KX is only for your battery pack Owner's Manual. Note: The parallel system cannot use a common external battery pack. Adding external batteries...'s external A battery connector A where the battery pack connects. Ensure the cables are needed only to an independent battery pack. This UPS supports Tripp Lite external battery model BP240V135*. Small ...
Owners Manual
Page 11
... front panel to show the UPS operation status: Mode / LED Bypass Line Initialization Standby mode Bypass mode Online mode Battery mode Freq. Battery Fault 11 Turn off . * Freq. UP Button: Press to section 4.4.9 for more than 0.5 seconds to confirm a selection in Online mode and Freq. Enter Button: Press to test the battery while in the settings menu. 4. Operation 4.1 Button Operation Button ON/Enter Button OFF...
... front panel to show the UPS operation status: Mode / LED Bypass Line Initialization Standby mode Bypass mode Online mode Battery mode Freq. Battery Fault 11 Turn off . * Freq. UP Button: Press to section 4.4.9 for more than 0.5 seconds to confirm a selection in Online mode and Freq. Enter Button: Press to test the battery while in the settings menu. 4. Operation 4.1 Button Operation Button ON/Enter Button OFF...
Owners Manual
Page 14
...problem cannot be fixed, please contact Tripp Lite Tech Support. 3) In case of power loss for connected devices. 2) In Bypass mode, UPS output voltage is in Online mode 1) Turn off the UPS, be blank and the UPS will cut off the output, switch off the UPS by pressing the "OFF" button for more details. 2) Some warning alarms...Battery mode 1) Turn off the line input breaker. Otherwise, there is a fatal error in Fault mode 1) When the Fault LED illuminates and the buzzer sounds continuously, there is a risk of data loss or load failure. 2) In Battery mode, users can press the "Test"...
...problem cannot be fixed, please contact Tripp Lite Tech Support. 3) In case of power loss for connected devices. 2) In Bypass mode, UPS output voltage is in Online mode 1) Turn off the UPS, be blank and the UPS will cut off the output, switch off the UPS by pressing the "OFF" button for more details. 2) Some warning alarms...Battery mode 1) Turn off the line input breaker. Otherwise, there is a fatal error in Fault mode 1) When the Fault LED illuminates and the buzzer sounds continuously, there is a risk of data loss or load failure. 2) In Battery mode, users can press the "Test"...
Owners Manual
Page 15
... Battery mode and add to the parallel system when the whole system is turned on the UPS; The load must be added to the parallel system. 4) If there is greater than 1.5V, contact Tripp Lite Technical Support for parallel installation)...SVT20KX and SVT30KX) 4.5.1 Parallel system initial startup Before initial startup, first ensure all UPS systems enter Bypass mode, measure the output voltage between actual output and setting value is correct. Then remove the unit from the parallel system: Method 1: 1) Press the "OFF" key twice, each UPS to Online mode (refer to Program Codes...
... Battery mode and add to the parallel system when the whole system is turned on the UPS; The load must be added to the parallel system. 4) If there is greater than 1.5V, contact Tripp Lite Technical Support for parallel installation)...SVT20KX and SVT30KX) 4.5.1 Parallel system initial startup Before initial startup, first ensure all UPS systems enter Bypass mode, measure the output voltage between actual output and setting value is correct. Then remove the unit from the parallel system: Method 1: 1) Press the "OFF" key twice, each UPS to Online mode (refer to Program Codes...
Owners Manual
Page 20
...alarm will sound. Notes: • Battery disconnect should be performed by qualified service personnel only. • Before making voltage adjustments, be sure to first disconnect all batteries to get the accurate charger voltage. • Any modifications must mute the alarm and put the UPS back to Normal mode manually...UPS is the default setting. 13: Battery voltage calibration Interface Setting Parameter 2: Select Add or Sub function to adjust battery voltage to Normal mode automatically. CHE is turned on the latest status until the neutral is detected, the alarm will be muted ...
...alarm will sound. Notes: • Battery disconnect should be performed by qualified service personnel only. • Before making voltage adjustments, be sure to first disconnect all batteries to get the accurate charger voltage. • Any modifications must mute the alarm and put the UPS back to Normal mode manually...UPS is the default setting. 13: Battery voltage calibration Interface Setting Parameter 2: Select Add or Sub function to adjust battery voltage to Normal mode automatically. CHE is turned on the latest status until the neutral is detected, the alarm will be muted ...
Owners Manual
Page 24
Converter mode Description LCD screen When the output frequency is beyond the acceptable operating range or a power failure occurs, the UPS will beep every 4 seconds. In this mode, the UPS will have no bypass output, but will output constant frequency (50Hz or 60Hz). Operation Operating mode/status Freq. Battery mode Description When the input voltage/frequency is set to "CF", the inverter will still charge the battery. The alarm will use backup power from the battery. LCD screen 24 4.
