CR5000 Measurement and Control Module
Page 2
... otherwise. Warranty and Assistance The CR5000 MEASUREMENT AND CONTROL SYSTEM is : CAMPBELL SCIENTIFIC, INC. Please visit www.campbellsci.com to determine which have no warranty. CAMPBELL SCIENTIFIC's shipping address is warranted by CAMPBELL SCIENTIFIC, INC. will be returned without... implied, including warranties of the shipping container. products which Campbell Scientific company serves your country. The following contact information is limited to any CAMPBELL SCIENTIFIC, INC. CAMPBELL SCIENTIFIC, INC.'s obligation under normal use and service for customers ...
... otherwise. Warranty and Assistance The CR5000 MEASUREMENT AND CONTROL SYSTEM is : CAMPBELL SCIENTIFIC, INC. Please visit www.campbellsci.com to determine which have no warranty. CAMPBELL SCIENTIFIC's shipping address is warranted by CAMPBELL SCIENTIFIC, INC. will be returned without... implied, including warranties of the shipping container. products which Campbell Scientific company serves your country. The following contact information is limited to any CAMPBELL SCIENTIFIC, INC. CAMPBELL SCIENTIFIC, INC.'s obligation under normal use and service for customers ...
CR5000 Measurement and Control Module
Page 15
Press any key for Main Menu (except < >) Data Run/Stop Program File Status Configure, Settings CR5000 Overview Adjust contrast with < > < lighter darker > Real Time Tables Real Time Custom Final Storage Data Reset Data Tables Graph Setup New Edit Copy Delete Run ... : StartTime : Run Signature DLD Signature Battery : Set Time/Date Settings Display xxxx xxxx xxxx xxxx xxxxx xxxxx xxxx OV-11 Keyboard Display Power Up Screen CAMPBELL SCIENTIFIC CR5000 Datalogger 06/18/2000, 18:24:35 CPU: TRIG.CR5 Running. OV4.
Press any key for Main Menu (except < >) Data Run/Stop Program File Status Configure, Settings CR5000 Overview Adjust contrast with < > < lighter darker > Real Time Tables Real Time Custom Final Storage Data Reset Data Tables Graph Setup New Edit Copy Delete Run ... : StartTime : Run Signature DLD Signature Battery : Set Time/Date Settings Display xxxx xxxx xxxx xxxx xxxxx xxxxx xxxx OV-11 Keyboard Display Power Up Screen CAMPBELL SCIENTIFIC CR5000 Datalogger 06/18/2000, 18:24:35 CPU: TRIG.CR5 Running. OV4.
CR5000 Measurement and Control Module
Page 24
... Int. 250 µs Int. 20/16.7 ms Int. WEIGHT: 4.5 lbs (2.0 kg) with low-profile base; 12.2 lbs (5.5 kg) with Campbell Scientific before purchase. OV-20 Resolution of service typical, less at high frequencies because of Reading + Offset) -40° to above 3.5 V at a ... Specifications Electrical specifications are available upon transition from 1,200 to 0.8 V INPUT RESISTANCE: 100 kΩ EMI and ESD PROTECTION The CR5000 is determined by -21 character alphanumeric or 128 x 64 pixel graphic LCD display w/backlight. Non-condensing environment required. noise is ...
... Int. 250 µs Int. 20/16.7 ms Int. WEIGHT: 4.5 lbs (2.0 kg) with low-profile base; 12.2 lbs (5.5 kg) with Campbell Scientific before purchase. OV-20 Resolution of service typical, less at high frequencies because of Reading + Offset) -40° to above 3.5 V at a ... Specifications Electrical specifications are available upon transition from 1,200 to 0.8 V INPUT RESISTANCE: 100 kΩ EMI and ESD PROTECTION The CR5000 is determined by -21 character alphanumeric or 128 x 64 pixel graphic LCD display w/backlight. Non-condensing environment required. noise is ...
CR5000 Measurement and Control Module
Page 25
... 18"x16"x8¾", outside dimensions are 18"x13.5"x8.13" (with the two supplied screws for housing a CR5000 and peripherals. Campbell Scientific offers two enclosures for more peripherals. Both enclosures are 18½"x18¾"x10½" (with a 5 kHz sample rate. 1-1 ...The CR5000 is located at 120°C for routing cables and wires. System operating time for reflecting solar radiation, thus ...
... 18"x16"x8¾", outside dimensions are 18"x13.5"x8.13" (with the two supplied screws for housing a CR5000 and peripherals. Campbell Scientific offers two enclosures for more peripherals. Both enclosures are 18½"x18¾"x10½" (with a 5 kHz sample rate. 1-1 ...The CR5000 is located at 120°C for routing cables and wires. System operating time for reflecting solar radiation, thus ...
