LM21XPBB Manual
Page 2
...device, you must read and fully understand this Signal Word on rolling doors, single-slide and center-parting level and inclined track doors. ADVERTENCIA The release device is provided with a battery management system that ...PARTS 14 APPENDIX 15 WARNING Mechanical CAUTION WWEAlAecRRtriNcNaIlINNGG CAWUATRIONNING When you see this manual and AAVTETRETNITSISOENMENT follow all releasing device PRECAUCIÓN systems, maximum fire protection is provided when installed in conjunction with a fusible link system. Read them . INTRODUCTION GENERAL DESCRIPTION The LiftMaster® LM21XPBB...
...device, you must read and fully understand this Signal Word on rolling doors, single-slide and center-parting level and inclined track doors. ADVERTENCIA The release device is provided with a battery management system that ...PARTS 14 APPENDIX 15 WARNING Mechanical CAUTION WWEAlAecRRtriNcNaIlINNGG CAWUATRIONNING When you see this manual and AAVTETRETNITSISOENMENT follow all releasing device PRECAUCIÓN systems, maximum fire protection is provided when installed in conjunction with a fusible link system. Read them . INTRODUCTION GENERAL DESCRIPTION The LiftMaster® LM21XPBB...
LM21XPBB Manual
Page 5
... L2 (neutral) of the fusible link assembly and the resulting door closure. and Class 2 circuits, shall be performed in accordance with the Canadian Electrical Code, Part I, with local electrical codes. • 120Vac should ONLY be dry contact type. WARNING ON WIRING INSTRUCTIONS Verify wiring configuration with , • DO NOT disconnect battery...
... L2 (neutral) of the fusible link assembly and the resulting door closure. and Class 2 circuits, shall be performed in accordance with the Canadian Electrical Code, Part I, with local electrical codes. • 120Vac should ONLY be dry contact type. WARNING ON WIRING INSTRUCTIONS Verify wiring configuration with , • DO NOT disconnect battery...
LM21XPBB Manual
Page 6
WIRE ROUTING WIRING Low Voltage Wiring High Voltage Wiring Mechanical Reset Plunger Power Strip Ground L1 L2 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Annunciator Wiring with Sleeve Voice Board Wiring PARTS KIT LMEOLRES-10 Wire Jumper 10k Ohm Resistor Refer to wiring section for proper application of these parts. 6
WIRE ROUTING WIRING Low Voltage Wiring High Voltage Wiring Mechanical Reset Plunger Power Strip Ground L1 L2 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Annunciator Wiring with Sleeve Voice Board Wiring PARTS KIT LMEOLRES-10 Wire Jumper 10k Ohm Resistor Refer to wiring section for proper application of these parts. 6
LM21XPBB Manual
Page 9
... Relay Outputs (#11 N/C or #13 N/O and #12 Common) to the appropriate inputs on the Fire Alarm Control Panel to N/O Position on Proximity Switch Proximity Switch Part No. Fire Alarm Control Panel + AVERTISSEMENT ATTENTION OPTIONAL CONNECTIONS CLOSE DOOR DETECTION OPTION Connect wiring from the FIGURE 10 Trouble Relay Outputs (#14 N/C or #16...
... Relay Outputs (#11 N/C or #13 N/O and #12 Common) to the appropriate inputs on the Fire Alarm Control Panel to N/O Position on Proximity Switch Proximity Switch Part No. Fire Alarm Control Panel + AVERTISSEMENT ATTENTION OPTIONAL CONNECTIONS CLOSE DOOR DETECTION OPTION Connect wiring from the FIGURE 10 Trouble Relay Outputs (#14 N/C or #16...
LM21XPBB Manual
Page 12
... dry contact input. Red (+) and Black (-)? Is the battery discharged? If so, allow 10 minutes for the battery management system to the "Replacement Parts and Accessories" section of this manual for correct wiring instructions (Figures 3-5). Refer to recharge the battery. Also, if N/O smoke detectors are in alarm... connected or do the leads have a defective connector? 2. Does the unit go into alarm and release the fusible link as soon as part of the enclosure lit? Refer to the Annunciator section of this manual for correct wiring instructions (Figures 6 and 7). If not lit, ...
