Operation Manual
Page 1
Aqua Solar Electronic Solar Control Center Operation and Installation Manual AQ-SOL-LV AQ-SOL-LV-TC AQ-SOL-LV-SP www.haywardnet.com
Aqua Solar Electronic Solar Control Center Operation and Installation Manual AQ-SOL-LV AQ-SOL-LV-TC AQ-SOL-LV-SP www.haywardnet.com
Operation Manual
Page 2
... at all AC power during installation. • Warning - To reduce the risk of the pool, spa or hot tub shall be bonded to the equipment grounding bus with a continuous copper wire equivalent in size to the grounding means provided in the electrical supply service panel with copper conductors not smaller than 8 AWG US/ 6 AWG Canada. IMPORTANT SAFETY INSTRUCTIONS When using this electrical equipment, basic...
... at all AC power during installation. • Warning - To reduce the risk of the pool, spa or hot tub shall be bonded to the equipment grounding bus with a continuous copper wire equivalent in size to the grounding means provided in the electrical supply service panel with copper conductors not smaller than 8 AWG US/ 6 AWG Canada. IMPORTANT SAFETY INSTRUCTIONS When using this electrical equipment, basic...
Operation Manual
Page 3
Table of Contents SPECIFICATIONS Specifications 1 OPERATION Controls 2 Temperature Display 3 INSTALLATION Mounting 4 Wiring 4 Jumper Settings 9 TROUBLESHOOTING Troubleshooting 10 WARRANTY Warranty 12
Table of Contents SPECIFICATIONS Specifications 1 OPERATION Controls 2 Temperature Display 3 INSTALLATION Mounting 4 Wiring 4 Jumper Settings 9 TROUBLESHOOTING Troubleshooting 10 WARRANTY Warranty 12
Operation Manual
Page 4
...) override of the optional high voltage relays can be wired in series with an adjustable calibrated water temperature high limit. Automatic nocturnal cooling (for solar, water, and ambient temperature information as well as heating, cooling, and sensor fault. The AQ-SOL-LV-TC additionally provides a filter pump time clock, programmable in 15-minute intervals with AQSOL-LV-TC, maximum of pools, spas, and hot tubs. freeze: On when AUX sensor less than or equal to...
...) override of the optional high voltage relays can be wired in series with an adjustable calibrated water temperature high limit. Automatic nocturnal cooling (for solar, water, and ambient temperature information as well as heating, cooling, and sensor fault. The AQ-SOL-LV-TC additionally provides a filter pump time clock, programmable in 15-minute intervals with AQSOL-LV-TC, maximum of pools, spas, and hot tubs. freeze: On when AUX sensor less than or equal to...
Operation Manual
Page 5
Set the time clock for the filter pump. Controls and Displays MAIN SWITCH ON: The Aqua Solar directs water through the solar collectors regardless of operation for the correct time, the desired hours of Pool and Spa Professionals (APSP) standards, the pump should run long enough each day. For model AQ-SOL-LV-TC, this position, the Aqua Solar will operate automatically based on the solar and pool temperatures. AUTO: For normal operation. The digital display will show the exact temperature while rotating...
Set the time clock for the filter pump. Controls and Displays MAIN SWITCH ON: The Aqua Solar directs water through the solar collectors regardless of operation for the correct time, the desired hours of Pool and Spa Professionals (APSP) standards, the pump should run long enough each day. For model AQ-SOL-LV-TC, this position, the Aqua Solar will operate automatically based on the solar and pool temperatures. AUTO: For normal operation. The digital display will show the exact temperature while rotating...
Operation Manual
Page 6
... the Aqua Solar may keep the filter pump running even though the time clock is not functioning properly, the error message "Err" will loop back to purge from the system. If a temperature sensor is not wired to cycle through the various displays. Solar Sensor: A problem is in the ON position. "1" (up) - timer controls pump "0" (down) - If both Heating and Cooling are on , the switch is detected with the pool sensor (open or short circuit).
... the Aqua Solar may keep the filter pump running even though the time clock is not functioning properly, the error message "Err" will loop back to purge from the system. If a temperature sensor is not wired to cycle through the various displays. Solar Sensor: A problem is in the ON position. "1" (up) - timer controls pump "0" (down) - If both Heating and Cooling are on , the switch is detected with the pool sensor (open or short circuit).
Operation Manual
Page 7
... model) Filter Pump Rev Fwd } Valve Output Solar Pool Aux Input Power 120VAC 240 VAC Ground Cooling Recirculate/ Freeze Protection Celsius/ Fahrenheit Solar Override Temperature Sensor Inputs Output wiring to the relay first and then jumper over the Aqua Solar terminal block. If the valve operates opposite to , disconnect and plug into one of connectors). Follow NEC and all local electrical codes. INSTALLATION Mounting The Aqua Solar is designed for outdoor use a solar valve, which diverts water...