Converter mode Description LCD screen When the output frequency is beyond the acceptable operating range or a power failure occurs, the UPS will beep every 4 seconds. In this mode, the UPS will have no bypass output, but will output constant frequency (50Hz or 60Hz). Operation Operating mode/status Freq. Battery mode Description When the input voltage/frequency is set to "CF", the inverter will still charge the battery. The alarm will use backup power from the battery. LCD screen 24 4.
Owners Manual
Page 27
... switch is included as standard for further details. Use Tripp Lite's free PowerAlert® power management software (available for normal UPS operation. Keep pins 1 and 2 closed for download at a time. 5.3 EPO Connector The EPO is open...Install an optional WEBCARDLX in the UPS but it continues to remotely monitor and control the UPS via a network. To enable EPO function, open 3C Utility power imbalanced 3D Bypass unstable 5. Operation 4.11 Warning Code If errors occur in this slot to the WEBCARDLX and RELAYCARDSV manuals for site safety. Up to 3 error codes...
... switch is included as standard for further details. Use Tripp Lite's free PowerAlert® power management software (available for normal UPS operation. Keep pins 1 and 2 closed for download at a time. 5.3 EPO Connector The EPO is open...Install an optional WEBCARDLX in the UPS but it continues to remotely monitor and control the UPS via a network. To enable EPO function, open 3C Utility power imbalanced 3D Bypass unstable 5. Operation 4.11 Warning Code If errors occur in this slot to the WEBCARDLX and RELAYCARDSV manuals for site safety. Up to 3 error codes...
Owners Manual
Page 28
... the problem still persists, contact Tripp Lite Tech Support. Batteries are connected properly. The input neutral wire is shorter than nominal value. Symptom Possible cause Remedy No indication and alarm in the front display panel, even though the mains is locked in a fault. After repeated overloads, the UPS is normal. Warning code 02 is not connected properly. Replace...
... the problem still persists, contact Tripp Lite Tech Support. Batteries are connected properly. The input neutral wire is shorter than nominal value. Symptom Possible cause Remedy No indication and alarm in the front display panel, even though the mains is locked in a fault. After repeated overloads, the UPS is normal. Warning code 02 is not connected properly. Replace...
Owners Manual
Page 29
... to recharge. Note: Contact Tripp Lite Technical Support for an extended period of time, the batteries must be recharged once every three months and the charging time must be stored for more maintenance information. 7. If the charging source remains off for an extended period of service and/or maintenance, disconnect the batteries and verify that no...
... to recharge. Note: Contact Tripp Lite Technical Support for an extended period of time, the batteries must be recharged once every three months and the charging time must be stored for more maintenance information. 7. If the charging source remains off for an extended period of service and/or maintenance, disconnect the batteries and verify that no...
Owners Manual
Page 30
Specifications MODEL CAPACITY TOPOLOGY INPUT Voltage Range Frequency Range Phase Power Factor Input THD Input Voltage Tolerance (on Bypass EFFICIENCY AC mode BATTERY Type Numbers Nominal Voltage Charging Current Charging Voltage Matching Battery Cabinet PHYSICAL Outline Dimensions, D X W X H (mm) Net Weight (kg) Color Parallelling Capability SVT10KX SVT20KX SVT30KX 10000VA / 9000W 20000VA / 18000W 30000VA / 27000W Voltage and Frequency Independent (VFI) Double...
Specifications MODEL CAPACITY TOPOLOGY INPUT Voltage Range Frequency Range Phase Power Factor Input THD Input Voltage Tolerance (on Bypass EFFICIENCY AC mode BATTERY Type Numbers Nominal Voltage Charging Current Charging Voltage Matching Battery Cabinet PHYSICAL Outline Dimensions, D X W X H (mm) Net Weight (kg) Color Parallelling Capability SVT10KX SVT20KX SVT30KX 10000VA / 9000W 20000VA / 18000W 30000VA / 27000W Voltage and Frequency Independent (VFI) Double...
Owners Manual
Page 32
... which vary from the date of the Tripp Lite product. Specifications are available. 9. If the product was not startedup by the limited warranty described below. Warranty Your SmartOnline 3-Phase UPS System is covered by authorized Tripp Lite service, replacement parts will assign to the series number. Tripp Lite will be confused with all applicable instructions as to be obtained by the...
... which vary from the date of the Tripp Lite product. Specifications are available. 9. If the product was not startedup by the limited warranty described below. Warranty Your SmartOnline 3-Phase UPS System is covered by authorized Tripp Lite service, replacement parts will assign to the series number. Tripp Lite will be confused with all applicable instructions as to be obtained by the...