... dry contact input. Red (+) and Black (-)? Is the battery discharged? If so, allow 10 minutes for the battery management system to the "Replacement Parts and Accessories" section of this manual for correct wiring instructions (Figures 3-5). Refer to recharge the battery. Also, if N/O smoke detectors are in alarm... connected or do the leads have a defective connector? 2. Does the unit go into alarm and release the fusible link as soon as part of the enclosure lit? Refer to the Annunciator section of this manual for correct wiring instructions (Figures 6 and 7). If not lit, ...
LM21XPBB Manual
Page 13
...fuse, a 3 Amp, 3AG, slo-blo fuse, is applied, check switched "on the release device. For replacement parts refer to Accessory and Replacement Parts page. For replacement parts refer to Accessory and Replacement PAartsVpaEgeR. level. Power Red If the Red LED is lit, then the line power ...LED Color Description Action Required Battery Green If the Green LED is lit, then the battery is required for use in a separate parts bag. closed position. This indicates the need to normally open (N.O.). This configuration check that power is connected as hazardous waste and ...
...fuse, a 3 Amp, 3AG, slo-blo fuse, is applied, check switched "on the release device. For replacement parts refer to Accessory and Replacement Parts page. For replacement parts refer to Accessory and Replacement PAartsVpaEgeR. level. Power Red If the Red LED is lit, then the line power ...LED Color Description Action Required Battery Green If the Green LED is lit, then the battery is required for use in a separate parts bag. closed position. This indicates the need to normally open (N.O.). This configuration check that power is connected as hazardous waste and ...
LM21XPBB Manual
Page 14
... - 24Vdc Ion Smoke Detector - 12Vdc Ion Heat Detector - 135 Degree Fixed Temperature Heat Detector - 194 Degree Fixed Temperature ITEM PART # 12 LMEH1224ADA 13 LMPSTR2475ADA 14 LML2475ADA 15 LMHS2475ADA 16 LMEH1224ADA 17 LMPSTR1V75ADA 18 LML1V750ADA 19 LMHS1V75ADA 20 LMEH120ADA 21 LM8SP 22 LMEOLR1224...- 120Vac Strobe - 120Vac Horn/Strobe - 120Vac Horn - 120Vac Speaker 8" End-of-Line Relay - 12/24Vdc End-of-Line Relay - 120Vac REPLACEMENT PARTS ITEM PART # 1 LMRK 2 LMELH 3 LM2AG3AMP 4 LMEOLRES10 5 LM4AH12 DESCRIPTION Reset Knob End Link Fuse - 3Amp End-of-Line Resistor, 10 kOhm Battery NOTE:...
... - 24Vdc Ion Smoke Detector - 12Vdc Ion Heat Detector - 135 Degree Fixed Temperature Heat Detector - 194 Degree Fixed Temperature ITEM PART # 12 LMEH1224ADA 13 LMPSTR2475ADA 14 LML2475ADA 15 LMHS2475ADA 16 LMEH1224ADA 17 LMPSTR1V75ADA 18 LML1V750ADA 19 LMHS1V75ADA 20 LMEH120ADA 21 LM8SP 22 LMEOLR1224...- 120Vac Strobe - 120Vac Horn/Strobe - 120Vac Horn - 120Vac Speaker 8" End-of-Line Relay - 12/24Vdc End-of-Line Relay - 120Vac REPLACEMENT PARTS ITEM PART # 1 LMRK 2 LMELH 3 LM2AG3AMP 4 LMEOLRES10 5 LM4AH12 DESCRIPTION Reset Knob End Link Fuse - 3Amp End-of-Line Resistor, 10 kOhm Battery NOTE:...