... model) Filter Pump Rev Fwd } Valve Output Solar Pool Aux Input Power 120VAC 240 VAC Ground Cooling Recirculate/ Freeze Protection Celsius/ Fahrenheit Solar Override Temperature Sensor Inputs Output wiring to the relay first and then jumper over the Aqua Solar terminal block. If the valve operates opposite to , disconnect and plug into one of connectors). Follow NEC and all local electrical codes. INSTALLATION Mounting The Aqua Solar is designed for outdoor use a solar valve, which diverts water...
Operation Manual
Page 8
... filter pump timer. Pool Sensor: The pool sensor should be substituted. Insert the PC sensor until the O-ring makes an adequate seal. Order additional relays separately (Hayward p/n AQ-RELAY). AQ-SOL-LV: For most systems, simply connect the Aqua Solar power to attach the solar sensor near other electrical wiring use shielded cable (Belden 8428 for both legs of this function on page 9). See wiring diagram on the hole. For long runs or runs near the solar collector array. High Voltage...
... filter pump timer. Pool Sensor: The pool sensor should be substituted. Insert the PC sensor until the O-ring makes an adequate seal. Order additional relays separately (Hayward p/n AQ-RELAY). AQ-SOL-LV: For most systems, simply connect the Aqua Solar power to attach the solar sensor near other electrical wiring use shielded cable (Belden 8428 for both legs of this function on page 9). See wiring diagram on the hole. For long runs or runs near the solar collector array. High Voltage...
Operation Manual
Page 9
... Pump 120/240 VAC Contactor (240 VAC Coil) Aqua Solar (AQ-SOL-LV) Pool Sweep Timer Booster Pump Pool Sweep Filter Pump 240 VAC Ground 240 VAC Filter Pump Timer Pool Filter Pump Be careful not to cross phases on filter pump wiring AQ-SOL-LV with Solar Override & Boost Pump Boost relay power connected to LOAD side of Filter Pump Timer to ensure that boost pump only runs when filter pump is runnning Boost Pump Aqua Solar (AQ-SOL-LV) Booster Pump Pool Sweep Filter Pump 240 VAC Ground 240 VAC Filter Pump Timer Be careful not to cross phases on filter pump wiring Pool Filter Pump...
... Pump 120/240 VAC Contactor (240 VAC Coil) Aqua Solar (AQ-SOL-LV) Pool Sweep Timer Booster Pump Pool Sweep Filter Pump 240 VAC Ground 240 VAC Filter Pump Timer Pool Filter Pump Be careful not to cross phases on filter pump wiring AQ-SOL-LV with Solar Override & Boost Pump Boost relay power connected to LOAD side of Filter Pump Timer to ensure that boost pump only runs when filter pump is runnning Boost Pump Aqua Solar (AQ-SOL-LV) Booster Pump Pool Sweep Filter Pump 240 VAC Ground 240 VAC Filter Pump Timer Be careful not to cross phases on filter pump wiring Pool Filter Pump...
Operation Manual
Page 10
...-SOL-LV-TC with filter pump & pool sweep relays 120/240 VAC Pool Sweep Timer 240 VAC Aqua Solar (AQ-SOL-LV-TC) Booster Pump Pool Sweep Filter Pump 240 VAC Ground Sweep Pump Filter Pump NOTES: 1) Do not use Aqua Solar terminal block as a junction for pump wiring. 2) Most codes require that each pump be on a separate circuit. 3) Aqua Solar will ensure sweep pump runs only when filter pump is running. 4) Sweep pump will turn off for pump wiring. 2) Most codes require that each pump be on . 7 AQ-SOL-LV-TC with filter pump & booster pump relays Aqua Solar 240 (AQ-SOL-LV-TC) VAC...
...-SOL-LV-TC with filter pump & pool sweep relays 120/240 VAC Pool Sweep Timer 240 VAC Aqua Solar (AQ-SOL-LV-TC) Booster Pump Pool Sweep Filter Pump 240 VAC Ground Sweep Pump Filter Pump NOTES: 1) Do not use Aqua Solar terminal block as a junction for pump wiring. 2) Most codes require that each pump be on a separate circuit. 3) Aqua Solar will ensure sweep pump runs only when filter pump is running. 4) Sweep pump will turn off for pump wiring. 2) Most codes require that each pump be on . 7 AQ-SOL-LV-TC with filter pump & booster pump relays Aqua Solar 240 (AQ-SOL-LV-TC) VAC...
Operation Manual
Page 11
... Aqua Solar will operate the filter pump according to "Pool Sweep" 240 VAC Aqua Solar (AQ-SOL-LV-SP) Booster Pump Pool Sweep Filter Pump 240 VAC Ground NOTES: 1) Do not use Aqua Solar terminal block as a junction for solar heating. For model, AQ-SOL-LV-TC the relay will also turn the filter pump on when there is turned off whenever the filter pump is a call for pump wiring. 2) Most codes require that the filter pump is no other timer. AQ-SOL-LV-TC: This relay is the primary control for typical wiring. AQ-SOL-LV-SP HEATER...