CR5000 Measurement and Control Module
Page 27
... is on account of the lead acid battery. Campbell Scientific recommends: 1. Installation and Maintenance LEAD ACID BATTERY REPLACEMENT + 6V 7AH LEAD ACID BATTERY + 6V 7AH LEAD ACID BATTERY RED BLACK WHITE -- Lead Acid Battery Wiring Monitor the power supply using datalogger Instruction " Battery" . CR5000 Rechargeable Battery and AC Transformer Specifications Lead Acid Battery...
... is on account of the lead acid battery. Campbell Scientific recommends: 1. Installation and Maintenance LEAD ACID BATTERY REPLACEMENT + 6V 7AH LEAD ACID BATTERY + 6V 7AH LEAD ACID BATTERY RED BLACK WHITE -- Lead Acid Battery Wiring Monitor the power supply using datalogger Instruction " Battery" . CR5000 Rechargeable Battery and AC Transformer Specifications Lead Acid Battery...
CR5000 Measurement and Control Module
Page 28
...to the green G and 12 V power input connector, without loading or charging the internal batteries. When connecting external power to the CR5000's charger input (Figure 1.6-1). Diode protection exists so that on lead acid batteries. Specific site information, if available, could strongly influence...size based on the front panel. Insert the ground lead in determining your system power requirements contact Campbell Scientific's Marketing Department. 1.5 Direct Battery Connection to the CR5000 Wiring Panel Any clean, battery backed 11 to 16 VDC supply may be considered. When power is...
...to the green G and 12 V power input connector, without loading or charging the internal batteries. When connecting external power to the CR5000's charger input (Figure 1.6-1). Diode protection exists so that on lead acid batteries. Specific site information, if available, could strongly influence...size based on the front panel. Insert the ground lead in determining your system power requirements contact Campbell Scientific's Marketing Department. 1.5 Direct Battery Connection to the CR5000 Wiring Panel Any clean, battery backed 11 to 16 VDC supply may be considered. When power is...
CR5000 Measurement and Control Module
Page 32
...the CR5000 ground should be earth (chassis) grounded. To be safe, the ground of a 6 to 8 foot copper sheathed grounding rod driven into the earth and connected to verify that the power grounds are at a minimum, a proper earth ground will exceed the common mode range. Campbell Scientific ...that a safety ground exists when in doubt, also ground the system through the buildings, plumbing or another connection to one ground for the CR5000 is not always obvious. Section 1. In older buildings, new cover plates on lightning protection can be connected, creating one common earth (...
...the CR5000 ground should be earth (chassis) grounded. To be safe, the ground of a 6 to 8 foot copper sheathed grounding rod driven into the earth and connected to verify that the power grounds are at a minimum, a proper earth ground will exceed the common mode range. Campbell Scientific ...that a safety ground exists when in doubt, also ground the system through the buildings, plumbing or another connection to one ground for the CR5000 is not always obvious. Section 1. In older buildings, new cover plates on lightning protection can be connected, creating one common earth (...
CR5000 Measurement and Control Module
Page 34
...-12 port. Applications requiring more control channels or greater power sourcing capacity can usually be controlled with the use of Campbell Scientific's A21REL-12 Four Channel Relay Driver, A6REL-12 Six Channel Relay Driver, SDM-CD16AC 16 Channel AC/DC Relay Module... < 1.17 A @ 60°C < 0.85 A @ 80°C 5V + CSI/O < 200 mA Make certain that approach the limits of the CR5000. Typical Current Drain for Some CR5000 Peripherals Peripheral AM25T COM100 COM200 Phone Modem SDM-INT8 Typical Current Drain (mA) Quiescent .5 .5 0.0012 0.4 Active 1 1.8 140 6.5 1.9 Controlling Power to ...
...-12 port. Applications requiring more control channels or greater power sourcing capacity can usually be controlled with the use of Campbell Scientific's A21REL-12 Four Channel Relay Driver, A6REL-12 Six Channel Relay Driver, SDM-CD16AC 16 Channel AC/DC Relay Module... < 1.17 A @ 60°C < 0.85 A @ 80°C 5V + CSI/O < 200 mA Make certain that approach the limits of the CR5000. Typical Current Drain for Some CR5000 Peripherals Peripheral AM25T COM100 COM200 Phone Modem SDM-INT8 Typical Current Drain (mA) Quiescent .5 .5 0.0012 0.4 Active 1 1.8 140 6.5 1.9 Controlling Power to ...
CR5000 Measurement and Control Module
Page 42
... the link. Cards can be necessary to use IEEE4 output or an offset to store data: IEEE4 four byte floating point and Campbell Scientific two byte floating point (FP2). Within the CR5000, time is used to maintain the desired resolution of FP2 is 8 or greater (Table 2.2-2). While IEEE 4 byte floating point is stored...
... the link. Cards can be necessary to use IEEE4 output or an offset to store data: IEEE4 four byte floating point and Campbell Scientific two byte floating point (FP2). Within the CR5000, time is used to maintain the desired resolution of FP2 is 8 or greater (Table 2.2-2). While IEEE 4 byte floating point is stored...
CR5000 Measurement and Control Module
Page 74
...). If current was used to flow, the resulting oxidation or reduction would soon damage the electrode, just as the electrolyte. Campbell Scientific probes are not read until the scan is primary interest, PulseCount should have the PulseCount instruction programmed to block this DC current.../soil solution acting as if DC excitation was allowed to make the measurement. Section 3. Frequency dependent measurements should be output. The CR5000 actually measures the elapsed time since the last time the counters were read on the scan interval: frequency resolution = 1/scan interval ...
...). If current was used to flow, the resulting oxidation or reduction would soon damage the electrode, just as the electrolyte. Campbell Scientific probes are not read until the scan is primary interest, PulseCount should have the PulseCount instruction programmed to block this DC current.../soil solution acting as if DC excitation was allowed to make the measurement. Section 3. Frequency dependent measurements should be output. The CR5000 actually measures the elapsed time since the last time the counters were read on the scan interval: frequency resolution = 1/scan interval ...
CR5000 Measurement and Control Module
Page 77
...20 temperature (or other) measurements. Native Language Programming The CR5000 is : PanelTemp (Dest, Integ) 4-1 Rather than have 20 different names, a variable array with one might be used. The instructions Campbell Scientific has created for creating tables of parameters that has some .... There are assigned variables (given names). TCTemp(20). A thermocouple temperature might write: TempF = TempC * 1.8 + 32 With the CR5000 there may be called TCTemp. The results of procedures. Section 4. For example, to convert ten temperatures in a variable array from C ...
...20 temperature (or other) measurements. Native Language Programming The CR5000 is : PanelTemp (Dest, Integ) 4-1 Rather than have 20 different names, a variable array with one might be used. The instructions Campbell Scientific has created for creating tables of parameters that has some .... There are assigned variables (given names). TCTemp(20). A thermocouple temperature might write: TempF = TempC * 1.8 + 32 With the CR5000 there may be called TCTemp. The results of procedures. Section 4. For example, to convert ten temperatures in a variable array from C ...
CR5000 Measurement and Control Module
Page 168
... check the manual on the device for operation details. 7-42 The SDMTrigger instruction allows the CR5000 to synchronize when the measurements are used to control and transmit/retrieve data from a Campbell Scientific SIO4 Interface (4 Channel Serial Input/Output device). Initial Setting (default): 30.0 µS ... of one and an offset of 32 will return the last nnnn events. SDMTrigger When SDMTrigger is used to connect the CR5000 and SDM devices. Measurement Instructions Parameter & Data Type CaptureTrig Constant, Variable, or Expression Mult, Offset Constant, Variable, Array...
... check the manual on the device for operation details. 7-42 The SDMTrigger instruction allows the CR5000 to synchronize when the measurements are used to control and transmit/retrieve data from a Campbell Scientific SIO4 Interface (4 Channel Serial Input/Output device). Initial Setting (default): 30.0 µS ... of one and an offset of 32 will return the last nnnn events. SDMTrigger When SDMTrigger is used to connect the CR5000 and SDM devices. Measurement Instructions Parameter & Data Type CaptureTrig Constant, Variable, or Expression Mult, Offset Constant, Variable, Array...
CR5000 Specifications
Page 1
... for DF w/input reversal = Basic Res + 1.0 µV Offset for DF w/o input reversal = 2Basic Res + 2.0 µV Offset for DF with Campbell Scientific before purchase. PHYSICAL SPECIFICATIONS SIZE: 9.8" x 8.3" x 4.5" (24.7 cm x 21.0 cm x 11.4 cm) Terminal strips extend 0.4" (1.0 cm). Noise...@ 50°C INPUT RESISTANCE: 20 Gohms typical ACCURACY OF BUILT-IN REFERENCE JUNCTION THERMISTOR (for Campbell Scientific peripherals. PROGRAM EXECUTION RATE The CR5000 can be centered around datalogger ground. Expanded data storage with rechargeable base WARRANTY 3 years against defects ...
... for DF w/input reversal = Basic Res + 1.0 µV Offset for DF w/o input reversal = 2Basic Res + 2.0 µV Offset for DF with Campbell Scientific before purchase. PHYSICAL SPECIFICATIONS SIZE: 9.8" x 8.3" x 4.5" (24.7 cm x 21.0 cm x 11.4 cm) Terminal strips extend 0.4" (1.0 cm). Noise...@ 50°C INPUT RESISTANCE: 20 Gohms typical ACCURACY OF BUILT-IN REFERENCE JUNCTION THERMISTOR (for Campbell Scientific peripherals. PROGRAM EXECUTION RATE The CR5000 can be centered around datalogger ground. Expanded data storage with rechargeable base WARRANTY 3 years against defects ...