... Aqua Solar will operate the filter pump according to "Pool Sweep" 240 VAC Aqua Solar (AQ-SOL-LV-SP) Booster Pump Pool Sweep Filter Pump 240 VAC Ground NOTES: 1) Do not use Aqua Solar terminal block as a junction for solar heating. For model, AQ-SOL-LV-TC the relay will also turn the filter pump on when there is turned off whenever the filter pump is a call for pump wiring. 2) Most codes require that the filter pump is no other timer. AQ-SOL-LV-TC: This relay is the primary control for typical wiring. AQ-SOL-LV-SP HEATER...
Operation Manual
Page 12
... AQ-SOL-LV or internal timeclock for solar heating or cooling. SOLAR OVERRIDE: A high voltage relay connected to the "FILTER PUMP" output is NOT selected, then you use a non-positive seal valve or drill a hole in climates where freezing temperatures are located on and off cloudy days this function. COOLING: A high voltage relay for typical relay wiring. While this function. When recirculate freeze protection is unprotected in series with susceptible plumbing...
... AQ-SOL-LV or internal timeclock for solar heating or cooling. SOLAR OVERRIDE: A high voltage relay connected to the "FILTER PUMP" output is NOT selected, then you use a non-positive seal valve or drill a hole in climates where freezing temperatures are located on and off cloudy days this function. COOLING: A high voltage relay for typical relay wiring. While this function. When recirculate freeze protection is unprotected in series with susceptible plumbing...
Operation Manual
Page 13
... any freeze snap switches wired in series with the "AUX" sensor are closed. The Aqua Solar will operate the solar valve and the booster pump (if installed) regardless of the main circuit board. "Pool Sensor" LED on or flashing "Err" on the right upper side of the sensor temperatures. "Power" LED off if the pool temperature is less than the pool temperature. Lastly, check the internal fuse which is open . Check the sensor temperatures: The "Heating" LED should turn the filter pump on the back...
... any freeze snap switches wired in series with the "AUX" sensor are closed. The Aqua Solar will operate the solar valve and the booster pump (if installed) regardless of the main circuit board. "Pool Sensor" LED on or flashing "Err" on the right upper side of the sensor temperatures. "Power" LED off if the pool temperature is less than the pool temperature. Lastly, check the internal fuse which is open . Check the sensor temperatures: The "Heating" LED should turn the filter pump on the back...
Operation Manual
Page 14
...". "Aux Sensor" LED flashing "Err" on the back cover to check the "POOL" sensor with a voltmeter (you don't need to disconnect the sensor). Replace the sensor or fix the wiring as required. If the sensor and wiring are both good, then the main circuit PCB may have a problem. 11 When the Aux sensor is less than 60ºF. Use the chart on the Aux temperature display: Flashing indicates a probable short circuit in the "SOLAR" sensor or wiring. Use the...
...". "Aux Sensor" LED flashing "Err" on the back cover to check the "POOL" sensor with a voltmeter (you don't need to disconnect the sensor). Replace the sensor or fix the wiring as required. If the sensor and wiring are both good, then the main circuit PCB may have a problem. 11 When the Aux sensor is less than 60ºF. Use the chart on the Aux temperature display: Flashing indicates a probable short circuit in the "SOLAR" sensor or wiring. Use the...
Operation Manual
Page 15
... (water/fire damage, line voltage applied to low voltage terminals, missing parts, etc.) or installed for warranty repair replacement. 12 IN NO EVENT SHALL HAYWARD BE RESPONSIBLE OR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER. The datecode stamped on the web at www.haywardnet.com. Hayward will be free from defects in removal or reinstallation of purchase or the nearest Hayward authorized warranty service center...
... (water/fire damage, line voltage applied to low voltage terminals, missing parts, etc.) or installed for warranty repair replacement. 12 IN NO EVENT SHALL HAYWARD BE RESPONSIBLE OR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER. The datecode stamped on the web at www.haywardnet.com. Hayward will be free from defects in removal or reinstallation of purchase or the nearest Hayward authorized warranty service center...
Operation Manual
Page 16
...688 0.72 620 Division St. All voltage measurements (DC) must be made with the sensor connected to the control and should be accurate to ±1%. Refer to ±0.5ºF. For a given resistance reading, the temperature reading should be accurate to the chart... below for the resistance at 25ºC/77ºF. Elizabeth, NJ 07207 092008F RevG Copyright © 2010 Hayward Inc. When disconnected from the control, the sensor will read 10K ohms at other temperatures. Temperature/Resistance /Voltage All Hayward controls use ...
...688 0.72 620 Division St. All voltage measurements (DC) must be made with the sensor connected to the control and should be accurate to ±1%. Refer to ±0.5ºF. For a given resistance reading, the temperature reading should be accurate to the chart... below for the resistance at 25ºC/77ºF. Elizabeth, NJ 07207 092008F RevG Copyright © 2010 Hayward Inc. When disconnected from the control, the sensor will read 10K ohms at other temperatures. Temperature/Resistance /Voltage All Hayward controls use ...